ANSI/ASHRAE Standard 193-2010 (RA 2014)

(Reaffirmation of ANSI/ASHRAE Standard 193-2010)

Method of Test for


Determining the
Airtightness of
HVAC Equipment

Approved by the ASHRAE Standards Committee on January 18, 2014; by the ASHRAE Board of Directors on January 22, 2014;
and by the American National Standards Institute on January 23, 2014.

ASHRAE Standards are scheduled to be updated on a five-year cycle; the date following the standard number is the year of
ASHRAE Board of Directors approval. The latest edition of an ASHRAE Standard may be purchased on the ASHRAE website
(www.ashrae.org) or from ASHRAE Customer Service, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. E-mail:
orders@ashrae.org. Fax: 678-539-2129. Telephone: 404-636-8400 (worldwide) or toll free 1-800-527-4723 (for orders in US and
Canada). For reprint permission, go to www.ashrae.org/permissions.

© 2014 ASHRAE ISSN 1041-2336


ASHRAE Standard Project Committee 193
Cognizant TCs: TC 4.3, Ventilation Requirements and Infiltration, and
TC 6.3, Central Forced Air Heating and Cooling Systems
SPLS Liaison: K. William Dean
Michael R. Lubliner, Chair* Paul M. Haydock* Elbert G. Phillips*
Iain S. Walker, Vice-Chair* Kevin E. Keller* Brian L. Reynolds
James Lee Austermiller* Lalit Kumar* Armin Rudd*
Roy R. Crawford* Collin L. Olson* Steven Schneider*
James B. Cummings* Hans Paller Steven Andrew Tice
Glenn Friedman* George A. Yaeger*

*Denotes members of voting status when the document was approved for publication

ASHRAE STANDARDS COMMITTEE 2013–2014


William F. Walter, Chair David R. Conover Malcolm D. Knight
Richard L. Hall, Vice-Chair John F. Dunlap Rick A. Larson
Karim Amrane James W. Earley, Jr. Mark P. Modera
Joseph R. Anderson Steven J. Emmerich Cyrus H. Nasseri
James Dale Aswegan Julie M. Ferguson Janice C. Peterson
Charles S. Barnaby Krishnan Gowri Heather L. Platt
Steven F. Bruning Cecily M. Grzywacz Douglas T. Reindl
John A. Clark Rita M. Harrold Julia A. Keen, BOD ExO
Waller S. Clements Adam W. Hinge Thomas E. Werkema, Jr., CO
Debra H. Kennoy

Stephanie C. Reiniche, Manager of Standards

SPECIAL NOTE
This American National Standard (ANS) is a national voluntary consensus standard developed under the auspices of ASHRAE.
Consensus is defined by the American National Standards Institute (ANSI), of which ASHRAE is a member and which has approved this
standard as an ANS, as “substantial agreement reached by directly and materially affected interest categories. This signifies the concurrence
of more than a simple majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that an
effort be made toward their resolution.” Compliance with this standard is voluntary until and unless a legal jurisdiction makes compliance
mandatory through legislation.
ASHRAE obtains consensus through participation of its national and international members, associated societies, and public review.
ASHRAE Standards are prepared by a Project Committee appointed specifically for the purpose of writing the Standard. The Project
Committee Chair and Vice-Chair must be members of ASHRAE; while other committee members may or may not be ASHRAE members, all
must be technically qualified in the subject area of the Standard. Every effort is made to balance the concerned interests on all Project
Committees.
The Manager of Standards of ASHRAE should be contacted for:
a. interpretation of the contents of this Standard,
b. participation in the next review of the Standard,
c. offering constructive criticism for improving the Standard, or
d. permission to reprint portions of the Standard.

DISCLAIMER
ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available information and
accepted industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or performance of any products, components,
or systems tested, installed, or operated in accordance with ASHRAE’s Standards or Guidelines or that any tests conducted under its
Standards or Guidelines will be nonhazardous or free from risk.

ASHRAE INDUSTRIAL ADVERTISING POLICY ON STANDARDS


ASHRAE Standards and Guidelines are established to assist industry and the public by offering a uniform method of testing for rating
purposes, by suggesting safe practices in designing and installing equipment, by providing proper definitions of this equipment, and by providing
other information that may serve to guide the industry. The creation of ASHRAE Standards and Guidelines is determined by the need for them,
and conformance to them is completely voluntary.
In referring to this Standard or Guideline and in marking of equipment and in advertising, no claim shall be made, either stated or implied,
that the product has been approved by ASHRAE.
CONTENTS

ANSI/ASHRAE Standard 193-2010 (RA 2014)


Method of Test for Determining the Airtightness of HVAC Equipment
SECTION PAGE
Foreword ................................................................................................................................................................... 2
1 Purpose .......................................................................................................................................................... 2
2 Scope ............................................................................................................................................................. 2
3 Definitions....................................................................................................................................................... 2
4 Nomenclature ................................................................................................................................................. 2
5 Test Apparatus and Specifications ................................................................................................................. 3
6 Test Procedure ............................................................................................................................................... 3
7 Data to be Recorded ...................................................................................................................................... 5
Informative Annex A—Bibliography ...................................................................................................................... 5

NOTE

Approved addenda, errata, or interpretations for this standard can be downloaded free of charge from the ASHRAE
Web site at www.ashrae.org/technology.

© 2014 ASHRAE
1791 Tullie Circle NE · Atlanta, GA 30329 · www.ashrae.org · All rights reserved.
ASHRAE is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
ANSI is a registered trademark of the American National Standards Institute.
(This foreword is not part of this standard. It is merely 1. PURPOSE
informative and does not contain requirements necessary
This standard prescribes a method of test to determine the
for conformance to the standard. It has not been
airtightness of forced-air HVAC equipment prior to field
processed according to the ANSI requirements for a
installation.
standard and may contain material that has not been
subject to public review or a consensus process.
2. SCOPE
Unresolved objectors on informative material are not
offered the right to appeal at ASHRAE or ANSI.) 2.1 This standard applies to the following:

FOREWORD a. Equipment intended for installation in ducted systems,


including furnaces, heat pumps, air conditioners, coil
One of the most important predictors of a building’s boxes, filter boxes, and associated components.
energy efficiency is its HVAC system. There are a number b. Equipment that moves less than 3000 cfm (1400 L/s) of
of ways to measure the performance of HVAC systems— air.
energy efficiency ratings being one of the most common—
but the airtightness of the equipment is obviously an 2.2 This standard does not apply to ducts, plenums, or other
important factor as well. Air that is not delivered to areas field-constructed components.
as specified in the building design is air that is not being
used efficiently. With this in mind, ASHRAE Standard 193 3. DEFINITIONS
was created to test the airtightness of HVAC equipment.
Where the following terms occur in this standard, the defi-
Targeted at systems that move less than 3000 cfm nitions provided in this section apply.
(1400 L/s), Standard 193 will provide results that may be
used by cognizant authorities who wish to regulate the air air-handling unit (AHU): any device that includes a fan or
leakage of HVAC equipment and by contractors and blower for moving air through ductwork. Examples include
installers that wish to specify and install equipment with furnaces, fan-coil units, energy or heat recovery units, and
known leakage characteristics. exhaust fans.

The approach taken in this method of test is to deter- cased coil: a heating or cooling coil that is mounted in a cabi-
mine the air leakage rate of HVAC equipment at a fixed net and contains no fan or blower.
reference pressure difference. In this way Standard 193 is
duct-mounted air cleaner: a media air filter or other air-
similar to other rating standards that perform evaluations
cleaning device that is mounted in a cabinet and has no fan or
at a single condition for comparison purposes rather than
blower.
attempting to estimate performance for an individual
installation. Because this test method can be applied to a standard conditions: for the purposes of this standard, stan-
wide range of equipment, it is beyond the scope of this dard conditions are defined as follows: 68°F (20°C) for
standard to fully specify detailed test arrangements. temperature, 0.07517 lb/ft 3 (1.2041 kg/m3) for air density, and
Currently the need for minimizing air leakage in 29.92 in. Hg (101.325 kPa) for barometric pressure.
HVAC systems is reflected in various ASHRAE standards. variable-air-volume (VAV) box: a terminal air control device
ASHRAE Standard 62.2 limits allowable air leakage that regulates the amount of air entering a space; usually
between garages and houses due to leaks in forced-air contains a damper but no fan or blower.
HVAC systems. ASHRAE Standard 152 includes HVAC
system air leakage in estimates of distribution system effi- 4. NOMENCLATURE
ciency for residential buildings. But while these standards
aim to reduce the overall air leakage found in HVAC sys- Pbaro = barometric pressure, in. Hg (kPa)
tems, neither provides a way to determine the effectiveness Qleak = air leakage of equipment under test adjusted to
of specific components in an HVAC system in preventing standard conditions and corrected for
air leakage. Although ASHRAE Standard 130 includes a background leakage, cfm (L/s)
test method for measuring air leakage of air terminal Qbg = background air leakage rate of the test
units, it does not specify a fixed test pressure suitable for
apparatus, cfm (L/s)
airtightness ratings.
Qbg,std = background air leakage rate of the test apparatus
This is a reaffirmation of Standard 193-2010. This adjusted to standard conditions, cfm (L/s)
standard was prepared under the auspices of ASHRAE. It
Qmeas = measured air leakage rate, cfm (L/s)
may be used, in whole or in part, by an association or gov-
ernment agency with due credit to ASHRAE. Adherence is Qmeas,std = measured air leakage of equipment under test
strictly on a voluntary basis and merely in the interests of adjusted to standard conditions, cfm (L/s)
obtaining uniform guidelines throughout the industry. This Tmeas = temperature of air flowing through the air
version of the reaffirmation has minor editorial changes. flowmeter, °F (°C)

2 ANSI/ASHRAE Standard 193-2010 (RA 2014)


5. TEST APPARATUS AND SPECIFICATIONS 6.1.2 The air-moving device shall be turned on and used to
create a pressure difference of 0.5 in. H2O (125 Pa) between
This method of test requires the depressurization and/or
the inside and outside of the equipment under test, with the
pressurization of HVAC equipment to a specified test pres-
inside of the equipment depressurized relative to ambient con-
sure. The airflow rate required to maintain the applied pres- ditions.
sures is the air leakage rate of the equipment under test,
6.1.3 Measure the volumetric airflow, (Qbg–).
Qleak . Schematics of typical test apparatuses are shown in
Figures 1 and 2. 6.1.4 Convert the background leakage flows to standard
conditions, Qbg–,std, using Equation 2 or 3, as applicable.
5.1 Test Apparatus 6.1.5 If positive pressure tests are to be performed, repeat
The test apparatus shall consist of the following compo- the background leakage test in pressurization mode to deter-
nents: mine Qbg+,std.
a. An air-moving blower or equivalent device capable of 6.2 Air-Leakage Test Methods
controlling airflow for pressurizing or depressurizing the 6.2.1 Depressurization Test
equipment under test to a pressure difference of 0.5 in. 6.2.1.1 The equipment shall be connected to the air-
H2O (125 Pa). moving device. An impermeable blanking cap shall be
b. An airflow measuring device capable of measuring volu- applied to the open end or ends of the equipment under test, if
metric airflow at the required test pressure difference with applicable. This connection shall be made with the same air-
the accuracy stated in Section 5.2.1. sealing technique as used for the background air leakage mea-
c. A pressure-measuring device capable of measuring the surements of Section 6.1.
required pressure difference with the accuracy stated in 6.2.1.2 The air-moving device shall be turned on and
Section 5.2.2. used to create a pressure difference of 0.5 in. H2O (125 Pa)
d. Temperature measurement devices capable of measuring between the inside and outside of the equipment under test,
air temperature with the accuracy stated in Section 5.2.3. with the inside of the equipment depressurized relative to
e. A pressure-measuring device to measure barometric pres- ambient conditions. The pressure measurement location shall
sure with the accuracy stated in Section 5.2.4. be selected to avoid, as much as possible, air velocities that
could influence the measurement.
5.2 Test Apparatus Specifications
The test apparatus shall meet the following specifications. 6.2.1.3 Determine the volumetric airflow through the
measurement device (Qmeas) required to maintain this pres-
5.2.1 Airflows shall be measured with an accuracy equal
sure difference. The airflow shall be converted to standard
to or better than 2 cfm (1 L/s) or 5% of measured flow, which-
conditions, Qmeas,std, using Equation 2 or 3, as applicable.
ever is larger, and with a precision equal to or better than 1 cfm
(0.5 L/s). 6.2.1.4 The background air leakage rate shall be sub-
tracted from the measured air leakage rate to determine the air
5.2.2 Pressures shall be measured with an accuracy equal
leakage rate of the equipment under test using Equation 1:
to or better than 0.004 in. H2O (1.0 Pa) and a precision equal
to or better than 0.002 in. H2O (0.5 Pa). Q leak = Q meas std – Q bg std (1)
5.2.3 Temperature measurements shall be made using
devices with an accuracy equal to or better than ±2°F (1°C) and 6.2.2 Pressurization Test
with a precision equal to or better than ±1°F (0.5°C). 6.2.2.1 The equipment shall be connected to the air-
5.2.4 Barometric pressures shall be measured with an moving device. An impermeable blanking cap shall be
accuracy equal to or better than 0.15 in. Hg (0.5 kPa). applied to the open end or ends of the equipment under test, if
applicable. This connection shall be made with the same air
6. TEST PROCEDURE sealing technique as used for the background air leakage mea-
surements of Section 6.1.
This test procedure shall be used to determine the amount 6.2.2.2 The air-moving device shall be turned on and
of airflow, Qleak, for the equipment under test. Qleak shall be used to create a pressure difference of 0.5 in. H2O (125 Pa)
a positive value representing the magnitude of the measured between the inside and outside of the equipment under test,
airflow. with the inside of the equipment pressurized relative to ambi-
The background leakage described in Section 6.1 shall be ent conditions. The pressure measurement location shall be
measured for all test procedures. Table 1 shall then be used to selected to avoid, as much as possible, air velocities that could
select an additional equipment-specific test method to be influence the measurement.
performed. The barometric pressure, Pbaro, and the tempera-
6.2.2.3 Determine the volumetric airflow through the
ture, Tmeas, of the air flowing through the measurement device
measurement device (Qmeas) required to maintain this pres-
shall be determined for each airflow measurement.
sure difference. The airflow shall be converted to standard
6.1 Background Air-Leakage Rate of the Test Apparatus conditions, Qmeas,std, using Equation 2 or 3, as applicable.
6.1.1 An air impermeable blanking cap shall be used to 6.2.2.4 The background air leakage rate shall be sub-
cover the opening of the test apparatus to which the equip- tracted from the measured air leakage rate to determine the air
ment under test is connected. leakage rate of the equipment under test using Equation 1.

ANSI/ASHRAE Standard 193-2010 (RA 2014) 3


Figure 1 Schematic of test apparatus and equipment under test for pressurization or depressurization testing.

Figure 2 Schematic of test apparatus and equipment under test for split-test procedure.

4 ANSI/ASHRAE Standard 193-2010 (RA 2014)


6.2.3 Split Test to standard conditions (Qmeas–,std) using Equation 2 or 3, as
6.2.3.1 The equipment shall be split between its posi- applicable.
tive and negative pressure zones by sealing between the two 6.2.3.4 The background air leakage rate shall be sub-
pressure zones. This split can be made either with the blower tracted from the measured air leakage rate to determine the air
in place or with the blower removed. If the blower is retained, leakage rate of the equipment using Equations 4 and 5.
then the inlets or outlets of the blower shall be covered such
that they do not move or leak air during the test. If the blower Q leak + = Q meas+ std – Q bg+ std (4)
is removed, an airtight cover shall be placed over the opening
between the negative and positive pressure sections of the Q leak – = Q meas– std – Q bg– std (5)
equipment under test. The cover shall be placed over the
6.2.3.5 The sum of the positive and negative pressure
opening through which the blower discharges into the positive
zone tests shall be reported as the air leakage of the equip-
pressure section of the equipment. Any other openings
ment:
between the positive and negative pressure zones shall also be
sealed. Q leak = Q leak + + Q leak – (6)
6.2.3.2 Positive Pressure Zone Measurements
The air-moving device shall be connected to the side of
7. DATA TO BE RECORDED
the equipment that is under positive pressure during normal
operation, i.e., on the discharge side of the air-handling unit The test report shall contain the following information:
(AHU). The air-moving device shall be turned on and used to
create a pressure difference of 0.5 in. H2O (125 Pa) between a. Date of test
the inside and outside of the equipment under test, with the b. Name of test organization
inside of the equipment pressurized relative to ambient condi- c. Description of equipment under test, including the manu-
tions. The airflow through the measurement device required to facturer, make, model number, serial number, and the
maintain this pressure difference (Qmeas+) shall be measured. type of device (e.g., furnace, VAV box)
If there is more than one positive pressure zone, repeat this d. Whether manufacturer-supplied grommets were used to
section of test for each zone and Qmeas+ shall be the sum total seal penetrations
from all positive pressure zones. The airflow shall be e. Method used to seal condensate drains
converted to standard conditions, Qmeas+,std, using Equation 2 f. Air leakage test result, Qleak (see Section 6.2.3.5.)
or 3, as applicable:
(This annex is not part of this standard. It is merely
P baro 528
Q leak  std = Q leak ------------- ----------------------------------
- (I-P) (2) informative and does not contain requirements necessary
29.92  T meas + 460 
for conformance to the standard. It has not been
processed according to the ANSI requirements for a
P baro 293 standard and may contain material that has not been
Q leak  std = Q leak ------------------
- ----------------------------------- (SI) (3)
101.325  T meas + 273  subject to public review or a consensus process.
Unresolved objectors on informative material are not
6.2.3.3 Negative Pressure Zone Measurements
offered the right to appeal at ASHRAE or ANSI.)
The air-moving device shall be connected to the side of
the equipment that is under negative pressure during normal INFORMATIVE ANNEX A
operation, i.e., on the inlet side of the blower in the equipment BIBLIOGRAPHY
under test. The air-moving device shall be turned on and used
to create a pressure difference of 0.5 in. H2O (125 Pa) between ANSI/ASHRAE Standard 62.2-2007, Ventilation and
the inside and outside of the equipment under test, with the Acceptable Indoor Air Quality in Low-Rise Residential
inside of the equipment depressurized relative to ambient Buildings.
conditions. The airflow through the measurement device ANSI/ASHRAE Standard 130-2008, Methods of Testing Air
required to maintain this pressure difference (Qmeas–) shall be Terminal Units.
measured. If there is more than one negative pressure zone, ANSI/ASHRAE Standard 152-2004, Method of Test for
repeat this section of test for each zone and Qmeas– shall be the Determining the Design and Seasonal Efficiencies of
sum total from all negative pressure zones. Convert the airflow Residential Thermal Distribution Systems.

ANSI/ASHRAE Standard 193-2010 (RA 2014) 5


POLICY STATEMENT DEFINING ASHRAE’S CONCERN
FOR THE ENVIRONMENTAL IMPACT OF ITS ACTIVITIES

ASHRAE is concerned with the impact of its members’ activities on both the indoor and outdoor environment. ASHRAE’s
members will strive to minimize any possible deleterious effect on the indoor and outdoor environment of the systems and
components in their responsibility while maximizing the beneficial effects these systems provide, consistent with accepted
standards and the practical state of the art.
ASHRAE’s short-range goal is to ensure that the systems and components within its scope do not impact the indoor and
outdoor environment to a greater extent than specified by the standards and guidelines as established by itself and other
responsible bodies.
As an ongoing goal, ASHRAE will, through its Standards Committee and extensive technical committee structure,
continue to generate up-to-date standards and guidelines where appropriate and adopt, recommend, and promote those new
and revised standards developed by other responsible organizations.
Through its Handbook, appropriate chapters will contain up-to-date standards and design considerations as the material is
systematically revised.
ASHRAE will take the lead with respect to dissemination of environmental information of its primary interest and will seek
out and disseminate information from other responsible organizations that is pertinent, as guides to updating standards and
guidelines.
The effects of the design and selection of equipment and systems will be considered within the scope of the system’s
intended use and expected misuse. The disposal of hazardous materials, if any, will also be considered.
ASHRAE’s primary concern for environmental impact will be at the site where equipment within ASHRAE’s scope
operates. However, energy source selection and the possible environmental impact due to the energy source and energy
transportation will be considered where possible. Recommendations concerning energy source selection should be made by
its members.
ASHRAE · 1791 Tullie Circle NE · Atlanta, GA 30329 · www.ashrae.org

About ASHRAE
ASHRAE, founded in 1894, is an international building technology society with more than 50,000 members worldwide.
The Society and its members focus on building systems, energy efficiency, indoor air quality, refrigeration, and
sustainability. Through research, standards writing, publishing, certification and continuing education, ASHRAE shapes
tomorrow’s built environment today.

For more information or to become a member of ASHRAE, visit www.ashrae.org.

To stay current with this and other ASHRAE standards and guidelines, visit www.ashrae.org/standards.

Visit the ASHRAE Bookstore


ASHRAE offers its standards and guidelines in print, as immediately downloadable PDFs, on CD-ROM, and via ASHRAE
Digital Collections, which provides online access with automatic updates as well as historical versions of publications.
Selected standards are also offered in redline versions that indicate the changes made between the active standard and
its previous version. For more information, visit the Standards and Guidelines section of the ASHRAE Bookstore at
www.ashrae.org/bookstore.

IMPORTANT NOTICES ABOUT THIS STANDARD

To ensure that you have all of the approved addenda, errata, and interpretations for this
standard, visit www.ashrae.org/standards to download them free of charge.

Addenda, errata, and interpretations for ASHRAE standards and guidelines are no
longer distributed with copies of the standards and guidelines. ASHRAE provides
these addenda, errata, and interpretations only in electronic form to promote
more sustainable use of resources.