EEV-KIT
Manual No.
General information '15 t KX-T-241
For single refrigeration system (EEVKIT6-E-C/A) '15 t KX-T-242
Contents
1. What is a multiple refrigeration system .................................................... 2
1.1 Benefit of maltiple refigeration system ................................................. 3
1.2 System control ........................................................................................ 5
1.3 System control A ..................................................................................... 6
1.4 System control B ..................................................................................... 6
1.5 System control C ..................................................................................... 7
1.6 System control D ..................................................................................... 8
2. Component of multiple refrigeration system . .......................................... 9
3. Function of the master . ............................................................................... 16
4. Function of the slave ................................................................................... 31
5. Summary ....................................................................................................... 47
6. Instruction how to replace indoor unit control PCB ................................. 48
- -
'15 • KX-T-243
Advantage
• Large systems are possible
(Over 48 HP for KXE6 or 60 HP for KXZE1 )
• External control
• Capacity step control
S
Additional parts over a single refrigeration system FAN
Master control
• Measurement of ThI-AF, ThI-A
• AHU fan operation input
• ON/OFF control of each slave
control
• Oil return control for connected
S
outdoor units FAN
• External input for system control
S
Slave control
S Slave
• Measurement of ThI-R1,2,3 control
Master
• EEV-Control S Control
- 2-
'15 • KX-T-243
Master EEV-KIT
Master EEV-Control box FAN The master EEV control controls the whole system
Sensor (2pcs) 1. Basic operation can be done by the remote control (RC-E5)
2. Central control including other KXE6 system can be done.
Return air Supply air ( Superlink adaptor SC-ADNA-E is required.)
temperature sensor temperature sensor
ThI-A ThI-AF
Not possible to connect with other normal indoor unit in same Superlink.
3. External input for switching operation mode is available.
Slave EEV-KIT #1
(Input signal is connected to master EEV-Control box)
Slave EEV-Control box
Heat exchanger temperature
Sensor x 3 Sensor (ThI-R1,R2,R3) Outdoor air
EEV x 1 ThI - A Exhaust air
EEV-Set Return air or outdoor air
Strainer Strainer
Superlink adaptor DX Outdoor Outdoor
Slave EEV-KIT #2 Return air AHU Box Box
Slave EEV-Control box
Heat exchanger temperature
Sensor x 3
ThI - AF
Sensor (ThI-R1,R2,R3)
EEV x 1 EEV-Set
Strainer Strainer
Slave EEV-KIT #3
Slave EEV-Control box
Heat exchanger temperature RA SA
Sensor x 3 Sensor (ThI-R1,R2,R3)
EEV x 1 RC-E5 RC-E5
EEV-Set
Strainer Strainer Central control
(SC-SL4N)
1.1Benefi
1.1 Benefit of multiple
t of multiple refrigeration
refrigeration system
system
(1)Large
(1) Large capacity
capacity system system (Different
(Different oil oil
return control) return control)
As per a normal indoor unit, the AHU fan motor must stop during heating mode
oil return operation. However oil return interval depends on each outdoor unit…
S
Oil return control for connected outdoor FAN
units is one of the functions of the master
S
control.
S Slave
control
Over 48HP system is possible. Master
S Control
- 3-
'15 • KX-T-243
(2)External
(2) Externalinput
inputfor
formode
modeselection
selection
The master control has an external input terminal block.
Operation mode control
External input TB2
Operation mode
4-5 6-7
Dry contact
OFF OFF No signal
ON OFF Cooling
OFF ON Heating
ON ON Fan
Emergency stop
Normal Emergency stop
Close
Open
Dry contact
(3)Capacity
(3) Capacitystep
stepcontrol
control
The master control can control total capacity by temperature difference
from set temperature.
Possible to better track target temperature
All ON
Adjustable
1st step
Capacity 2nd step
3rd step
4th step (All OFF)
Set temperature +0.5 +1.0 +1.5 +2.0
Adjustable
- -
'15 • KX-T-243
Set Thermo
System control type EEV control
temperature ON/OFF
System control A: R/A R/A sensor Superheat of indoor
Return air temperature control set by R/C = R/A Set unit heat exchanger
(Same as single refrigeration temperature becomes constant.
system return air temperature (set by R/C) (cooling)
control) Subcool of indoor
System control B: S/A S/A sensor unit heat exchanger
Supply air temperature control set by R/C = S/A Set becomes constant.
temperature (heating)
(set by R/C)
S/A R/A sensor = Supply air
System control C: set by R/C S/A Set temperature
Supply air temperature control temperature becomes constant.
+3deg.C
System control D: S/A R/A sensor =
Supply air temperature control set by PCB R/A Set
(Same as single refrigeration R/A temperature
system supply air temperature set by R/C (set by R/C)
control)
- -
'15 • KX-T-243
Thermo ON/OFF control is done by R/A temperature (or R/C sensor) and set
temperature by remote control (R/C).
Thermo ON/OFF control is done by S/A temperature and set temperature by remote
control (R/C).
- -
'15 • KX-T-243
Flow Flow
ThI-R2 ThI-R1 ThI-R3 ThI-R2 ThI-R1 ThI-R3
SH = Constant SH SH = Constant SH
OFF ON
Outdoor air te
mperature
EEV
Step
control
Time
- -
'15 • KX-T-243
When R/A temperature becomes set S/A temperature + 3deg.C =Thermo OFF
Cooling
OFF ON
Outdo
or air
tempe
Temperature rature
3deg.C
R/C set S/A temperature Supply air temperature
EEV pulse
EEV
Step
control
Time
- -
'15 • KX-T-243
EEV
SH SH
Time
Strainer
ThI-A ThI-AF ThI-R2
ThI-R1 ThI-R3
2 or more refrigeration systems
are connected to 1 air handling
Slave ThI-R3
O/U Address ThI-R2
unit system which has 2 or
01
EEV-Control I/U Address 01 ThI-R1 more direct expansion heat
exchanger coils.
01
05 FAN
ThI-A ThI-AF Signal line
03
09
Master
EEV-Control 03
13
RC-E5
RC
- 9-
'15 • KX-T-243
The master control PCB and slave control PCB are supplied as an EEV-Control box.
They should be installed in the control box of the air handling unit.
Example of layout : 1 master control box and 6 slave control boxes
R/C
Power cable
Sensor wiring
External control
Superlink signal wiring
Remote control wiring
External input signal wiring
Duct for sensor wire Signal wire Duct for power cable
The two air sensors (ThI-A, ThI-AF) in the slave EEV -Control ASSY are
not required.
- 10 -
'15 • KX-T-243
EEVKIT6-E-M/A EEVKIT6-E-C/A
EEV-Control box EEV-Control box
Sensor (2pcs) Sensor (3pcs)
- 11 -
'15 • KX-T-243
Parts of EEV-set
Model Name
Part name Part No. EEV6-71-E EEV6-160-E EEV6-280-E
EEV6-71-E/A EEV6-160-E/A EEV6-280-E/A
VALVE, BODY (EXP) SSA387F047A 1
VALVE, BODY (EXP) SSA387F045 1
VALVE, BODY (EXP) SSA387F049A 1
STRAINER SSA357A005B 1 1 1
STRAINER SSA357A005T 1 1
STRAINER SSA357A005AC 1
COIL, SOLENOID PCH387F002 1
COIL, SOLENOID PCH387F002A 1 1
These parts are the same as KXE6 indoor units.
7- segment display
- 12 -
'15 • KX-T-243
The setting for the outdoor unit is required for it to KXE6 4–6HP P54
recognize the multiple refrigeration system. KXE6 8–12HP P54
KXE6 14HP– P58
Setting method -
1. Select P54/P58/P68 of 7-segment using SW8 and SW9. KXRE6 P54
2. Push SW7 more than 3 seconds. KXZE1 P68
3. 7-segment display right side starts blinking.
(If there is no operation for more than 10 seconds, it goes back to normal
display and changed setting is cancelled.)
4. Push SW8 to change from “0” to “1”. (factory setting is “1”.)
5. Push SW7 more than 3 seconds.
The setting is memorized in the EEPROM. 7-segment setting part 7-segment data part
Outdoor unit software change might be required.
SW8 / SW9
SW7 (write data / delete data)
- 13 -
'15 • KX-T-243
1. Select 7-segment code according outdoor unit model by using SW8 and SW9.
2. Push SW7 (Data setting/deleting) more than 3 seconds.
3. 7-segment right side starts blinking. (Every 0.5 seconds)
(If there is no operation for more than 10 seconds, it goes back to normal display and
changed setting is cancelled.)
4. Push SW8 (ones digit) and select the adjusting valuefrom standard value.
Cooling (Standard value is 0.83MPa (5℃) in STANDARD mode
1.05MPa (12℃) in TYPE1 mode)
0.00 → 0.01 → 0.02 ....... → 0.50 → –0.30 → –0.29 → ...... → –0.01 → 0.00
Heating (Standard value is 2.75MPa(47℃) in STANDARD mode
1.77MPa(30℃) in TYPE1 mode)
0.00 → 0.10 → 0.20 ....... → 0.70 → –0.90 → –0.80 → ...... → –0.10 → 0.00
5. Display the required adjusting pressure, then push SW7 for 3 seconds.
The setting is memorized in EEPROM.
6. Confirm the setting by selecting 7-segment code again.
Example1 Example2
1. FDC400KXE6 1. FDC450KXE6
2. Air-conditioning mode 2. OA processing mode
3. Target condensing temperature is 40℃ 3. Target evaporating temperature is 8℃
High pressure in heating 2.35 MPa Cooling pressure in cooling
↓
0.92 MPa
↓ ↓
1. Select C73 1. Select C72
2. Select “– 0.40” 2. Select “– 0.13”
(=2.35 – 2.75) (= 0.92 –1.05 = – 0.13)
- 14 -
'15 • KX-T-243
- 15 -
3. Functions of the master
240 4-φ6
18
8
Label model name
Wiring label
307
275
321
(The back)
10
-
215
16 -
212
Notes
(1)This control box is not waterproof.
Please do water or dust does not fall within the box.
(2)Mounting of the box, use the four holes shown in the figure, please firmly attached.
Thermistor for return air
Please check after local attached so as not to come off by vibration. Black
(3)Wiring connected to the terminal block. Please fix tie wrap included in the control box outside. THI-A CNH
1
Please make sure that you also pull the wiring not to apply direct tension to the terminal block.
It should be noted that the holes in the tie wrap to secure the control box outside, 8000
there are two places to be able to respond flexibly to local wiring direction. Please use either,
depending on usage.
PCH000Z417
(4)Label model name is located on the side of the left side of the control box.
Thermistor for supply air
'15 • KX-T-243
(5)Wiring diagram is located on the back of the lid.
In addition, if you do not use the lid of the control box, please use wiring diagram that comes with the Yellow
control box. THI-AF 1
2
CNF
(It comes with the same as the connection nameplate you have pasted on the back of the control box lid.)
(6)You will need a gap at the top to the desorption of the lid of the control box.
(If you want to install this box, please ensure a gap of about 15mm in the box top.)
8000
※3 ※2
CNF
※1
Hole for power source line
(AC220-240V 50Hz,
AC220V 60Hz)
※1
SW7
Hole for communication line
J1
(Remote control X and Y
SW5
SW6
Signal line A and B)
-
※1 ※1
(ThI-A, ThI-AF)
Not use
※1 ※1
Notes
(1)This page is shown by removing the lid.
Wiring diagram has been pasted to the back
PCH000Z417
'15 • KX-T-243
please managed so as not to lose to store
wiring diagram in an accessory.
(2)※1 is hole for accessory band for fixing the
site wiring.
(3)※2 is a connector to be connected to ThI-A.
(4)※3 is a connector to be connected to ThI-AF.
240 4-䃥6
7.5 225
(Local mounting holes) (67)
16
8
CNF
302
275
SW7
J1
SW5
SW6
-
18 -
Notes
(1)When removing the sheet metal around, please
note the internal wiring.
Please do not attempt to hurt or cut the wiring.
(2)After connecting the local wiring, please confirm
that to take direct tension to the terminal block
and the connector of printed circuit board(PCB).
PCH000Z417
'15 • KX-T-243
・Since the high-temperature parts and the high-voltage
parts is exposed, please make sure that you are not in
contact with the wiring.
・The upper part of the high-temperature parts and the
high-voltage parts is required gap(air layer), please ensure
the more than 90mm(the same height as the MHI's box).
'15 • KX-T-243
Input
Input emergency stop
operation mode ThI-A ThI-AF TrI Free cooling
Connector for branching AC220V-240V
control of heat recovery t° t°
3-pipe system
CNU
TB2 4 5 6 7 8 9 CND1
Power source line
BL
WH
between indoor units
RD
YE
YE
19V 24V
GY
GY
RD
RD
BR
BR
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
AC220-240V 50Hz,
Prepare on site
AC220V 60Hz Control PCB 1 2 3 4 5 6 1 2 1 2 CNW1 CNW2 1 2
+12 1
Power source TB1 CNN CNH CNF CND
(Operation)
WH BK
Single-phase YE BK YE BL 2 XR1
(Heating)
RD 3
Power L RD J1 CNT 3 XR2
source
line N WH
F(3.15A) 1
WH BL 4 XR3 (Compressor ON)
F(3.15A) RD
CNW0
X6 X2 X4 SW5
SW1 SW2 LED・2 5 XR4 (Inspection)
JSL1 6
X1 Superlink(spare) XR5 (Remote operation input:volt-free contact)
Earth
YE/GN X3 SW6 SW3 SW4 LED・3 BK
CNK2
BK
+12 1 10
SW7 BL
2 11
CNT2 3
RD
BR
12 Other output
CNB CNK1 4
OR
13
CNM3 1 CNR 1 3 CNA RD WH WH
CNI RD
WH 3 5 7 9 WH
BL 1 2 3 4 5 6 1 3 1 2 5 14
TB2
WH
WH
RD
RD
RD
RD
BR
BK
BK
BL
BL
TB2 15 16 TB3 X Y A B
BR
TB2 1 2
SL connection
slave control
Output 15 16 TB2 X Y CNB
Remote
AHU fan motor control
t° Thc X Y
Fan motor
error signal SW8 SW9
TB2
FAN
- 19 -
'15 • KX-T-243
Closed
Close Open
This table shows the summary of terminals and external inputs and outputs.
Terminal Function Specification Note
Terminal size
TB1 Power source terminal block AC300V, 25A
M4
TB2 1,2 Output: fan AC230V, 1A
4,5 Terminal size
Input: Operation mode change Dry contact
6,7 M3.5
8,9 Input: Emergency stop Dry contact
11 Output: Cooling operation DC12V
AC600V 15A
12 Output: Defrost operation DC12V CNT2 :
13 Output: Oil return operation DC12V Max 160mA in total
14 Output: Return temperature is below 0deg.C DC12V
Terminal size
15,16 Input: AHU anomaly Dry contact
M3.5
TB3 Remote control/ Superlink line
Relay capacity: DC12V Same as normal
CNT External control
max 160mA at total use KX indoor
CND Free cooling Output Relay capacity: DC12V max 75mA
Operation mode
Connector TB2
External input No signal Cooling Heating Fan
for operation mode CNN1, 2 4, 5 0 1 0 1
CNN3, 4 6, 7 0 0 1 1
0 : Open (OFF), 1: Short (ON)
- 20 -
'15 • KX-T-243
This table shows the DIP-SW settings, and the symbol meanings in the wiring diagrams.
CNA-Z Connector
F Fuse
FS Float switch
JSL1 Spare Superlink terminal setting (for spare)
LED・2 Indication lamp (Green-Normal operation)
LED・3 Indication lamp (Red-Inspection)
SM Stepping motor (for electronic expansion valve)
SW1 Supply air temperature setting at system control D in cooling mode
SW2 Changing the temperature interval for multiple step control in heating mode
SW3 Supply air temperature setting at system control D in heating mode
SW4 Changing the temperature interval for multiple step control in heating mode
SW5-1, 2 Multiple step control (☆OFF)
SW6-1, 2 Automatic operation valid/invalid and switching operation pattern (☆OFF)
SW6-3 Hot start control (☆ON)
SW6-4 Medium temperature cooling setting (☆OFF)
SW7-1 Check indoor fan operation (☆OFF)
SW7-2, 3 Switching return/supply air temperature control (☆OFF) ※1
SW7-4 1fan tap/3fan tap (☆OFF/ON)
J1 Setting of indoor fan control during defrost operation (☆Short)
TB1 Terminal block (Power source line) (□mark)
TB2 Terminal block (Relay connect) (□mark)
TB3 Terminal block (Signal line)(□mark)
Thc Thermistor (Remote control)
ThI-A Thermistor (Return air)
ThI-AF Thermistor (Supply air)
ThI-R1, 2, 3 Thermistor (Heat exchanger)
TrI Transformer
X1~3, 6 Relay for FM
■mark Closed-end connector
☆Factory default
※ 1 You must also configure the slave EEV-KIT.Refer to the technical documentation of slave EEV-KIT how to set.
When the multiple refrigeration system is in use, it is necessary to set it with the outdoor unit control.
Refer to the technical documentation.
- 21 -
'15 • KX-T-243
SW1-SW4
• SW1-SW4 are not for the address setting of the master EEV-Control box.
• The address of the master EEV-Control box is fixed [00].
Operation
Switch Function
mode
Target S/A temperature setting
SW1 Rotary switch (Blue)
for system control D
Cooling
Temperature interval
SW2 Rotary switch (Blue)
for multiple step control
Target S/A temperature setting
SW3 Rotary switch (Green)
for system control D
Heating
Temperature interval
SW4 Rotary switch (Green)
for multiple step control
- 22 -
'15 • KX-T-243
- 23 -
'15 • KX-T-243
Step number
Step number
4 3 4 3
3 2 3 2
2 1 2 1
1 0 1 0
0 -1 0 -1
Time Time
Adjustable
- 24 -
'15 • KX-T-243
When SW7-2 of the slave PCB is ON, the heating target supply air temperature
becomes +15deg.C. (Range becomes 31deg.C to 45deg.C)
- 25 -
'15 • KX-T-243
Fan mode Cooling mode Fan mode Cooling mode Fan mode Cooling mode
- 26 -
'15 • KX-T-243
3.9 SW7
★Factory default
Switch Function ON/OFF Setting
★OFF Invalid
SW7-1 Check indoor fan operation
ON Valid
SW7-2 Switching return/supply ★OFF/ON
As per setting
SW7-3 air temperature control ★OFF/ON
★OFF 1 fan step
SW7-4 1 fan step/ 3 fan step
ON 3 fan step
• SW7-1 is used for the operation check of indoor fan, before connecting the
refrigeration piping.
• The indoor fan can operate by switching SW7-1 ON.
• (This function is useful to check the AHU fan operation without the outdoor unit)
• SW7-4 can change from 1 fan step to 3 fan step, but requires wiring adjustment.
- 27 -
'15 • KX-T-243
- 28 -
'15 • KX-T-243
Terminal block
Connector Function Remarks
TB2
CnN1,2 Switching operation mode See following table
4, 5, 6, 7
CnN3,4 6P (Cooling, Fan, Heating) for details
CnN5,6 Emergency stop 8, 9
Overcurrent anomaly
CnI 2P 15, 16
of fan motor
- 29 -
'15 • KX-T-243
- 30 -
Thermistor for heat exchanger 4-φ6
THI-R2 CNN
3
18
4
THI-R3
5
8
8000
Label model name
Thermistor for return air
Black
THI-A 1
CNH
Wiring label
307
275
2
321
(The back)
8000
2
CNF
8000
10
-
215
31 -
27.2
Leaf spring
Thermistor holder* 212
Thermistor for
heat exchanger
Notes
Discrimination tape
With/Without (1)This control box is not waterproof.
Please check after local attached so as not to come off by vibration.
(3)Wiring connected to the terminal block. Please fix tie wrap included in the control box outside.
*Thermistor holder : Provided locally Please make sure that you also pull the wiring not to apply direct tension to the terminal block.
It should be noted that the holes in the tie wrap to secure the control box outside,
φ
24 there are two places to be able to respond flexibly to local wiring direction. Please use either,
depending on usage.
PCH000Z418
Thermistor φ Material
For ThI-R3 (4)Label model name is located on the side of the left side of the control box.
'15 • KX-T-243
φ9.52×0.6t
Copper tube
For ThI-R1,-R2 φ8.0×0.6t (5)Wiring diagram is located on the back of the lid.
In addition, if you do not use the lid of the control box, please use wiring diagram that comes with the
control box.
(It comes with the same as the connection nameplate you have pasted on the back of the control box lid.)
(6)You will need a gap at the top to the desorption of the lid of the control box.
(If you want to install this box, please ensure a gap of about 15mm in the box top.)
※3 ※6 ※2 ※4
CNF
※1
Hole for power source line
(AC220-240V 50Hz,
AC220V 60Hz)
Wiring hole for total
※1
SW7
enthalpy heat exchanger
J1
SW5
SW6
-
※1 ※1
※5(WHITE CONNECTOR)
Not use
Notes
(1)This page is shown by removing the lid.
Wiring diagram has been pasted to the back
of the lid. If you do not want to use the lid,
please managed so as not to lose to store
wiring diagram in an accessory.
PCH000Z418
'15 • KX-T-243
site wiring.
(3)※2 is a connector to be connected to ThI-A.
(4)※3 is a connector to be connected to ThI-AF.
(5)※4 is a connector to be connected to ThI-R1,R2,R3.
(6)※5 is a connector to be connected to FS.
(7)※6 is a connector to be connected to SM.
240 4-䃥6 (67)
7.5 225 (Local mounting holes)
16
8
CNF
302
275
SW7
J1
SW5
SW6
-
33 -
Notes
(1)When removing the sheet metal around, please
note the internal wiring.
Please do not attempt to hurt or cut the wiring.
(2)After connecting the local wiring, please confirm
that to take direct tension to the terminal block
and the connector of printed circuit board (PCB).
(3)If you want to use by removing the plate around as shown
PCH000Z418
'15 • KX-T-243
・Since the high-temperature parts and the high-voltage
parts is exposed, please make sure that you are not in
contact with the wiring.
・The upper part of the high-temperature parts and the
high-voltage parts is required gap (air layer), please ensure
the more than 90mm (the same height as the MHI's box).
Wiring diagram of slave EEV
Single refrigeration system
ThI-R1 ThI-R2 ThI-R3 ThI-A ThI-AF
t° t° t° t° t° TrI Free cooling
Connector for branching AC220V-240V
controller of heat recovery
3-pipe system CND1
Power source line CNU
between indoor units BL
YE
YE
19V 24V
GY
GY
RD
RD
BR
BR
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
AC220-240V 50Hz, Prepare on site
WH
RD
AC220V 60Hz Control PCB 1 2 3 4 5 6 1 2 1 2 CNW1 CNW2 1 2
+12 1
RD
Power source TB1 CNN CNH CNF CND
(Operation)
WH BK
Single-phase YE BK YE BL 2 XR1
(Heating)
RD 3 7 8
Power L RD CNT 3
YE
XR2
source
line N
F(3.15A)
WH 1 SW5
SW1 SW2 LED・2 BL 4 XR3 (Compressor ON)
WH
F(3.15A) CNW0
RD X6 X2 X4
JSL1
5 XR4 (Inspection)
SW6 Superlink(spare)
XR5 (Remote operation input
6
WH
SW3 SW4 LED・3
RD
CNK2
YE/GN X1 X3
Earth SW7
BK :volt-free contact)
For heat recovery 3-pipe system
+12 1
2 XB1 (20S)
CNT2 3 XB2 (SVH)
RD
CNB CNK1 4 XB3 (SVG)
7 CNI BL CNA RD (SVE)
-
WH WH 5 XB4
51X1 CNM3 1 3 5 7 9
CNR 1 3 1 2 1 2 3 4 5 6 1 3 1 2
WH WH
34 -
3 3 3 8
52X1 52X2 XR2 C UH H M L
WH
WH
WH
OR
RD
RD
RD
RD
BR
YE
BK
BL
BL
5 5 5 <5> <6>
<1> <2> <7> <8> <3> <4>
WH X Y A B
RD
BR
BK
BL
F(0.16A) 1 TB3
WH
YE
YE
YE
YE
YE
YE
1 2 7 8 3 4 5 6 TB2 51X1
WH
5
CNR2 M
BR
X Y
BL
BL YE YE To outdoor unit
RD
7 7 Signal line
SM Remote (Shielded cord)
52X1 52X2 M CNI2 control
8 8 1∼ WH 1 2 (RC−E4)
Heat exch (air) Heat exch (air) Humidifier Fan motor DM
Thc
Hi operation Lo operation operation error signal t°
RC−E4:single only
PCH000Z420
'15 • KX-T-243
'15 • KX-T-243
- 35 -
'15 • KX-T-243
- 36 -
'15 • KX-T-243
Refrigerant Refrigerant
01 system (*)
Indoor address
system (* )
Indoor address
* In ( ) shows
No.1 (01) 01, 02, 03, 04 No.5 (05) 17, 18, 19, 20 examples of
SW1 SW2 outdoor unit
No.2 (02) 05, 06, 07, 08 No.6 (06) 21, 22, 23, 24
No.3 (03) 09, 10, 11, 12 No.7 (07) 25, 26, 27, 28 address as
No.4 (04) 13, 14, 15, 16 No.8 (08) 29, 30, 31, 32
single use
- 37 -
'15 • KX-T-243
Refrigerant Refrigerant
Slave address Slave address
system (*) system (*)
No.1 (01) 01, 02, 03, 04 No.5 (05) 17, 18, 19, 20
No.2 (02) 05, 06, 07, 08 No.6 (06) 21, 22, 23, 24
No.3 (03) 09, 10, 11, 12 No.7 (07) 25, 26, 27, 28
No.4 (04) 13, 14, 15, 16 No.8 (08) 29, 30, 31, 32
6-step control 01 02 03 04 05 06 ON
OFF
6 refrigeration system 01 05 09 13 17 21
- 38 -
'15 • KX-T-243
EEV-SET
04
<Example 3>
Slave EEV-Control x 4 03
4-step control 02
4 refrigeration system
Outdoor unit
Master PCB 01
Address
SW5-1 SW5-2 Slave
EEV-Control
ON O/U Address 04
OFF I/U Address 13
03
ThI-A FAN ThI-AF
09
Signal line
SW5 02
All slave PCB 05
Master
SW5-1 SW5-2
EEV-Control 00 ThI-R3
ON 01 Th
ThI-R2
OFF 01 TThI-R1
Don’t forget to switch
SW5-1 of slave EEV-
Control box to ON
R/C
Slave EEV-Control x 8 01 03 01 03 ON
OFF
OFF
4-step control 01 09 02 10
4 refrigeration system 02 04 02 04 Master PCB
SW5-1 SW5-2
05 13 06 14 ON
OFF
<Example 6> 1st step 2nd step 3rd step 4th step 5th step 6th step 7th step 8th step
Slave EEV-Control x 8
01 02 03 04 01 02 03 04
8-step control
01 05 09 13 02 06 10 14
4 refrigeration system
<Example 7> 1st step 2nd step 3rd step 4th step 5th step 6th step Master PCB
SW5-1 SW5-2
Slave EEV-Control x 12 01 03 05 01 03 05 ON
OFF
6-step control 01 09 17 02 10 18
6 refrigeration system
02 04 06 02 04 06
05 13 21 06 14 22
- 39 -
'15 • KX-T-243
13 29 14 30 ON
01 Slave box address: OFF
<Example 9> 1st step 2nd step 3rd step 4th step 5th step 6th step 7th step 8th step
Slave EEV-Control x 16 01 03 05 07 01 03 05 07
8-step control 01 09 17 25 02 10 18 26
8 refrigeration system
02 04 06 08 02 04 06 08
05 13 21 29 06 14 22 30
SW5-1 SW5-2 ON
6-step control ON
1st step 2nd step 3rd step 4th step OFF
- 40 -
'15 • KX-T-243
<Example 11 >
07 (08)
EEV-SET×4
EEV-SET×4
03 (04)
01 01 01 01
EEV-SET×4 01 02 03 04
09 (10)
EEV-SET×4
05 (06)
03 03 03 03
05 06 07 08
Master PCB FAN ThI-AF
SW5-1 SW5-2 ThI-A
ON
OFF 05
05 05 05 Signal line
09 10 11 12 All slave PCB
ThI-R3 SW5-1 SW5-2
SW5 T
ThI-R2 ON
ThI-R1
T OFF
00 07 07 07 07
13 14 15 16 Slave
EEV- Control
Master
EEV-control
RC 09 09 09 09 Outdoor unit address
RC-E4 17 18 19 20 I/U Address
1-Step 3-Step
2-Step 4-Step
4-step control 01 02 03 04
6 refrigeration system 02 02 02 02
05 06 07 08
03 03 03 03
Master PCB 09 10 11 12
SW5-1 SW5-2
ON 04 04 04 04
OFF
13 14 15 16
05 05 05 05
01 Outdoor unit address
17 18 19 20
01 Slave box address:
06 06 06 06
21 22 23 24
- -
'15 • KX-T-243
1st step 2nd step 3rd step 4th step 5th step 6th step
<Example 13> 01 05 03 01 05 03
Slave EEV-Control x 24 01 17 10 03 19 12
6-step control 02 06 04 02 06 04
6 refrigeration system 05 21 14 07 23 16
03 01 05 03 01 05
09 02 18 11 04 20
04 02 06 04 02 06
13 06 22 15 08 24
01 Outdoor unit address
Master PCB
01 Slave box address:
SW5-1 SW5-2
All slave PCB
SW5-1 SW5-2
ON
ON
OFF OFF
1st step 2nd step 3rd step 4th step 5th step 6th step 7th step 8th step
01 04 01 04 01 04 01 04
01 13 02 14 03 15 04 16
02 05 02 05 02 05 02 05
05 17 06 18 07 19 08 20
03 06 03 06 03 06 03 06
09 21 10 22 11 23 12 24
- 42 -
'15 • KX-T-243
3rd step
01 02 03 04 05 06 07
Master PCB
SW5-1 SW5-2
03 07 11 15 19 23 27
ON
OFF 4th step
01 02 03 04 05 06 07
04 08 12 16 20 24 28
<Example 16> 1st step 2nd step 3rd step 4th step 5th step 6th step
Slave EEV-Control x 30 01 06 03 08 05 03
6-step control 01 21 10 30 19 12
8 refrigeration system 02 07 04 01 06 04
05 25 14 03 23 16
All slave PCB Master PCB
SW5-1 SW5-2 SW5-1 SW5-2 03 08 05 02 07 05
ON
ON 09 29 18 07 27 20
OFF OFF
04 01 06 03 01 06
13 02 22 11 04 24
01 Outdoor unit address 05 02 07 04 02 07
01 Slave box address:
17 06 26 15 08 28
- 43 -
'15 • KX-T-243
01 02 03 04 05 06 07 08
1st step
01 05 09 13 17 21 25 29
All slave PCB
SW5-1 SW5-2
ON 2nd step 01 02 03 04 05 06 07 08
OFF 02 06 10 14 18 22 26 30
Master PCB
3rd step
01 02 03 04 05 06 07 08
SW5-1 SW5-2
ON
03 07 11 15 19 23 27 31
OFF
4th step
01 02 03 04 05 06 07 08
04 08 12 16 20 24 28 32
(Note) These rules for setting the slave box address must be followed as
per the examples 1 - 18 shown or error code “E18” will occur.
- 44 -
'15 • KX-T-243
- 45 -
'15 • KX-T-243
0.013
%0)
13
8
y (2 0.012
12
i[d%i]t
0.9
11
m
7
H 0.011
huR
2
10
e度
tiv湿 0.010
6
Re相
8
0.009
5
0.008
6
4
Humidifying
0.007
Bo
4
3
10
xv
0.006
2
1
olu
0.005
0
0 .9
-1
me
0.004
-2
1
-3
(m
-4
0.003
3
0.002
/kg
)
0.001
0.000
-5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45
Dry-bulb
乾球温度 Temperature
DB [℃] ( ℃)
+15deg.C
0 .8
0 .8
0.8
0 .8
0 .8
0 .8
0.8
0.8
0.9
0.7
0.7
0.7
0 .7
0
6
- 46 -
'15 • KX-T-243
5. Summary
1. Multiple refrigeration systems use 1 master EEV-Control box with multiple slave
EEV-Control boxes.
2. Superlink adaptor SC-ADNA-E is needed to connect with central controls.
3. 4 temperature control systems are available.
4. Outdoor unit 7-segment setting is required.
5.The number of slave control boxes are regulated. Slave control box Superlink
addresses are also allotted.
6. Step control of slave control boxes is available.
7.Depending on installation, the fan stop function during defrost operation can be
cancelled.
8. All slave control boxes must be changed to the same settings.
(especially don’t forget SW5-1 ON)
- 47 -
●
●
'15 • KX-T-243
SAFETY PRECAUTIONS
● Read the "SAFETY PRECAUTIONS" carefully first of all and then strictly follow it during the replacement in order to protect yourself.
● The precautionary items mentioned below are distinguished into two levels, WARNING and CAUTION.
Both mentions the important items to protect your health and safety so strictly follow them by any means.
WARNING Wrong installation would cause serious consequences such as injuries or death.
CAUTION Wrong installation might cause serious consequences depending on circumstances.
● After completing the replacement, do commissioning to confirm there are no abnormalities.
WARNING
● Replacement should be performed by the specialist.
If you replace the PCB by yourself, it may lead to serious trouble such as electric shock or fire.
● Replace the PCB correctly according to these instructions.
Improper replacement may cause electric shock or fire.
● Shut off the power before electrical wiring work.
Replacement during the applying the current would cause the electric shock, unit failure or improper running. It would cause the damage of connected equipment such as fan motor,etc.
● Fasten the wiring to the terminal securely, and hold the cable securely so as not to apply unexpected stress on the terminal.
Loose connections or hold could result in abnormal heat generation or fire.
● Check the connection of wiring to PCB correctly before turning on the power, after replacement.
Defectiveness of replacement may cause electric shock or fire.
CAUTION
● In connecting connector onto the PCB, connect not to deform the PCB. It may cause breakage or malfunction.
● Insert connecter securely, and hook stopper. It may cause fire or improper running.
● Bundle the cables together so as not to be pinched or be tensioned. It may cause malfunction or electric shock for disconnection or deformation.
①Check the model type ②Set to an appropriate address and function using switch on PCB.
Setting according to the model *1
Applicable model
I/U FAN LOUVER SW
Select the same setting with the removed PCB.
EEVKIT3-M
Applied differently depending on the model set.
HI INVALID For more information please see also the back side.
EEVKIT6-E-M
④Control PCB
CNW1(White)
Primary transformer SW5 CNW2(Black)
Secondary transformer
CNM3(White)
CNB(White)
Fan motor
Remote control
CNG(Blue)
CNK1(White)
Superlink
CNE(White) CND(Black)
CNR(White) RAM checker Free cooling
CNA(Red)
CNJ(White)
CNF(Yellow)
CNV(Black)
CNH(Black)
CNT2(Red)
(Return air)
CNZ(White)
(Air supply)
CNS(Blue)
Thermistor
CNT(Blue)
Thermistor
CNO(Red)
CNI(Blue)
(Yellow)
Auto lift
(White)
CNQ
CNN
- 48 -
'15 • KX-T-243
- 9 -
ThI-A ThI-AF Meaning of marks
Free cooling Mark Parts name
t° t° TrI CNA−Z Connector
AC220V-240V F Fuse
TB2 4 5 6 7 8 9 CND1 FS Float switch
Power source line JSL1 Spare Superlink terminal setting(for spare)
between indoor units
YE
YE
J1 Setting of indoor fan control during defrosting(☆Short)
19V 24V
GY
GY
RD
RD
BR
BR
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
AC220-240V 50Hz, LED・2 Indication lamp(Green-Normal operation)
Prepare on site
AC220V 60Hz Control PCB 1 2 3 4 5 6 1 2 1 2 CNW1 CNW2 1 2
+12 1 LED・3 Indication lamp(Red-Inspection)
Power source TB1 CNN CNH CNF CND
(Operation)
WH BK SM Stepping motor(for electronic expansion valve)
Single-phase YE BK YE BL 2 XR1
(Heating)
RD 3 SW1 Supply air temperature setting at system control D in cooling mode
Power L RD J1 CNT 3 XR2
(Compressor ON)
source F(3.15A) BL 4 SW2 Changing the temperature interval for
line N WH WH 1 XR3 multiple step control in cooling mode
F(3.15A) CNW0
RD X6 X2 X4 SW5
SW1 SW2 LED・2 5 XR4 (Inspection) SW3 Supply air temperature setting at system control D in heating mode
JSL1 6
X1 Superlink(spare) XR5 (Remote operation input:volt-free contact) SW4 Changing the temperature interval for
Earth
YE/GN X3 SW6 multiple step control in heating mode
SW3 SW4 LED・3 CNK2 +12 1
BK
10 (+12V,common) SW5-1,2 Multiple step control(☆OFF)
BK
SW7 BL SW6-1,2 Automatic operation valid/invalid and
2 11 Output during cooling operation
switching operation pattern(☆OFF)
BR
CNT2
RD
3 12 Output during defrosting operation for one or more refrigeration systems SW6-3 Hot start control(☆ON)
CNB CNK1 4
OR
13 Output when any one of refrigeration systems starts oil return operation SW6-4 Medium temperature cooling setting(☆OFF)
CNM3 CNR CNA RD WH WH
CNI RD SW7-1 Check indoor fan operation(☆OFF)
WH 1 3 5 7 9 WH 1 3 BL 1 2 3 4 5 6 1 3 1 2 5 14 Output when the return air temperature becomes below 0°C
SW7-2,3 Switching return/supply air temperature control(☆OFF)※1
TB2 Coil maximum capacity:160mA(DC12V)
WH
WH
SW7-4 1 fan tap/3 fan tap(☆OFF/ON)
RD
RD
RD
RD
BR
BK
BK
BL
BL
TB1 Terminal block(Power source line)(□mark)
TB3 X Y A B
BR
TB2 15 16 TB2 Terminal block(Relay connect)(□mark)
TB3 Terminal block(Signal line)(□mark)
TB2 1 2 Signal line Thc Thermistor(Remote control)
(Only slave EEV-KIT) ThI-A Thermistor(Return air)
X Y ThI-AF Thermistor(Supply air)
Notes 1. indicates wiring on site. Remote
ThI-R1,2,3 Thermistor(Heat exchanger)
2. Use twin core cable(0.75-1.25mm2)at signal line between indoor unit 15 16 TB2 control TrI Transformer
X1−3,6 Relay for FM
and outdoor unit, and signal line between indoor units. t° Thc ■mark Closed-end connector
☆ Factory default
3. Terminal A B are signal terminal.(DC5V) ※1 You must also configure the slave EEV-KIT. Refer to the
4. Use twin core cable(0.3mm2) at remote control line. See spec sheet Fan motor
technical documentation of slave EEV-KIT how to set.
When the multiple refrigeration system is in use, it is
-
of remote control in case that the total length is more than 100m. error signal
Error code indoor unit
necessary to set it with the outdoor unit control.
Refer to the technical documentation.
5. Do not put signal line and remote control line alongside power source line.
50 -
'15 • KX-T-243
TB2 8,9 Input for emergency stop
Connector: Made by Molex 5264-06
CNT 6P Output for operation mode Relay capacity,DC12V,max 160mA at total use
Terminal: Made by Molex 5263T
CNT2 Output for mode select(Cooling,Defrost,Oil return on cooling, Relay capacity,DC12V,max 160mA at total use
5P
Return air temp.0degC)
CND 2P Output for free cooling Relay capacity,DC12V,max 160mA at total use Connector includes control unit
CNI 2P Input for indoor unit error signal DC5V,max 2mA
'15 • KX-T-243
SAFETY PRECAUTIONS
● Read the "SAFETY PRECAUTIONS" carefully first of all and then strictly follow it during the replacement in order to protect yourself.
● The precautionary items mentioned below are distinguished into two levels, WARNING and CAUTION.
Both mentions the important items to protect your health and safety so strictly follow them by any means.
WARNING Wrong installation would cause serious consequences such as injuries or death.
CAUTION Wrong installation might cause serious consequences depending on circumstances.
● After completing the replacement, do commissioning to confirm there are no abnormalities.
WARNING
● Replacement should be performed by the specialist.
If you replace the PCB by yourself, it may lead to serious trouble such as electric shock or fire.
● Replace the PCB correctly according to these instructions.
Improper replacement may cause electric shock or fire.
● Shut off the power before electrical wiring work.
Replacement during the applying the current would cause the electric shock, unit failure or improper running. It would cause the damage of connected equipment such as fan motor,etc.
● Fasten the wiring to the terminal securely, and hold the cable securely so as not to apply unexpected stress on the terminal.
Loose connections or hold could result in abnormal heat generation or fire.
● Check the connection of wiring to PCB correctly before turning on the power, after replacement.
Defectiveness of replacement may cause electric shock or fire.
CAUTION
● In connecting connector onto the PCB, connect not to deform the PCB. It may cause breakage or malfunction.
● Insert connecter securely, and hook stopper. It may cause fire or improper running.
● Bundle the cables together so as not to be pinched or be tensioned. It may cause malfunction or electric shock for disconnection or deformation.
①Check the model type ②Set to an appropriate address and function using switch on PCB.
Setting according to the model *1 Select the same setting with the removed PCB.
Applicable model
I/U FAN LOUVER SW Applied differently depending on the model set.
SAF-DXP、SAF-DX-6 For more information please see also the back side.
HI
EEVKIT3-C INVALID
EEVKIT6-E-C HI-MID
1 There is a unit having plural applicable PCB depending on a model.
2 Set the function setting corresponding the spare PCB
3 Do "Setting according to the model *1" refer to "⑥Function setting
of wired remote control" after turning on the power source when
CNW1(White)
CNW2(Black)
Primary transformer
Secondary transformer
SW5
CNB(White)
CNM3(White) Remote control
Fan motor
CNG(Blue) CNK1(White)
Superlink
CNK2(Black)
CNJ2(Blue) SW6 SW7 Superlink(spare)
CND(Black)
CNR(White) CNE(White) Free cooling
Drain pump RAM checker
CNA(Red)
Expansion valve
CNJ(White)
CNH(Black)
CNZ(White)
CNQ(White)
(Return air)
CNV(Black)
CNT2(Red)
(Air supply)
Thermistor
Thermistor
CNO(Red)
CNS(Blue)
CNT(Blue)
CNI(Blue)
Branching
controller
Float SW
(Yellow)
(Yellow)
Heater
Option
CNF
CNN
HA
- 51 -
'15 • KX-T-243
- 2 -
Single refrigeration system Meaning of marks
ThI-R1 ThI-R2 ThI-R3 ThI-A ThI-AF Mark Parts name
Single refrigeration system Multiple refrigeration system
t° t° t° t° t° TrI Free cooling
CNAーZ Connector Connector
DM Drain motor Drain motor
Connector for branching AC220V-240V F Fuse Fuse
controller of heat recovery
3-pipe system CND1 JSL1 Spare Superlink terminal setting(for spare) Spare Superlink terminal setting(for spare)
Power source line CNU LED・2 Indication lamp(Green-Normal operation) Indication lamp(Green-Normal operation)
between indoor units BL
YE
YE
LED・3 Indication lamp(Red-Inspection) Indication lamp(Red-Inspection)
19V 24V
GY
GY
RD
RD
BR
BR
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
AC220-240V 50Hz, SM Stepping motor(for electronic expansion valve) Stepping motor(for electronic expansion valve)
Prepare on site
WH
RD
AC220V 60Hz Control PCB 1 2 3 4 5 6 1 2 1 2 CNW1 CNW2 1 2
+12 1
RD SW1 Indoor unit address:tens place Slave box address:tens place
Power source TB1 CNN CNH CNF CND SW2 Indoor unit address:ones place Slave box address:ones place
(Operation) ※1
WH BK
Single-phase YE BK YE BL 2 XR1 SW3 Outdoor unit address:tens place Outdoor unit address:tens place
(Heating)
RD 3 7 8
Power L RD CNT 3
YE
XR2 SW4 Outdoor unit address:ones place Outdoor unit address:ones place
source
line N
F(3.15A)
WH 1 SW5
SW1 SW2 LED・2 BL 4 XR3 (Compressor ON) SW5-1 Switching PCB setting for single/multiple Switching PCB setting for single/multiple
WH
F(3.15A) CNW0
X6 X2 X4
JSL1
5 XR4 (Inspection) refrigeration system(☆OFF=single/ON=multiple) refrigeration system(☆OFF=single/ON=multiple)
RD
Superlink(spare) SW5-2 Indoor unit address:hundreds place(☆OFF) Reserved(keep off)
SW6
XR5 (Remote operation input
6
WH
SW3 SW4 LED・3 SW6-1ー4 Model capacity setting(☆ON) Model capacity setting(☆ON)
RD
CNK2
YE/GN X1 X3 SW7-1 Test run,drain motor test(☆OFF) Reserved(keep off)
Earth SW7
BK :volt-free contact)
SW7-2 Target supply air temperatuer adjustment +15degC setting at supply air temp. control in
For heat recovery 3-pipe system (heating mode) (☆OFF) heating(☆OFF)
+12 1
2 XB1 (20S) SW7-3 Switching return/supply air temperatuer control Switching the control method of refrigerant flow volume
CNT2 3 XB2 (SVH) (☆OFF) (☆OFF=Super heat control ,ON=Supply air temperatuer control)
RD
CNB CNK1 4 XB3 (SVG) SW7-4 Automatic supply air temperatuer adjust. control(☆OFF)Reserved(keep off)
7
CNM3 CNR 1 CNI BL CNA RD WH WH 5 XB4 (SVE) TB1 Terminal block(Power source line)(ƑPDUN) Terminal block(Power source line)(ƑPDUN)
51X1 WH 1 3 5 7 9 WH 3 1 2 1 2 3 4 5 6 1 3 1 2 TB2 Terminal block(ƑPDUN) Terminal block(ƑPDUN)
3 3 3 8 TB3 Terminal block(Signal line)(ƑPDUN) Terminal block(Signal line)(ƑPDUN)
52X1 52X2 XR2 C UH H M L
WH
WH
WH
OR
RD
RD
RD
RD
BR
YE
BK
BL
BL
5 5 5 <5> <6> Thc Thermistor(Remote control)
<1> <2> <7> <8> <3> <4> ThI-A Thermistor(Return air) It is not used in the multiple system.
WH
X Y A B
RD
BR
BK
BL
F(0.16A) 1 TB3
WH
YE
YE
YE
YE
YE
YE
WH
5 ThI-R1,2,3 Thermistor(Heat exchanger) Thermistor(Heat exchanger)
BR CNR2 M TrI Transformer Transformer
X Y
BL
BL YE YE To outdoor unit X1ー3,6 Relay for FM Relay for FM
RD
7 7 Signal line
SM Remote (Shielded cord) X4 Relay for DM Relay for DM
52X1 52X2 M CNI2 control XR2 Relay(DC12V) Relay(DC12V)
8 8 1∼ WH 1 2 (RC−E4) 52X1,52X2,51X1 Relay(AC200V) Relay(AC200V)
Heat exch (air) Heat exch (air) Humidifier Fan motor DM ŶPDUN Closed-end connector Closed-end connector
Thc
Hi operation Lo operation operation error signal t° ☆ Factory default
-
RC−E4:single only ※1 The method of setting the address of the multiple system is different than usual.
53 -
Screw: M3.5 E19 1-time flash Keeps flashing Indoor unit operation check/drain motor check mode faulty
TB2 3,4 Output for humidifier operation E28 Stays OFF Keeps flashing Remote control thermistor anomaly
'15 • KX-T-243
TB2 5,6 Input for fan motor error signal AC200V, 1A Over E30 Stays OFF Keeps flashing Outdoor unit checking (outdoor circuit board LED checking)
E63 Stays OFF Keeps flashing Emergency stop
CNT 6P Connector: Made by Molex 5264-06
Output for operation mode Relay capacity, DC12V, max 160mA at total use
Terminal: Made by Molex 5263T
CNT2 5P Output for heat recovery 3-pipe system Relay capacity, DC12V, max 160mA at total use
CND 2P Output for free cooling Relay capacity, DC12V, max 160mA at total use Connector includes control unit