A.
System
Overview
Wiring Duct is the premium wire management solution for routing and concealing wiring in electrical B2.
control panels. Panduct ® Wiring Duct provide solutions for the original equipment manufacturing, Cable
Accessories
transportation, contract manufacturing, maintenance and repair and communications markets.
All Panduct ® Wiring Duct are UL Recognized and CSA Certified and most carry the CE mark. B3.
Stainless
Steel Ties
D3.
Grounding
Connectors
E1.
Labeling
Systems
Panduit continues to develop new Panduct ® Wiring Duct solutions to satisfy the challenges facing our
customers worldwide. Maximize the utilization of enclosure space with PanelMax ™ Corner Wiring Duct,
E2.
DIN Rail Wiring Duct, and Noise Shield. PanelMax ™ Corner Wiring Duct fits into unused space in the Labels
corner of enclosures providing up to 20% enclosure space savings*.Integrate component mounting with
wire management with PanelMax ™ DIN Rail Wiring Duct for up to 30% enclosure space savings. E3.
Pre-Printed
PanelMax ™ Noise Shield provides noise mitigation between noisy and sensitive cabling and can reduce & Write-On
Markers
air space requirements within the enclosure.
E4.
*Versus panel layouts using conventional wiring duct. Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.1
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview
C1.
Wiring
Duct
PanelMax™
Noise Shield 2
C2. Installed separately or
Surface
Raceway within wiring duct.
D3.
Grounding
Connectors
E3.
Pre-Printed
& Write-On
Markers
F.
Index
C1.2
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview
B1.
Cable Ties
Type F Narrow Slot
5 Wiring Duct
Narrow slot, narrow B2.
finger design fits the Cable
spacing of high-density Accessories
terminal blocks.
B3.
(pages C1.14 – C1.15) Stainless
Steel Ties
C1.
Wiring
5 Duct
Type G Wide Slot
Wiring Duct
Wide slot, wide C2.
Surface
finger design. Raceway
3 (pages C1.12 – C1.13)
C3.
Abrasion
Protection
6 C4.
Cable
Management
Type D Round Hole
Wiring Duct
D1.
Multiple rows of holes Terminals
to retain and support
wire of variable heights
and positions.
D2.
Power
(pages C1.16 – C1.17) Connectors
D3.
Grounding
Connectors
Type MC Metric
Wiring Duct E1.
2 Narrow slot, narrow finger
Labeling
Systems
design with DIN 43 659
mounting holes.
E2.
(pages C1.18 – C1.19) Labels
E3.
Pre-Printed
& Write-On
Markers
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.3
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview Features and Benefits – Panduct ® PanelMax ™ DIN Rail Wiring Duct
DIN rail and DIN component compatible Hinged and flexible cover
B1. acts as ledge for wire installation and
Cable Ties Unique finger/slot
progression for aesthetics flexes for easy opening and increased
and maximum slot capacity channel access for maintenance
B3.
Stainless
Steel Ties Locating ribs
align and center DIN rail
during installation
C1.
Wiring
Duct
Pass-through holes
C2.
Surface shorten the wiring path between
Raceway components on the same DIN rail
C3.
Abrasion
Protection
D1.
Terminals
Conventional Wiring Duct Panel Layout:
D2.
Power
Connectors
D3.
Grounding
Connectors
E1.
Labeling
Systems
E2. DIN Rail Wiring Duct Panel Layout with 30% Space Savings:
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions Panduit ® PanelMaxTM DIN Rail Wiring Duct positions DIN rail and components off the panel directly
above an integrated wire management channel for a 30%+ smaller footprint to the panel layout.
F.
Index
• Space saving design positions DIN rail and components off the • Slotted platform (horizontal) manage the wire from channel B1.
panel directly above an integrated wire management channel mounted components, outer sidewall slots (vertical) manage wire Cable Ties
for up to a 30% smaller footprint for duct and components; from adjacent panel mounted components; unique finger and slot
increased design flexibility and component access for easier progression for optimal wire management and aesthetics
installation and maintenance • Channel pass through slots allows wires to transition internally B2.
• DIN rail and DIN component compatible with standard 35mm between channels to ease wire connections Cable
Accessories
or 15mm rails and many DIN rail mount components for to either side of components mounted on the same rail minimizing
design flexibility wire length and reducing material cost
• Integrated DIN rail fastening slot allows the DIN rail to mount • Optional wire retainer accessory retains cabling with B3.
directly to product with plastic thread cutting screws for up to cover opened or removed easing wire installation and Stainless
Steel Ties
40% faster duct and rail installation and reduced labor costs future wire additions
• Hinged cover remains attached during maintenance and upgrades
preventing lost covers, ensuring panel integrity, safety and C1.
aesthetics; L-shaped cover acts as ledge to aid wire installation Wiring
Duct
for ease of use
DRDC2LG6 2" replacement cover for PanelMax ™ DIN Rail 6 Ft. 24 Ft.
Wiring Duct. D1.
Terminals
DRDC3LG6 3" replacement cover for PanelMax ™
DIN Rail 6 Ft. 24 Ft.
Wiring Duct.
DRDC4LG6 4" replacement cover for PanelMax ™ DIN Rail 6 Ft. 24 Ft. D2.
Wiring Duct. Power
DRDWR Connectors
DRDSF-C Replacement DIN rail fasteners for PanelMax ™ 100 —
DIN Rail Wiring Duct.
DRDWR2-X 2" wire retainer for PanelMax ™ DIN Rail Wiring Duct. 10 100 D3.
Grounding
Connectors
DRDWR3-X 3" wire retainer for PanelMax ™ DIN Rail Wiring Duct. 10 100
E1.
DRDWR4-X 4" wire retainer for PanelMax ™ DIN Rail Wiring Duct. 10 100 Labeling
Systems
DRDCS2-X 2" corner strip for PanelMax ™ DIN Rail Wiring Duct. 10 100
DRDCS
DRDCS3-X 3" corner strip for PanelMax ™ DIN Rail Wiring Duct. 10 100 E2.
Labels
DRDCS4-X 4" corner strip for PanelMax ™ DIN Rail Wiring Duct. 10 100
E3.
Pre-Printed
Product sold base and cover together in 6 ft. lengths. Replace LG with WH for white color. & Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com C1.5
ELECTRICAL SOLUTIONS
A.
System
Overview Features and Benefits – Panduct ® PanelMax ™ Noise Shield
C2.
Surface
Raceway
C3.
Abrasion
Protection
D1.
Terminals
D2.
Power PanelMax™ Noise Shield Metal noise barrier
Connectors separates drive cables and sensitive equivalent to 6 inches of air spacing
communication/signal cables within between power and signal cables,
industrial control panels to reduce saves valuable panel space.
D3. electromagnetic interference (EMI)
Grounding
while saving valuable space.
Connectors
E1.
Labeling
Systems
Perforated and pre-scored sections
make it easy to cut to length with
minimal deburring required.
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
• Metal noise barrier reduces EMI noise coupling between noise • Vertical wall slots allow wires to cross the
emitting and sensitive cabling within a control panel; provides barrier at 90° when necessary, providing B1.
up to 20dB reduction in noise which is equivalent to 6 inches greater design flexibility Cable Ties
of air spacing • Horizontal cable tie slots allow cable bundles to be held in
• Installs directly to metal panel surface or within 2, 3, or 4 inch place using cable ties so cabling is kept near barrier for greater
height Panduit wiring duct (when shield is installed with supplied reliability and optimal aesthetics B2.
bonding clips) Cable
• Zinc plated steel surface in contact areas with sub-panel Accessories
• Perforated and pre-scored sections speed installation by allowing and bonding clip ensures continuity and is corrosion resistant
sections of the shield to be snapped off at pre-scored locations • Black powder coated vertical surface for smooth edges
to easily cut to length with minimal deburring required B3.
• Meets UL 508/508A requirements as a barrier between conductors Stainless
Steel Ties
Std.
Pkg.
Part Number Part Description Qty. C1.
Wiring
SD2EMI EMI Noise Shield kit for 2" height Panduit Wiring Duct; (2) three foot 1 Duct
sections, bonding clips, and anti-oxidizing paste.
SD3EMI EMI Noise Shield kit for 3" height Panduit Wiring Duct; (2) three foot 1
sections, bonding clips, and anti-oxidizing paste. C2.
Surface
SD4EMI EMI Noise Shield kit for 4" height Panduit Wiring Duct; (2) three foot 1 Raceway
sections, bonding clips, and anti-oxidizing paste.
C3.
Abrasion
Protection
D1.
Terminals
Noise Coupling vs. Frequency
Noise Frequency (MHz)
0 2.0 4.0 6.0 8.0 10.0
D2.
0
Power
Connectors
-10
Noise Coupling (dB)
No Shield D3.
-20 Grounding
PanelMax™ Connectors
Noise
-30 Shield
E1.
Labeling
-40 Systems
-50
PanelMax™ Noise Shield delivers approximately 20dB of noise E2.
reduction across common industrial noise frequencies at 30mm Labels
wire separation.
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.7
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview Features and Benefits – Panduct ® PanelMax ™ Corner Wiring Duct
B1.
One-piece base Conventional
Cable Ties reduces fasteners Wiring Duct
required for minimal
installation time Co-extruded Unused
hinged base Panel Space
B2.
Cable sits flat for
Accessories cutting and
also conforms Space is lost at
to corner the edges of the
B3. for installation Enclosure corner
Stainless top view mounting panels.
Steel Ties
Upper and Space Savings with
C1. lower PanelMax ™ Corner
Wiring scorelines Wiring Duct
Duct allow easy
finger and Panel
sidewall Integral Space Gain
C2. section
Surface divider wall
Raceway removal mount feature Up to 5 square feet of
in base additional mounting space
gained per enclosure.*
C3.
Abrasion
Protection
C4.
Cable
Management
D1.
Both sizes use
Terminals 2 inch Type C
cover (C2)
Specially
formulated
D2. lead-free PVC Up to a 20% reduction in enclosure footprint size is
Power possible vs. a conventional wiring duct installation.*
material
Connectors
D3.
Grounding
Connectors
Panduct ® Nylon Rivets Panduct ® Installation Tools
E1. Fast, lowest cost mounting method. Wide selection of hand tools for
Labeling (see page C1.34) cutting and installing wiring duct.
Systems (see page C1.34)
E2.
Labels
E3.
Pre-Printed Panduct ® Type C Cover Panduct ® Divider Wall
& Write-On with Protective Film Creates separate wiring channels
Markers Reduces scrap and labor costs within the wiring duct base. Available
by protecting the surface during in solid or slotted wall styles.
E4. storage, handling, and installation. (see page C1.26)
Permanent (see page C1.9)
Identification
E5.
Lockout/
Tagout *Actual subpanel space savings will vary depending on wiring duct size, component layout, and enclosure size and type. Footprint savings is based on
& Safety commercially available enclosures and may not be achievable in some applications.
Solutions
F.
Index
• Fits in the unused space in the vertical corner • Panduit divider wall snaps directly to the integrated mounting
B1.
of enclosures, gaining sub-panel space or saving feature in the channel to create two separate channels Cable Ties
enclosure footprint area • Compatible with Panduit 3" and 4" height wiring duct;
• One-piece base requires less time to install than both product sizes use standard 2 inch wiring duct cover
multi-piece solutions • Base and cover length is 6 feet. B2.
• Optional quick mount clips engage anywhere along Cable
• Base and covers sold separately Accessories
the product base further reducing assembly costs
B3.
Std. Base Cover Stainless
Slot Width Steel Ties
Base Duct Size W x H Cover Pkg. Ctn. Ctn.
Part Number (In.) In. mm Part Number Qty. Qty. Qty.
CWD3LG6 4.40 x 3.57 0.20 5.0 C2LG6 6 24 120 C1.
CWD4LG6 5.33 x 4.58 0.20 5.0 C2LG6 6 24 120 Wiring
CWD3WH6 4.40 x 3.57 0.20 5.0 C2WH6 6 24 120 Duct
CWD4WH6 5.33 x 4.58 0.20 5.0 C2WH6 6 24 120
Part number shown in LG (Light Gray) color, also available in WH (White) color. Product available in 6' lengths. C2.
Surface
Raceway
C4.
H
Cable
Management
D2.
Power
Connectors
D3.
Grounding
Connectors
To order cover with protective
film add "–F" to part number.
6" cover not available with E1.
protective film. Labeling
Systems
Std. Std.
Pkg. Ctn.
E2.
Part Number Part Description Fastener Size Qty. Qty. Labels
Quick Mount Clips
CDLB3 L-bracket with quick mounting clip for #10-32 x 1/4 (user supplied) 16 —
E3.
CDLB installing CWD3 to back panel only. Pre-Printed
CDLB4 L-bracket with quick mounting clip for #10-32 x 1/4 (user supplied) 16 — & Write-On
installing CWD4 to back panel only. Markers
CDCLP3 Quick mounting clip for installing #10-32 x 1/4 (user supplied) 16 —
CWD3 corner wiring duct. E4.
CDCLP4 Quick mounting clip for installing #10-32 x 1/4 (user supplied) 16 — Permanent
CWD4 corner wiring duct. Identification
CDCLP
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.9
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview Features and Benefits – Panduct ® Type H and HN Hinged Cover Wiring Duct
Available in eight sizes from 1.5" x 2" up to 4" x 4" in light gray, black, and white colors.
B1.
Cable Ties
Dual-sided hinge cover Cover removal rib eases cover opening
opens up to 100° from either for quick channel access during
sidewall of duct for up to 20% wiring changes
B2.
Cable faster wiring changes
Accessories
C1.
Wiring
Duct Robust channel
profile withstands a
side impact force up
C2. to two times greater
Surface than conventional
Raceway wiring duct
C3.
Abrasion
Protection
C4. Upper and lower scoreline allows easy fingers and Specially formulated
Cable sidewall section removal, saving installation time lead-free PVC material
Management
Labor Savings
D1.
Terminals
■ By avoiding the time and hassle in removing and replacing covers, simple wiring changes can be made up to 20% faster
compared to conventional wiring duct installations*
D2.
Power Avoid Cover Replacement Costs % of Wiring Duct Cost
Connectors
■ Covers represent 20% of the cost of the wiring
duct purchase
D3.
Grounding ■ Misplaced covers are a common occurrence after Base Cover
Connectors years of use
■ Not needing to remove covers during maintenance
E1. ensures better aesthetics and safety and avoids
Labeling
Systems the cost to replace lost covers
E4.
Permanent
Identification Panduct ® Installation Tools Panduct ® Nylon Rivets
Wide selection of hand tools for Fast, lowest cost mounting method.
E5. cutting and installing wiring duct. (see page C1.34)
Lockout/ (see page C1.34)
Tagout
& Safety
Solutions
F. *Based on mock panel installations of type H hinged cover wiring duct and other commonly available wiring ducts adding a single component with four wires.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com C1.11
ELECTRICAL SOLUTIONS
A.
System
Overview Features and Benefits – Panduct ® Type G Wide Slot Wiring Duct
Available in 35 sizes from .5" x .5" up to 6" x 4" in a variety of colors.
B1.
Cable Ties
B3.
Stainless
Steel Ties
Specially formulated
lead-free PVC material
C1.
Wiring
Duct
Flush cover design
C2. provides a neat and
Surface finished appearance
Raceway
C3.
Abrasion
Protection Wide finger/slot design
provides greater rigidity
and allows use with a
C4. wide range of wire and
Cable
Management bundle sizes
Upper and lower scorelines allows Restricted slot design
easy finger and sidewall section retains wires, eliminating
removal saving installation time hassle and saving time
D1.
Terminals
D2.
Power
Connectors
Panduct ® Wire Retainers Panduct ® Divider Wall
Contain wiring when duct cover is Create separate wiring channels
D3.
Grounding opened. Wire retainers snap easily within the wiring duct base. Available
Connectors between duct fingers. in solid or slotted wall styles.
See page C1.28. See page C1.26.
E1.
Labeling
Systems
E4.
Permanent
Identification Panduct ® Installation Tools
Wide selection of hand tools for
E5. cutting and installing wiring duct.
Lockout/ See page C1.34.
Tagout
& Safety
Solutions
F.
Index
• Wide slot/finger design provides greater sidewall rigidity and can • Conforms with NFPA 79-2007 section 13.3.1 requirement
be used with a wide range of wire bundle sizes for flame retardant material B1.
• Material: Lead-free PVC • Provided with mounting holes Cable Ties
• UL recognized continuous use temperature: 122°F (50°C) • Base and cover length is 6 feet
• UL 94 flammability rating of V-0 B2.
Cable
Accessories
G.5X1LG6 0.69 x 1.06 17.5 x 26.9 0.31 7.9 C.5LG6 6 120 120
G.5X2LG6 0.69 x 2.03 17.5 x 51.6 0.31 7.9 C.5LG6 6 120 120 C1.
Wiring
G.75X.75LG6 0.93 x 0.82 23.6 x 20.8 0.31 7.9 C.75LG6 6 120 120 Duct
G.75X1LG6 0.93 x 1.06 23.6 x 26.9 0.31 7.9 C.75LG6 6 120 120
G.75X1.5LG6 0.93 x 1.57 23.6 x 39.9 0.31 7.9 C.75LG6 6 120 120
C2.
G.75X2LG6 0.93 x 2.03 23.6 x 51.7 0.31 7.9 C.75LG6 6 120 120 Surface
G1X1LG6 1.26 x 1.12 32.0 x 28.4 0.31 7.9 C1LG6 6 120 120 Raceway
W
G1X1.5LG6 1.26 x 1.62 32.0 x 41.1 0.31 7.9 C1LG6 6 120 120
G1X2LG6 1.26 x 2.12 32.0 x 53.8 0.31 7.9 C1LG6 6 120 120 C3.
Abrasion
G1X3LG6 1.26 x 3.12 32.0 x 79.2 0.31 7.9 C1LG6 6 120 120 Protection
H
G1X4LG6 1.26 x 4.10 32.0 x 104.1 0.31 7.9 C1LG6 6 60 120
G1.5X1LG6 1.75 x 1.12 44.5 x 28.4 0.31 7.9 C1.5LG6 6 120 120 C4.
G1.5X1.5LG6 1.75 x 1.62 44.5 x 41.1 0.31 7.9 C1.5LG6 6 120 120 Cable
Management
G1.5X2LG6 1.75 x 2.12 44.5 x 53.8 0.31 7.9 C1.5LG6 6 120 120
G1.5X3LG6 1.75 x 3.12 44.5 x 79.2 0.31 7.9 C1.5LG6 6 120 120
F G1.5X4LG6 1.75 x 4.10 44.5 x 104.1 0.31 7.9 C1.5LG6 6 60 120 D1.
G2X1LG6 2.25 x 1.12 57.2 x 28.4 0.31 7.9 C2LG6 6 120 120 Terminals
G2X1.5LG6 2.25 x 1.62 57.2 x 41.1 0.31 7.9 C2LG6 6 120 120
G2X2LG6 2.25 x 2.12 57.2 x 53.8 0.31 7.9 C2LG6 6 120 120
D2.
E G2X3LG6 2.25 x 3.12 57.2 x 79.2 0.31 7.9 C2LG6 6 60 120 Power
E F Connectors
For .5" duct height: 0.37" [9.4] 0.80" [20.3] G2X4LG6 2.25 x 4.10 57.2 x 104.1 0.31 7.9 C2LG6 6 60 120
0.75" to 2" duct height: 0.31" [7.9] 0.80" [20.3] G2X5LG6 2.25 x 5.10 57.2 x 129.5 0.38 9.7 C2LG6 6 60 120
3" to 4" duct height: 0.31" [7.9] 1.00" [25.4]
5" duct height: 0.38" [9.4] 1.33" [33.8] G2.5X3LG6 2.75 x 3.12 69.9 x 79.2 0.31 7.9 C2.5LG6 6 120 120 D3.
Grounding
G3X1LG6 3.25 x 1.12 82.6 x 28.4 0.31 7.9 C3LG6 6 120 120 Connectors
G3X2LG6 3.25 x 2.12 82.6 x 53.8 0.31 7.9 C3LG6 6 120 120
G3X3LG6 3.25 x 3.12 82.6 x 79.2 0.31 7.9 C3LG6 6 60 120
E1.
G3X4LG6 3.25 x 4.10 82.6 x 104.1 0.31 7.9 C3LG6 6 60 120 Labeling
Systems
G3X5LG6 3.25 x 5.10 82.6 x 129.5 0.38 9.7 C3LG6 6 60 120
G4X1.5LG6 4.25 x 1.62 108.0 x 41.1 0.31 7.9 C4LG6 6 120 120
G4X2LG6 4.25 x 2.12 108.0 x 53.8 0.31 7.9 C4LG6 6 60 120 E2.
G4X3LG6 4.25 x 3.12 108.0 x 79.2 0.31 7.9 C4LG6 6 60 120 Labels
To order cover with protective film
add “-F” to part number. 6" cover G4X4LG6 4.25 x 4.10 108.0 x 104.1 0.31 7.9 C4LG6 6 60 120
not available with film. G4X5LG6 4.25 x 5.10 108.0 x 129.5 0.38 9.7 C4LG6 6 60 120 E3.
Pre-Printed
G6X4LG6 6.25 x 4.15 158.8 x 105.4 0.31 7.9 C6LG6 6 60 120 & Write-On
Part number shown for LG (Light Gray). For other color availability see color selection guide, page C1.48. Markers
Base and cover sold separately.
*“H” dimension includes duct and cover. E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.13
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview Features and Benefits – Panduct ® Type F Narrow Slot Wiring Duct
Available in 31 sizes from .5" x .5" up to 6" x 4" in a variety of colors.
B1.
Cable Ties
C1.
Wiring Specially formulated
Duct lead-free PVC material
Flush cover
C2. design
Surface
Raceway
provides a neat
appearance
C3.
Abrasion
Protection
C4.
Cable
Narrow finger/slot design
Management
Upper and lower scorelines allows easy fingers closely matches the spacing
and sidewall section removal, saving installation time of high-density components
D1.
Terminals
D2.
Power
Connectors
Panduct ® Wire Retainers for Panduct ® Divider Wall
Type F Wiring Duct Create separate wiring channels
D3.
Grounding Contain wiring when duct cover is within the wiring duct base. Available
Connectors opened. Wire retainers snap easily in solid or slotted wall styles.
between duct fingers. (see page C1.26)
(see page C1.29)
E1.
Labeling
Systems
E4.
Permanent
Identification Panduct ® Installation Tools
Wide selection of hand tools for
E5. cutting and installing wiring duct.
Lockout/ (see page C1.34)
Tagout
& Safety
Solutions
F.
Index
• Narrow slot/finger design provides more slots to fit the spacing of • Conforms with NFPA 79-2007 section 13.3.1 requirement
high-density terminal blocks and other hardware for flame retardant material B1.
Cable Ties
• Material: Lead-free PVC • Provided with mounting holes
• UL recognized continuous use temperature: 122°F (50°C) • Base and cover length is 6 feet
• UL 94 flammability rating of V-0 B2.
Cable
Accessories
Std. Base Cover
Base Duct Size (W x H)* Slot Width Cover Pkg. Ctn. Ctn.
Part Number In. mm In. mm Part Number Qty. Qty. Qty. B3.
F.5X.5LG6 0.69 x 0.60 17.5 x 15.2 0.20 5.0 C.5LG6 6 120 120 Stainless
Steel Ties
F.5X1LG6 0.69 x 1.06 17.5 x 26.9 0.20 5.0 C.5LG6 6 120 120
F.75X.75LG6 0.93 x 0.82 23.6 x 20.9 0.20 5.0 C.75LG6 6 120 120
C1.
F.75X1.5LG6 0.93 x 1.57 23.6 x 39.9 0.20 5.0 C.75LG6 6 120 120 Wiring
F1X1LG6 1.26 x 1.13 32.0 x 28.7 0.20 5.0 C1LG6 6 120 120 Duct
F1X1.5LG6 1.26 x 1.62 32.0 x 41.1 0.20 5.0 C1LG6 6 120 120
W
F1X2LG6 1.26 x 2.12 32.0 x 53.8 0.20 5.0 C1LG6 6 120 120 C2.
F1X3LG6 1.26 x 3.12 32.0 x 79.2 0.20 5.0 C1LG6 6 120 120 Surface
Raceway
F1X4LG6 1.26 x 4.10 32.0 x 104.1 0.20 5.0 C1LG6 6 60 120
H F1.5X1LG6 1.75 x 1.12 44.5 x 28.4 0.20 5.0 C1.5LG6 6 120 120
C3.
F1.5X1.5LG6 1.75 x 1.62 44.5 x 41.1 0.20 5.0 C1.5LG6 6 120 120 Abrasion
F1.5X2LG6 1.75 x 2.12 44.5 x 53.8 0.20 5.0 C1.5LG6 6 120 120 Protection
F1.5X3LG6 1.75 x 3.12 44.5 x 79.2 0.20 5.0 C1.5LG6 6 120 120
.50 TYP [12.7] F1.5X4LG6 1.75 x 4.10 44.5 x 104.1 0.20 5.0 C1.5LG6 6 60 120 C4.
F2X1LG6 2.25 x 1.12 57.2 x 28.4 0.20 5.0 C2LG6 6 120 120 Cable
Management
F2X1.5LG6 2.25 x 1.62 57.2 x 41.1 0.20 5.0 C2LG6 6 120 120
F2X2LG6 2.25 x 2.12 57.2 x 53.8 0.20 5.0 C2LG6 6 120 120
F2X3LG6 2.25 x 3.12 57.2 x 79.2 0.20 5.0 C2LG6 6 60 120 D1.
Terminals
.20 TYP [5.0] F2X4LG6 2.25 x 4.10 57.2 x 104.1 0.20 5.0 C2LG6 6 60 120
Multiple slot restrictors present with F2X5LG6 2.25 x 5.10 57.2 x 129.5 0.20 5.0 C2LG6 6 60 120
2" and greater duct wall height. F2.5X3LG6 2.75 x 3.12 69.9 x 79.2 0.20 5.0 C2.5LG6 6 120 120 D2.
F3X1LG6 3.25 x 1.12 82.6 x 28.4 0.20 5.0 C3LG6 6 120 120 Power
Connectors
F3X2LG6 3.25 x 2.12 82.6 x 53.8 0.20 5.0 C3LG6 6 120 120
F3X3LG6 3.25 x 3.12 82.6 x 79.2 0.20 5.0 C3LG6 6 60 120
D3.
F3X4LG6 3.25 x 4.10 82.6 x 104.1 0.20 5.0 C3LG6 6 60 120 Grounding
F3X5LG6 3.25 x 5.10 82.6 x 129.5 0.20 5.0 C3LG6 6 60 120 Connectors
F4X2LG6 4.25 x 2.12 108.0 x 53.8 0.20 5.0 C4LG6 6 60 120
To order cover with protective film F4X3LG6 4.25 x 3.12 108.0 x 79.2 0.20 5.0 C4LG6 6 60 120 E1.
add “-F” to part number. 6" cover F4X4LG6 4.25 x 4.10 108.0 x 104.1 0.20 5.0 C4LG6 6 60 120 Labeling
not available with film. Systems
F4X5LG6 4.25 x 5.10 108.0 x 129.5 0.20 5.0 C4LG6 6 60 120
F6X4LG6 6.25 x 4.15 158.8 x 105.4 0.20 5.0 C6LG6 6 60 120
Part number shown for LG (Light Gray). For other color availability see color selection guide, page C1.48. E2.
Base and cover sold separately. Labels
*“H” dimension includes duct and cover.
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.15
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview Features and Benefits – Panduct ® Flush Cover Type D Round Hole Wiring Duct
Available in sixteen sizes from 1" x 2" up to 4" x 4" in a variety of colors.
B1.
Cable Ties
C1.
Wiring Specially
Duct formulated
lead-free PVC
material
C2.
Surface
Raceway
D1.
Terminals
D2.
Power
Connectors
Panduct ® Wire Retainers Panduct ® Divider Wall
for Type D Wiring Duct Create separate wiring channels
D3. Contain wiring when duct within the wiring duct base. Available
Grounding
Connectors cover is opened. Wire retainers in solid or slotted wall styles.
mount onto walls with pressure (see page C1.26)
sensitive adhesive.
E1. (see page C1.28)
Labeling
Systems
E4.
Permanent
Identification
Panduct ® Installation Tools
Wide selection of hand tools for
E5. cutting and installing wiring duct.
Lockout/ (see page C1.34)
Tagout
& Safety
Solutions
F.
Index
• Round hole design has multiple rows of holes to retain and support • Conforms with NFPA 79-2007 section 13.3.1 requirement
wire at variable heights and positions for flame retardant material B1.
• Material: Lead-free PVC • Provided with mounting holes Cable Ties
• UL recognized continuous use temperature: 122°F (50°C) • Base and cover length is 6 feet
• UL 94 flammability rating of V-0 B2.
Cable
Accessories
Std. Base Cover
Base Duct Size (W x H)* Cover Pkg. Ctn. Ctn.
Part Number In. mm Part Number Qty. Qty. Qty. B3.
Stainless
D1X2LG6 1.26 x 2.12 32.0 x 53.8 C1LG6 6 120 120 Steel Ties
D1X3LG6 1.26 x 3.12 32.0 x 79.2 C1LG6 6 120 120
D1X4LG6 1.26 x 4.10 32.0 x 104.1 C1LG6 6 120 120
C1.
D1.5X2LG6 1.75 x 2.12 44.5 x 53.8 C1.5LG6 6 120 120 Wiring
D1.5X3LG6 1.75 x 3.12 44.5 x 79.2 C1.5LG6 6 120 120 Duct
E1.
Labeling
Systems
E2.
Labels
E3.
To order cover with protective film Pre-Printed
add “-F” to part number. 6" cover & Write-On
not available with film. Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.17
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview
Features and Benefits – Panduct ® Type MC Metric Narrow Slot Wiring Duct
Available in 20 sizes from 25mm x 25mm up to 100mm x 100mm in international gray and white colors.
B1.
Cable Ties
B3.
Stainless
Steel Ties Narrow finger/slot design
matches the spacing of
C1.
high-density components
Wiring
Duct
C2.
Surface
Raceway Flush cover design
provides a neat
C3. finished appearance
Abrasion
Protection
C4.
Cable DIN 43 659 metric mounting
Management Specially
hole pattern meets European
formulated Upper and lower scorelines allow requirements
lead-free PVC easy fingers and sidewall section
D1. material removal saving installation time
Terminals
D2.
Power
Connectors
Panduct ® Wire Retainers for Panduct ® Divider Wall
D3.
Type MC Wiring Duct Create separate wiring channels
Grounding Contain wiring when duct cover is within the wiring duct base. Available
Connectors opened. Wire retainers snap easily in solid or slotted wall styles.
between duct fingers. (see page C1.26)
(see page C1.29)
E1.
Labeling
Systems
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
• CE compliant and metric sizing for control panels intended for • Conforms with NFPA 79-2007 section 13.3.1 requirement
European applications for flame retardant material B1.
• Material: Lead-free PVC • Provided with DIN 43 659 mounting holes Cable Ties
• UL recognized continuous use temperature: 122°F (50°C) • Duct and cover packaged together in 2m lengths
• UL 94 flammability rating of V-0 B2.
Cable
Accessories
Base
and Replacement
Cover Cover B3.
Base and Replacement Pkg. Std. Stainless
Cover Part Duct Size (W x H)* Slot Width Cover Qty. Pkg. Steel Ties
Number mm In. In. mm Part Number (m) Qty.
MC25X25IG2 24.6 x 23.6 0.97 x 0.93 0.20 5.0 C25IG2 20 20 C1.
MC25X37IG2 24.6 x 35.8 0.97 x 1.41 0.20 5.0 C25IG2 20 20 Wiring
Duct
MC25X50IG2 24.6 x 47.8 0.97 x 1.88 0.20 5.0 C25IG2 20 20
MC25X62IG2 24.6 x 59.7 0.97 x 2.35 0.20 5.0 C25IG2 20 20
C2.
MC25X75IG2 24.6 x 72.4 0.97 x 2.85 0.20 5.0 C25IG2 20 20 Surface
W
MC37X37IG2 37.1 x 35.8 1.46 x 1.41 0.20 5.0 C37IG2 20 20 Raceway
0.50 TYP [12.7] MC75X50IG2 74.7 x 48.0 2.94 x 1.89 0.20 5.0 C75IG2 20 20
D1.
MC75X62IG2 74.7 x 59.7 2.94 x 2.35 0.20 5.0 C75IG2 20 20 Terminals
MC75X75IG2 74.7 x 72.4 2.94 x 2.85 0.20 5.0 C75IG2 10 20
MC75X100IG2 74.7 x 97.8 2.94 x 3.85 0.20 5.0 C75IG2 10 20
D2.
MC100X50IG2 99.6 x 48.0 3.92 x 1.89 0.20 5.0 C100IG2 10 20 Power
0.20 TYP [5.0] Connectors
MC100X75IG2 99.6 x 72.4 3.92 x 2.85 0.20 5.0 C100IG2 10 20
Multiple slot restrictors present with
62mm and greater duct wall height. MC100X100IG2 99.6 x 97.8 3.92 x 3.85 0.20 5.0 C100IG2 10 20
D3.
Available in IG (International Gray) and WH (White) colors. Grounding
Base and cover sold together. Connectors
*"H" dimension includes duct and cover.
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.19
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview
Features and Benefits – Panduct ® Type FS Solid Wall Raceway
Available in 27 sizes from .5" x .5" up to 6" x 4" in a variety of colors.
B1.
Cable Ties
B2.
Cable
Accessories
Non-slip cover liner
prevents cover slide
B3.
Stainless
Steel Ties Specially
formulated
lead-free PVC
C1. material
Wiring
Duct
C2.
Surface
Raceway
Flush cover design
provides a neat and
C3. finished appearance
Abrasion
Protection
C4.
Cable
Management
D2.
Power
Connectors
Panduct ® Wire Retainers for Panduct ® Divider Wall
D3.
Type FS Solid Wall Raceway Create separate wiring channels
Grounding Contain wiring when duct cover within the wiring duct base. Available
Connectors is opened. Wire retainers mount in solid or slotted wall styles.
onto walls with pressure (see page C1.26)
sensitive adhesive.
E1. (see page C1.28)
Labeling
Systems
E4.
Permanent
Identification Panduct ® Installation Tools
Wide selection of hand tools for
E5. cutting and installing wiring duct.
Lockout/ (see page C1.34)
Tagout
& Safety
Solutions
F.
Index
• Solid wall design fully encloses cables providing maximum • UL recognized continuous use temperature: 122°F (50°C)
protection and aesthetics • UL 94 flammability rating of V-0 B1.
• Material: Lead-free PVC Cable Ties
• Base and cover length is 6 feet
E2.
Labels
E3.
Pre-Printed
To order cover with protective film & Write-On
add “-F” to part number. 6'' cover Markers
not available with film.
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.21
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview
Wiring Duct for Special Environments
Features and Benefits – Panduct ® Type NNC Halogen-Free Metric Wiring Duct
B1.
Cable Ties
Available in fourteen sizes from 25mm x 25mm up to 100mm x 100mm in light gray and white.
B2.
Cable
Accessories
DIN 43 659 metric Non-slip cover
mounting hole liner prevents
pattern meets cover slide
B3. European requirements
Stainless
Steel Ties
D2.
Power
Connectors
Panduct ® Type NNC Halogen-Free Panduct ® Nylon Rivets
D3. Solid Divider Wall Fast, lowest cost mounting method.
Grounding Create separate wiring channels (see page C1.34)
Connectors within the wiring duct base.
(see page C1.23)
E1.
Labeling
Systems
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
• Material: Halogen-free modified polyphenylene oxide (mPPO) • Conforms with NFPA 79-2007 section 13.3.1 requirement for
material as verified with IEC 60754-2 test method (test on gases flame retardant material B1.
evolved during combustion of electric cables) • Provided with DIN 43 659 mounting holes Cable Ties
• UL recognized continuous use temperature: 203°F (95°C) • Metric sizing and finger progression
• UL 94 flammability rating of V-0 • Duct and cover packaged together in two meter lengths B2.
Cable
Accessories
B3.
Stainless
Steel Ties
Base
and Replacement C1.
Cover Cover Wiring
Replacement Ctn. Ctn. Duct
Duct Size (W x H)* Slot Width
Base and Cover Cover Qty. Qty.
Part Number mm In. In. mm Part Number (m) (m)
C2.
NNC25X25LG2 24.6 x 23.6 .97 x .93 .39 10.0 NC25LG2 20 20 Surface
NNC25X37LG2 24.6 x 35.8 .97 x 1.41 .39 10.0 NC25LG2 20 20 Raceway
NNC25X50LG2 24.6 x 47.8 .97 x 1.88 .39 10.0 NC25LG2 20 20
NNC25X75LG2 24.6 x 72.4 .97 x 2.85 .39 10.0 NC25LG2 20 20 C3.
W NNC37X37LG2 37.1 x 35.8 1.46 x 1.41 .39 10.0 NC37LG2 20 20 Abrasion
Protection
NNC37X50LG2 37.1 x 47.8 1.46 x 1.88 .39 10.0 NC37LG2 20 20
NNC37X75LG2 37.1 x 72.4 1.46 x 2.85 .39 10.0 NC37LG2 20 20
C4.
H NNC50X50LG2 49.5 x 47.8 1.95 x 1.88 .39 10.0 NC50LG2 20 20 Cable
NNC50X75LG2 49.5 x 72.4 1.95 x 2.85 .39 10.0 NC50LG2 10 20 Management
NNC50X100LG2 49.5 x 97.8 1.95 x 3.85 .39 10.0 NC50LG2 10 20
NNC75X75LG2 74.7 x 72.4 2.94 x 2.85 .39 10.0 NC75LG2 10 20
D1.
.98 TYP [25.0] NNC100X50LG2 99.6 x 47.8 3.92 x 1.88 .39 10.0 NC100LG2 10 20 Terminals
NNC100X75LG2 99.6 x 72.4 3.92 x 2.85 .39 10.0 NC100LG2 10 20
NNC100X100LG2 99.6 x 97.8 3.92 x 3.85 .39 10.0 NC100LG2 10 20
D2.
Available in LG (Light Gray) and WH (White). Power
Do not allow cutting, tapping, or cleaning fluids that contain hydrocarbons to come in contact with type NNC Connectors
wiring duct as it will cause stress cracking. See page C1.49 for a list of chemicals to avoid.
.39 TYP [10.0] *"H" dimension includes duct and cover.
D3.
Multiple slot restrictors present with
Grounding
75mm and greater duct wall height. Connectors
E1.
Labeling
Panduct Type NNC Divider Wall
® Systems
• NNC solid divider wall can be mounted inside NNC and NE wiring • Simply install the divider wall base when mounting the duct
duct to create multiple channels and snap the divider wall onto mounting base, DB-C E2.
Labels
• Material: Halogen-free modified polyphenylene oxide (mPPO)
Std. E3.
For Nominal Std. Ctn. Pre-Printed
Length Duct Height Pkg. Qty. & Write-On
Part Number (m) (mm) Qty. (m) Markers
NNC50DWH2 2 50 2 40
E4.
NNC75DWH2 2 75 2 40
Permanent
Available in WH (White) color only. Identification
NOTE: Must be used with mounting base DB-C (see page C1.26), which is sold separately. Install mounting bases
to the duct channel, locate within 2" of each divider wall end and at least every 12" along the length. E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.23
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview Panduct ® Type NE Halogen-Free Wiring Duct
• Material: Halogen-free modified polyphenylene oxide (mPPO) • Provided with mounting holes
B1. • UL recognized continuous use temperature: 203°F (95°C) • Base and cover length is 6 feet
Cable Ties
• UL 94 flammability rating of V-0
B2.
Cable
Accessories
Std. Base Cover
Duct Size (W x H)* Slot Width
Base Cover Pkg. Ctn. Ctn.
B3.
Stainless Part Number In. mm In. mm Part Number Qty. Qty. Qty.
Steel Ties NE.5X.5WH6 .63 x .56 16.0 x 14.2 .38 9.7 NC.5WH6 6 120 120
NE.5X1WH6 .63 x 1.06 16.0 x 26.9 .31 7.9 NC.5WH6 6 120 120
C1. NE1X1WH6 1.14 x 1.06 29.0 x 26.9 .31 7.9 NC1WH6 6 120 120
Wiring NE1X1.5WH6 1.14 x 1.62 29.0 x 41.1 .31 7.9 NC1WH6 6 120 120
Duct
NE1X2WH6 1.14 x 2.06 29.0 x 52.3 .31 7.9 NC1WH6 6 120 120
NE1X3WH6 1.14 x 3.06 29.0 x 77.7 .31 7.9 NC1WH6 6 120 120
C2.
W NE1X4WH6 1.14 x 4.06 29.0 x 103.1 .31 7.9 NC1WH6 6 60 120
Surface
Raceway NE1.5X1.5WH6 1.64 x 1.62 41.7 x 41.1 .31 7.9 NC1.5WH6 6 120 120
NE1.5X2WH6 1.64 x 2.06 41.7 x 52.3 .31 7.9 NC1.5WH6 6 120 120
C3. H NE1.5X3WH6 1.64 x 3.06 41.7 x 77.7 .31 7.9 NC1.5WH6 6 120 120
Abrasion NE1.5X4WH6 1.64 x 4.06 41.7 x 103.1 .31 7.9 NC1.5WH6 6 60 120
Protection
NE2X1WH6 2.14 x 1.06 54.4 x 26.9 .31 7.9 NC2WH6 6 120 120
NE2X2WH6 2.14 x 2.06 54.4 x 52.3 .31 7.9 NC2WH6 6 120 120
C4.
Cable NE2X3WH6 2.14 x 3.06 54.4 x 77.7 .31 7.9 NC2WH6 6 60 120
Management NE2X4WH6 2.14 x 4.06 54.4 x 103.1 .31 7.9 NC2WH6 6 60 120
NE3X1WH6 3.14 x 1.06 79.8 x 26.9 .31 7.9 NC3WH6 6 120 120
F
NE3X2WH6 3.14 x 2.06 79.8 x 52.3 .31 7.9 NC3WH6 6 120 120
D1.
Terminals NE3X3WH6 3.14 x 3.06 79.8 x 77.7 .31 7.9 NC3WH6 6 60 120
NE3X4WH6 3.14 x 4.06 79.8 x 103.1 .31 7.9 NC3WH6 6 60 120
NE3X5WH6 3.14 x 5.06 79.8 x 128.5 .38 9.7 NC3WH6 6 60 120
D2. E
Power NE4X2WH6 4.14 x 2.06 105.2 x 52.3 .31 7.9 NC4WH6 6 60 120
Connectors E F NE4X3WH6 4.14 x 3.06 105.2 x 77.7 .31 7.9 NC4WH6 6 60 120
For .5" duct height: .37" [9.4] .80" [20.3]
1" to 2" duct height: .31" [7.9] .80" [20.3] NE4X4WH6 4.14 x 4.06 105.2 x 103.1 .31 7.9 NC4WH6 6 60 120
3" to 4" duct height: .31" [7.9] 1.00" [25.4]
D3. 5" duct height: .38" [9.4] 1.33" [33.8]
NE4X5WH6 4.14 x 5.06 105.2 x 128.5 .38 9.7 NC4WH6 6 60 120
Grounding
Connectors Available in WH (White) only.
Do not allow cutting, tapping, or cleaning fluids that contain hydrocarbons to come in contact with type NE wiring
duct as it will cause stress cracking. See page C1.49 for list of chemicals to avoid.
E1. Base and cover sold separately.
Labeling *”H” dimension includes duct and cover.
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
wiring duct.
B2.
Cable
Accessories
B3.
Some of the features and benefits found in Panduct ® Stainless
Steel Ties
Tools and Accessories include:
• Wide selection of hand tools for cutting and installing C1.
Wiring
wiring duct Duct
• Snap-in wire retainers to retain cabling when the cover is
removed or during cable installation C2.
Surface
• Divider walls that mount within the duct, enabling Raceway
D1.
Terminals
D2.
Power
Connectors
D3.
Grounding
Connectors
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.25
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview Panduct ® Type FL Flexible Wiring Duct
• Material: Flexible Polypropylene • UL 94 flammability rating of V-2
B1. • UL Recognized continuous use temperature: 149°F (65°C) • Factory applied adhesive tape provided for easy positioning**
Cable Ties
Std.
Duct Size (W x H)* Length Pkg.
B2. Part Number In. mm In. mm Qty.
Cable
Accessories FL12X12LG-A .49 x .49 12.5 x 12.5 19.7 500 112
FL25X25LG-A .98 x .98 25.0 x 25.0 19.7 500 70
FL50X50LG-A 1.97 x 1.97 50.0 x 50.0 19.7 500 32
B3.
Stainless Available in LG (RAL 7040 Light Gray) color only. Unit of measure is pieces.
Steel Ties *“H” dimension includes duct and cover.
**Adhesive tape is not meant for permanent mounting of wiring duct. One mounting hole on each end will be
exposed for permanent mounting with fasteners. For best results, wiring duct should be applied to clean, dry,
C1. grease-free surfaces. We recommend the surface be cleaned prior to wiring duct installation.
Wiring W
Duct
.20 TYP [5.0]
C2.
Surface H
Raceway
.25 TYP [6.2]
C3.
Abrasion
Protection
C4.
Panduct ® Divider Wall
Cable • Wiring duct divider wall can be mounted inside any type of • Meets UL508/508A insulation material requirement for barrier
Management Panduit PVC wiring duct to create multiple channels between conductors
• Simply install the divider wall base when mounting the duct • UL 94 flammability rating of V-0
and snap the divider wall onto the mounting base • Material: Lead-free PVC
D1.
Terminals
• All versions snap onto DB-C mounting base
• Divider wall heights 2" and greater have a scoreline feature
allowing sections to be removed leaving a smooth edge
D2.
Power Std. Std.
Connectors Pkg. Ctn.
Part Number Used with Anchors Qty. Qty.
Panduct ® Divider Wall Mounting Base
D3.
Grounding DB-C Panduit NR1 or #8, #10, M4 or M5 screw 100 1000
Connectors
DB-C
Std. Std.
For Nominal Duct Height Length
E1. Pkg. Ctn.
Labeling Part Number In. mm Ft. m Color Qty. Qty.
Systems Panduct Solid Divider Wall
®
F. SD*H6
Index
• NNC solid divider wall can be mounted inside NNC and NE • Simply install the divider wall base when mounting the duct
wiring duct to create multiple channels and snap the divider wall onto mounting base, DB-C B1.
• Material: Halogen-free modified polyphenylene oxide (mPPO) Cable Ties
Std. Std.
For Nominal Duct Height B2.
Pkg. Ctn.
Cable
Part Number In. mm Qty. Qty.
Accessories
NNC50DWH2 2.00 50 2 40
NNC75DWH2 3.00 75 2 40
B3.
Available in WH (White) color only. Stainless
NOTE: Must be used with mounting base DB-C (see page C1.26), which is sold separately. Install mounting bases Steel Ties
to the duct channel, locate within 2" of each divider wall end and at least every 12" along the length.
C1.
Wiring
Duct
C2.
Surface
Raceway
C3.
Abrasion
Protection
C4.
Cable
Management
D1.
Terminals
D2.
Power
Connectors
D3.
Grounding
Connectors
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.27
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview Panduct ® Type G and H Wiring Duct Wire Retainers
• Insert between fingers of type G and H to contain wiring when • Adjustable height
B1. cover is removed • Material: ABS
Cable Ties
Std. Std.
For Duct Width For Duct Height Pkg. Ctn.
B2. Part Number In. (mm) In. (mm) Qty. Qty.
Cable
Accessories
WR2-C 2.00 (50.8) 2.00 – 4.00 (50.8 – 101.6) 100 1000
WR2H-C 2.00 (50.8) 2.00 – 4.00 (50.8 – 101.6) 100 1000
WR3-C 3.00 (76.2) 2.00 – 4.00 (50.8 – 101.6) 100 1000
B3.
Stainless WR4-C 4.00 (101.6) 2.00 – 4.00 (50.8 – 101.6) 100 1000
Steel Ties WR5-C Use with: 3x5, 4x5, or 6x4 Use with: 3x5, 4x5, or 6x4 100 1000
*For 2" width type H hinged cover wiring duct use part number WR2H-C.
C1.
Wiring
Duct
C2.
Surface
Raceway
C3.
Abrasion
Protection Panduct ® Solid Wall Raceway Type FS and Type D Wiring Duct Wire Retainer
• Mounts onto walls of type FS raceway or type D duct with pressure • Full length is used with 2 inch wide duct; for small widths, break off
C4. sensitive adhesive segments at scorelines
Cable
Management • One size fits three different duct widths • Material: Lead-free PVC
Std. Std.
D1. For Duct Width Pkg. Ctn.
Terminals Part Number In. (mm) Qty. Qty.
WRS-A-C10 1.00 (25.4) 100 1000
1.50 (38.1)
D2. 2.00 (50.8)
Power
Connectors Full length is used with 2" wide duct. For smaller widths, break off segments at scorelines.
D3.
Grounding
Connectors
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
• Used to contain wiring when cover is removed and can also be • FMWR-C is compatible with type MC duct sizes
used as a labeling device • Material: Lead-free PVC B1.
• FWR-C is compatible with type F and HN duct sizes Cable Ties
C1.
Wiring
Duct
C2.
Surface
Raceway
Labeling Inside Duct – Labeling Outside Duct –
Snaps onto duct fingers. Full Break off the last segment from wire retainer below
length for use with 4" wide 1.5" mark and snap onto the back of the remaining C3.
duct. For smaller widths, break segment. Install label and mount between fingers Abrasion
off segments at scorelines. facing outward. Protection
C4.
Cable
Management
Panduct ® Duct Corner Strip with 1" Bend Radius Control
• Create a strong rigid corner at wiring duct junctions • Easy to install two-piece design D1.
• Provide bend radius protection for cabling as required in • Compatible with all styles of Panduit wiring duct Terminals
NFPA 79-2007 section 13.1.5.9 and TIA/EIA-568-B and 569-A • UL 94 flammability rating of V-0
• Available in 6 foot lengths that can be cut to size to meet any • Material: Lead-free PVC
size requirement D2.
Power
Connectors
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com C1.29
ELECTRICAL SOLUTIONS
A.
System
Overview Panduct ® Duct Corner Strip
• Slide onto duct at corner or t-junctions for smooth, round corners • Compatible with all styles of Panduit wiring duct
B1. • Available in 6 foot lengths that can be cut to size to meet • UL 94 flammability rating of V-0
Cable Ties
any requirement • Material: Lead-free PVC
• Easy to install one-piece design
B2.
Cable Std. Std.
Accessories For Nominal Duct Height Pkg. Ctn.
Part Number Part Description In. mm Color Qty. Qty.
B3. 6' Lengths for use with all Types of PVC Wiring Duct
Stainless CS1LG6 6 foot length is cut by user to fit All sizes All sizes Light 6 120
Steel Ties duct height. (Cut to (Cut to Gray
height)* height)*
C1. CS1LG6
*Refer to Cutting Guide below.
Wiring
Duct
C2.
Surface
Raceway
C3.
Abrasion
Protection
C4.
Cable
Management Cutting Guide for Duct Corner Strips (CSC1**6, CS1**6)
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
Snap-Clip Mounting Brackets for use with Types G, F, FS and D Wiring Duct
S1F-C #8-32 x 1/4 (Provided) 1.00 25.4 100 1000 B3.
Stainless
S1.5F-C #8-32 x 1/4 (Provided) 1.50 38.1 100 1000 Steel Ties
S2F-C #8-32 x 1/4 (Provided) 2.00 50.8 100 1000
S3F-C #8-32 x 1/4 (Provided) 3.00 76.2 100 1000 C1.
S4F-C #8-32 x 1/4 (Provided) 4.00 101.6 100 1000 Wiring
Duct
Snap-Clip Mounting Brackets for use with Types MC and NNC Wiring Duct
SNS25F-C #8-32 x 1/4 (User Supplied) 1.00 25 100 1000
SNS37F-C #8-32 x 1/4 (User Supplied) 1.50 37 100 1000 C2.
Surface
SNS50F-C #8-32 x 1/4 (User Supplied) 2.00 50 100 1000 Raceway
SNS62F-C #8-32 x 1/4 (User Supplied) 2.50 62 100 1000
SNS75F-C #8-32 x 1/4 (User Supplied) 3.00 75 100 1000 C3.
Abrasion
Protection
C4.
Cable
Management
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com C1.31
E L E C T R I C A L S O LU T I O N S
A.
System
Overview Adhesive Tape for Wiring Duct
• Recommended installation temperature is 70°F (21°C) • Optimum recommended dwell time for acrylic adhesive is 8 hours
B1. • UL Recognized service temperature is 32°F (0°C) to 140°F (60°C) • Recommended tape load is 1/2 lb. per square inch of tape area
Cable Ties
B2. Roll
Cable
Tape Std. Std.
Duct Size Part Length Pkg. Ctn.
Accessories
(W x H) Number Yds. m Qty. Qty.
.5 x .5 thru 1.5 x 4 P32W2A2-50-7 7.0 6.4 1 100
B3.
Stainless P32W2A2-50-72 72.0 65.5 1 9
Steel Ties 2 x 1 thru 3 x 3 P32W2A2-50-7 7.0 6.4 1 100
P32W2A2-50-72 72.0 65.5 1 9
C1. 3 x 4 thru 3 x 5 P32W2A2-75-7 7.0 6.4 1 60
Wiring P32W2A2-75-72 72.0 65.5 1 7
Duct
4 x 1.5 thru 4 x 3 P32W2A2-50-7 7.0 6.4 1 100
P32W2A2-75-72 72.0 65.5 1 9
C2.
Surface 4 x 4 thru 6 x 4 P32W2A2-75-7 7.0 6.4 1 60
Raceway P32W2A2-75-72 72.0 65.5 1 7
C3.
Abrasion
Protection Specifications for Factory Applied Tape
C4. Tape
Cable
Management Duct Size Rows of Width Thickness
(W x H) Tape In. mm In. mm
.5 x .5 through .75 x 2 1 .50 12.7 .03 .8
D1. 1 x 1 through 1.5 x 4 1 .75 19.1 .03 .8
Terminals
2 x 1 through 3 x 3 2 .50 12.7 .03 .8
3 x 4 through 3 x 5 2 .75 19.1 .03 .8
D2. 4 x 1.5 through 4 x 3 2 .50 12.7 .03 .8
Power
Connectors 4 x 4 through 6 x 4 2 .75 19.1 .03 .8
D3.
Grounding
Connectors
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
B2.
Cable
Accessories
G Duct G Duct G Duct F Duct F Duct FS Duct FS Duct FS Duct NE Duct B3.
Light Gray White Black Light Gray White Light Gray White Black White Stainless
G.5X.5LG6-A G.5X.5WH6-A — F.5X.5LG6-A — — — — — Steel Ties
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.33
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
E L E C T R I C A L S O LU T I O N S
A.
System
Overview Panduct ® Installation Tools
• Panduit ® Panduct ® Bench Mount Wiring Duct Cutting Tool and • TNR installs or removes Panduit nylon rivets, NR1-C and NR1-M,
B1. Duct Cutting Tool easily cut Panduct ® Wiring Duct and Cover quickly and easily
Cable Ties • DNT-100 notches duct sidewalls to bottom scoreline for tees • DFCT easily removes duct fingers in tight spaces
and corner junctions
B2.
Cable Std.
Accessories Pkg.
Part Number Part Description Qty
C3. DCT DFCT Duct Finger Cutting Tool (For use with all wide slotted duct types)
Abrasion
Protection DFCT Hand-held duct finger cutting tool. 1
Duct Notching Tool (For use with all wide slotted duct types)
C4. DNT-100 Hand-held sidewall notching tool. 1
Cable
Management
Nylon Rivet Installation Tool
TNR Hand-held nylon rivet installation tool. 1
DNT-100 TNR
D1.
Terminals Nylon Rivets
NR1-C Nylon rivet for use with TNR rivet tool. 100
Mean pull-off force PVC: 90 lbs. Type NE/Type NNC: 70 lbs.
D2. Mean shear force: PVC 139 lbs. Type NE/Type NNC: 126 lbs.
Power NR1-M Nylon rivet for use with TNR rivet tool. 1000
Connectors
Mean pull-off force PVC: 90 lbs. Type NE/Type NNC: 70 lbs.
NR1 Mean shear force: PVC 139 lbs. Type NE/Type NNC: 126 lbs.
D3. Always use approved safety goggles when using any tools.
Grounding
Connectors
ANSI
Total Thickness of Panel and Duct Panel Hole Dia. Needed Standard
E1.
Labeling In. mm In. mm Drill Bit
Systems .158 – .187 4.0 – 4.7 .187 4.7 #15
.188 – .218 4.8 – 5.5 .193 4.9 #11
.219 – .250 5.6 – 6.4 .203 5.2 #7
E2.
Labels .251 – .281 6.5 – 7.1 .213 5.4 #4
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
B3.
4.00 (101.6) Stainless
Steel Ties
1.18 1.68
.87
(30.0) (42.7)
(22.0) C1.
.31 (8.0) .63 (15.9) Wiring
TYP. TYP. Duct
C2.
Recommended Recommended Recommended Surface
Max. Component Max. Component Max. Component Raceway
2.35 2.85 Width 2.67 (67.9) 3.35
Width 2.62 (66.5) Width 3.67 (93.3)
(59.6) (72.3)
TYP. .20 (85.1)
TYP. TYP. C3.
(5.0)
TYP. Abrasion
2.00 2.00 Protection
(50.8) (50.8) .50 (12.7)
TYP. TYP. TYP.
C4.
Cable
Panduct PanelMax Noise Shield Dimensions
® ™
Management
Dimensions are shown for reference only. Contact Panduit Customer Service at 800-777-3300 for specific dimensional needs.
X 1.40 D2.
(35.6)
Power
.75 .20
(19.0) (5.1) Connectors
.96 .80 1.00
(24.4) (20.3) (25.4)
2.62 D3.
(66.6) Grounding
Part No. X Sidewall: SD2EMI shown. Bottom view. Bonding clip (for use with Connectors
SD3EMI, SD4EMI sidewall feature wiring duct).
SD2EMI 1.82 (46.1) two pairs of cable tie slots per section.
SD3EMI 2.88 (73.2)
E1.
SD4EMI 3.86 (98.2) Labeling
All dimension shown in inches (mm).
Systems
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com C1.35
E L E C T R I C A L S O LU T I O N S
A.
System
Overview Panduct ® Type G and D Wiring Duct Dimensions
Dimensions are shown for reference only. Contact Panduit Customer Service at 800-777-3300 for specific dimensional needs.
Duct Size Dimensions – Inches (mm)
B1. (W x H) A B C D E F H K T
Cable Ties
For .5" high duct. .5 x .5 .69 .60 .69 .38 .37 .80 .50 .05
>
C
(12.7) x (12.7) (17.5) (15.2) (17.5) (9.5) (9.3) (20.3) (12.7) (1.3)
F
.5 x 1 .69 1.06 .69 .75 .31 .80 1.00 .05
B2. >
(12.7) x (25.4) (17.5) (26.9) (17.5) (19.1) (7.9) (20.3) (25.4) (1.3)
Cable B D .5 x 2 .69 2.03 .69 1.63 .31 .80 2.00 .08
T H >
Accessories (12.7) x (50.8) (17.5) (51.6) (17.5) (41.3) (7.9) (20.3) (50.8) (2.0)
> .75 x .75 .93 .82 .94 .56 .31 .80 0.75 .06
A E
(19.1) x (19.1) (23.6) (20.8) (23.9) (14.3) (7.9) (20.3) (19.1) (1.4)
B3.
> .75 x 1 .93 1.06 .94 .75 .31 .80 1.00 .06
Stainless
Steel Ties (19.1) x (25.4) (23.6) 26.9 (23.9) (19.1) (7.9) (20.3) (25.4) (1.4)
For .75", 1", 1.5", 2", 3", 4" and 5" high duct.
> .75 x 1.5 .93 1.57 .94 1.20 .31 .80 1.50 .07
C
F (19.1) x (38.1) (23.6) (39.9) (23.9) (30.5) (7.9) (20.3) (38.1) (1.8)
C1. > .75 x 2 .93 2.03 .94 1.63 .31 .80 2.00 .08
ON CENTERLINE
Wiring (19.1) x (50.8) (23.6) (51.6) (23.9) (41.3) (7.9) (20.3) (50.8) (2.0)
Duct T B H
D
> 1x1 1.26 1.12 1.25 .75 .31 .80 1.00 .06
(25.4) x (25.4) (32.0) (28.4) (31.8) (19.1) (7.9) (20.3) (25.4) (1.4)
> 1 x 1.5 1.26 1.62 1.25 1.20 .31 .80 1.50 .07
C2. A E (25.4) x (38.1) (32.0) (41.1) (31.8) (30.5) (7.9) (20.3) (38.1) (1.8)
Surface 1x2 1.26 2.12 1.25 1.63 .31 .80 2.00 .08
Raceway (25.4) x (50.8) (32.0) (53.8) (31.8) (41.3) (7.9) (20.3) (50.8) (2.0)
1x3 1.26 3.12 1.25 2.63 .31 1.00 3.00 .10
Note: ‘A’ dimension is measured at base. (25.4) x (76.2) (32.0) (79.2) (31.8) (66.7) (7.9) (25.4) (76.2) (2.4)
Note: ‘K’ dimension shown in mounting hole 1x4 1.26 4.10 1.25 3.63 .31 1.00 4.00 .11
C3.
Abrasion dimensions below. (25.4) x (101.6) (32.0) (104.1) (31.8) (92.1) (7.9) (25.4) (101.6) (2.7)
Protection 1.5 x 1 1.75 1.12 1.75 .75 .31 .80 1.00 .06
>
(38.1) x (25.4) (44.5) (28.4) (44.5) (19.1) (7.9) (20.3) (25.4) (1.5)
1.5 x 1.5 1.75 1.62 1.75 1.20 .31 .80 1.50 .07
>
C4. (38.1) x (38.1) (44.5) (41.1) (44.5) (30.5) (7.9) (20.3) (38.1) (1.8)
Cable 1.5 x 2 1.75 2.12 1.75 1.63 .31 .80 2.00 .08
Management (38.1) x (50.8) (44.5) (53.8) (44.5) (41.3) (7.9) (20.3) (50.8) (2.0)
1.5 x 3 1.75 3.12 1.75 2.63 .31 1.00 3.00 .10
.44 +- .02
[11.2 +- 0.5] (38.1) x (76.2) (44.5) (79.2) (44.5) (66.7) (7.9) (25.4) (76.2) (2.4)
.67 +- .06 TYP 1.5 x 4 1.75 4.10 1.75 3.63 .31 1.00 4.00 .11
D1. [16.94 +- 1.5]
Terminals (38.1) x (101.6) (44.5) (104.1) (44.5) (92.1) (7.9) (25.4) (101.6) (2.7)
> 2x1 2.25 1.12 2.25 .75 .31 .80 1.00 .50 .06
(50.8) x (25.4) (57.2) (28.4) (57.2) (19.1) (7.9) (20.3) (25.4) (12.7) (1.5)
H > 2 x 1.5 2.25 1.62 2.25 1.20 .31 .80 1.50 .50 .07
D2. (50.8) x (38.1) (57.2) (41.1) (57.2) (30.5) (7.9) (20.3) (38.1) (12.7) (1.8)
Power 2x2 2.25 2.12 2.25 1.63 .31 .80 2.00 .50 .08
Connectors (50.8) x (50.8) (57.2) (53.8) (57.2) (41.3) (7.9) (20.3) (50.8) (12.7) (2.0)
For 2" duct height = 3 rows of holes 2x3 2.25 3.12 2.25 2.63 .31 1.00 3.00 .50 .10
3" duct height = 4 rows of holes (50.8) x (76.2) (57.2) (79.2) (57.2) (66.7) (7.9) (25.4) (76.2) (12.7) (2.4)
D3. 4" duct height = 6 rows of holes
2x4 2.25 4.10 2.25 3.63 .31 1.00 4.00 .50 .11
Grounding (50.8) x (101.6) (57.2) (104.1) (57.2) (92.1) (7.9) (25.4) (101.6) (12.7) (2.7)
Connectors
> 2x5 2.25 5.10 2.25 4.63 .38 1.33 5.00 .50 .12
(50.8) x (127.0) (57.2) (129.5) (57.2) (117.5) (9.5) (33.9) (127.0) (12.7) (2.9)
Mounting Hole Dimensions 2.5 x 3 2.75 3.12 2.75 2.63 .31 1.00 3.00 .73 .10
E1.
For .5", .75", 1", and 1.5" wide duct. (63.5) x (76.2) (69.9) (79.2) (69.9) (66.7) (7.9) (25.4) (76.2) (18.4) (2.5)
Labeling
Systems > 3x1 3.25 1.12 3.25 .75 .31 .80 1.00 1.00 .07
.50 TYP (76.2) x (25.4) (82.6) (28.4) (82.6) (19.1) (7.9) (20.3) (25.4) (25.4) (1.8)
[12.7] 3x2 3.25 2.12 3.25 1.63 .31 .80 2.00 1.00 .08
.20 TYP (76.2) x (50.8) (82.6) (53.8) (82.6) (41.3) (7.9) (20.3) (50.8) (25.4) (2.0)
E2. [5.0]
3x3 3.25 3.12 3.25 2.63 .31 1.00 3.00 1.00 .10
Labels (76.2) x (76.2) (82.6) (79.2) (82.6) (66.7) (7.9) (25.4) (76.2) (25.4) (2.4)
C
L 3x4 3.25 4.10 3.25 3.63 .31 1.00 4.00 1.00 .11
(76.2) x (101.6) (82.6) (104.1) (82.6) (92.1) (7.9) (25.4) (101.6) (25.4) (2.7)
E3. 3x5 3.25 5.10 3.25 4.63 .38 1.33 5.00 1.00 .12
Pre-Printed 4.0 [101.6] TYP 2.0 >
[50.8] (76.2) x (127.0) (82.6) (129.5) (82.6) (117.5) (9.5) (33.9) (127.0) (25.4) (2.9)
& Write-On 4 x 1.5 4.25 1.62 4.25 1.20 .31 .80 1.50 1.50 .07
Markers >
(101.6) x (38.1) (108.0) (41.1) (108.0) (30.5) (7.9) (20.3) (38.1) (38.1) (1.8)
For 2.0", 2.5", 3", 4" and 6" wide duct. 4x2 4.25 2.12 4.25 1.63 .31 0.80 2.00 1.50 .08
E4. (101.6) x (50.8) (108.0) (53.8) (108.0) (41.3) (7.9) (20.3) (50.8) (38.1) (2.0)
Permanent 4x3 4.25 3.12 4.25 2.63 .31 1.00 3.00 1.50 .10
Identification (101.6) x (76.2) (108.0) (79.2) (108.0) (66.7) (7.9) (25.4) (76.2) (38.1) (2.5)
K
C
L
4x4 4.25 4.10 4.25 3.63 .31 1.00 4.00 1.50 .11
E5. K (101.6) x (101.6) (108.0) (104.1) (108.0) (92.1) (7.9) (25.4) (101.6) (38.1) (2.7)
Lockout/ 4x5 4.25 5.10 4.25 4.63 .38 1.33 5.00 1.50 .12
>
Tagout (101.6) x (127.0) (108.0) (129.5) (108.0) (117.5) (9.5) (33.9) (127.0) (38.1) (2.9)
& Safety 4.0 [101.6] TYP 2.0 6x4 6.25 4.15 6.25 3.63 .31 1.00 4.00 2.50 .11
Solutions >
[50.8] (152.4) x (101.6) (158.8) (105.4) (158.8) (92.1) (7.9) (25.4) (101.6) (63.5) (2.8)
> Available for type G wiring duct only.
F. See page C1.13 and C1.17 for wiring duct color and size availability.
Index
ON CENTERLINE
(25.4) x (38.1) (32.0) (41.1) (31.8) (30.5) (5.0) (12.7) (38.1) (1.8)
C 1x2 1.26 2.12 1.25 1.63 .20 .50 2.00 .08 C1.
E
(25.4) x (50.8) (32.0) (53.8) (31.8) (41.3) (5.0) (12.7) (50.8) (2.0) Wiring
1x3 1.26 3.12 1.25 2.63 .20 .50 3.00 .10 Duct
(25.4) x (76.2) (32.0) (79.2) (31.8) (66.7) (5.0) (12.7) (76.2) (2.4)
B H D 1x4 1.26 4.10 1.25 3.63 .20 .50 4.00 .11
T
(25.4) x (101.6) (32.0) (104.1) (31.8) (92.1) (5.0) (12.7) (101.6) (2.7) C2.
1.5 x 1 1.75 1.12 1.75 .75 .20 .50 1.00 .06 Surface
(38.1) x (25.4) (44.5) (28.4) (44.5) (19.1) (5.0) (12.7) (25.4) (1.5) Raceway
A
F 1.5 x 1.5 1.75 1.62 1.75 1.20 .20 .50 1.50 .07
(38.1) x (38.1) (44.5) (41.1) (44.5) (30.5) (5.0) (12.7) (38.1) (1.8)
Note: ‘A’ dimension is measured at base. 1.5 x 2 1.75 2.12 1.75 1.63 .20 .50 2.00 .08 C3.
Note: ‘K’ dimension shown in mounting (38.1) x (50.8) (44.5) (53.8) (44.5) (41.3) (5.0) (12.7) (50.8) (2.0) Abrasion
hole dimensions below. 1.5 x 3 1.75 3.12 1.75 2.63 .20 .50 3.00 .10 Protection
(38.1) x (76.2) (44.5) (79.2) (44.5) (66.7) (5.0) (12.7) (76.2) (2.4)
1.5 x 4 1.75 4.10 1.75 3.63 .20 .50 4.00 .11
(38.1) x (101.6) (44.5) (104.1) (44.5) (92.1) (5.0) (12.7) (101.6) (2.7) C4.
2x1 2.25 1.12 2.25 .75 .20 .50 1.00 .50 .06 Cable
(50.8) x (25.4) (57.2) (28.4) (57.2) (19.1) (5.0) (12.7) (25.4) (12.7) (1.5) Management
2 x 1.5 2.25 1.62 2.25 1.20 .20 .50 1.50 .50 .07
(50.8) x (38.1) (57.2) (41.1) (57.2) (30.5) (5.0) (12.7) (38.1) (12.7) (1.8)
Mounting Hole Dimensions 2x2 2.25 2.12 2.25 1.63 .20 .50 2.00 .50 .08 D1.
For .5", .75", 1" and 1.5" wide duct. (50.8) x (50.8) (57.2) (53.8) (57.2) (41.3) (5.0) (12.7) (50.8) (12.7) (2.0) Terminals
2x3 2.25 3.12 2.25 2.63 .20 .50 3.00 .50 .10
.50 TYP (50.8) x (76.2) (57.2) (79.2) (57.2) (66.7) (5.0) (12.7) (76.2) (12.7) (2.4)
[12.7] 2x4 2.25 4.10 2.25 3.63 .20 .50 4.00 .50 .11
.20 TYP (50.8) x (101.6) (57.2) (104.1) (57.2) (92.1) (5.0) (12.7) (101.6) (12.7) (2.7)
D2.
[5.0] Power
2x5 2.25 5.10 2.25 4.63 .20 .50 5.00 .50 .12
Connectors
(50.8) x (127.0) (57.2) (129.5) (57.2) (117.5) (5.0) (12.7) (127.0) (12.7) (2.9)
C
L 3x1 3.25 1.12 3.25 .75 .20 .50 1.00 1.00 .07
(76.2) x (25.4) (82.6) (28.4) (82.6) (19.1) (5.0) (12.7) (25.4) (25.4) (1.7)
D3.
2.0 TYP 2.0 3x2 3.25 2.12 3.25 1.63 .20 .50 2.00 1.00 .08 Grounding
[50.8] [50.8] (76.2) x (50.8) (82.6) (53.8) (82.6) (41.3) (5.0) (12.7) (50.8) (25.4) (2.0) Connectors
3x3 3.25 3.12 3.25 2.63 .20 .50 3.00 1.00 .10
(76.2) x (76.2) (82.6) (79.2) (82.6) (66.7) (5.0) (12.7) (76.2) (25.4) (2.4)
For 2.0", 2.5", 3", 4" and 6" wide duct. 3x4 3.25 4.10 3.25 3.63 .20 50 4.00 1.00 .11 E1.
(76.2) x (101.6) (82.6) (104.1) (82.6) (92.1) (5.0) (12.7) (101.6) (25.4) (2.7) Labeling
3x5 3.25 5.10 3.25 4.63 .20 .50 5.00 1.00 .12 Systems
(76.2) x (127.0) (82.6) (129.5) (82.6) (117.5) (5.0) (12.7) (127.0) (25.4) (2.9)
K
C 4 x 1.5 4.25 1.62 4.25 1.50 .07
K
L > N/A N/A N/A N/A
(101.6) x (38.1) (108.0) (41.1) (108.0) (38.1) (1.8)
4x2 4.25 2.12 4.25 1.63 .20 .50 2.00 1.50 .08 E2.
(101.6) x (50.8) (108.0) (53.8) (108.0) (41.3) (5.0) (12.7) (50.8) (38.1) (2.0) Labels
2.0 TYP 2.0 4x3 4.25 3.12 4.25 2.63 .20 .50 3.00 1.50 .10
[50.8] [50.8] (101.6) x (76.2) (108.0) (79.2) (108.0) (66.7) (5.0) (12.7) (76.2) (38.1) (2.4)
4x4 4.25 4.10 4.25 3.63 .20 .50 4.00 1.50 .11 E3.
Pre-Printed
(101.6) x (101.6) (108.0) (104.1) (108.0) (92.1) (5.0) (12.7) (101.6) (38.1) (2.7)
& Write-On
Note: For type FS raceway, no mounting 4x5 4.25 5.10 4.25 4.63 .20 .50 5.00 1.50 .12 Markers
holes is the standard condition; if mounting (101.6) x (127.0) (108.0) (129.5) (108.0) (117.5) (5.0) (12.7) (127.0) (38.1) (2.9)
holes are required, delete NM from the 6x4 6.25 4.15 6.25 3.63 .20 .50 4.00 2.50 .11
part number. (152.4) x (101.6) (158.8) (105.4) (158.8) (92.1) (5.0) (12.7) (101.6) (63.5) (2.8) E4.
Permanent
> Available for type FS raceway only.
Identification
See page C1.48 for wiring duct color and size availability.
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com C1.37
E L E C T R I C A L S O LU T I O N S
A.
System
Overview Panduct ® Type MC Wiring Duct Dimensions
Dimensions are shown for reference only. Contact Panduit Customer Service at 800-777-3300 for specific dimensional needs.
C4. (1.97) x (2.95) (1.95) (2.85) (1.95) (2.27) (.20) (.49) (2.78) (.08)
Cable 50 x 100 49.5 97.8 49.6 81.0 5.0 12.5 95.5 2.2
Management (1.97) x (3.94) (1.95) (3.85) (1.95) (3.19) (.20) (.49) (3.76) (.09)
62.5 x 62.5 62.0 59.7 62.1 45.8 5.0 12.5 58.0 1.8
Mounting Hole Dimensions (2.46) x (2.46) (2.44) (2.35) (2.44) (1.80) (.20) (.49) (2.28) (.07)
D1. For 25mm, 37.5mm, and 50mm width duct. 75 x 50 74.7 48.0 74.6 34.8 5.0 12.5 45.5 2.0
Terminals
(2.95) x (1.97) (2.94) (1.89) (2.94) (1.37) (.20) (.49) (1.79) (.08)
2000 mm
[78.74]
75 x 62.5 74.7 59.7 74.6 45.8 5.0 12.5 58.0 2.0
D2. (2.95) x (2.46) (2.94) (2.35) (2.94) (1.80) (.20) (.49) (2.28) (.08)
Power 14 mm 75 x 75 74.7 73.2 74.6 57.6 5.0 12.5 70.5 2.2
Connectors [0.55]
(2.95) x (2.95) (2.94) (2.88) (2.94) (2.27) (.20) (.49) (2.78) (.09)
75 x 100 74.7 97.8 74.6 81.0 5.0 12.5 95.5 2.3
8 mm
D3. [0.32] (2.95) x (3.94) (2.94) (3.85) (2.94) (3.19) (.20) (.49) (3.76) (.09)
Grounding 1950 mm 100 x 50 99.6 48.0 99.6 34.8 5.0 12.5 45.5 2.0
Connectors [76.77]
(3.94) x (1.97) (3.92) (1.89) (3.92) (1.37) (.20) (.49) (1.79) (.08)
For 75mm and 100mm width duct. 100 x 75 99.6 73.2 99.6 57.6 5.0 12.5 70.5 2.5
E1. (3.94) x (2.95) (3.92) (2.88) (3.92) (2.27) (.20) (.49) (2.78) (.10)
Labeling 2000 mm
100 x 100 99.6 97.8 99.6 81.0 5.0 12.5 99.5 2.5
Systems [78.74]
(3.94) x (3.94) (3.92) (3.85) (3.92) (3.19) (.20) (.49) (3.76) (.10)
50 mm
[1.97]
E2. 6.5 mm
25 mm
12.5 mm
Labels [.98]
[.26] [.49]
E3.
Pre-Printed
& Write-On 4.5 mm 25 mm
Markers [.18] 1950 mm [.98]
[76.77]
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
8 mm D2.
[0.32] Power
1950 mm Connectors
[76.77]
50 mm
[1.97]
E1.
25 mm Labeling
6.5 mm [.98] 12.5 mm Systems
[.26] [.49]
E2.
Labels
4.5 mm 25 mm
[.18] 1950 mm [.98]
[76.77]
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com C1.39
E L E C T R I C A L S O LU T I O N S
A.
System
Overview Panduct ® Type NE Wiring Duct Dimensions
Dimensions are shown for reference only. Contact Panduit Customer Service at 800-777-3300 for specific dimensional needs.
Duct Size Dimensions – Inches (mm)
B1.
Cable Ties (W x H) A B C D E F H K T
.5 x .5 .63 .56 .69 .38 .37 .80 .50 .05
For .5" high duct.
(12.7) x (12.7) (16.0) (14.2) (17.5) (9.7) (9.4) (20.3) (12.7) (1.3)
B2. F C .5 x 1 .63 1.06 .69 .75 .31 .80 1.00 .06
Cable (12.7) x (25.4) (16.0) (26.9) (17.5) (19.1) (7.9) (20.3) (25.4) (1.5)
Accessories
1x1 1.14 1.06 1.25 .75 .31 .80 1.00 .06
D H B T
(25.4) x (25.4) (29.0) (26.9) (31.8) (19.1) (7.9) (20.3) (25.4) (1.5)
B3. 1 x 1.5 1.14 1.62 1.25 1.20 .31 .80 1.50 .07
Stainless E A (25.4) x (38.1) (29.0) (41.1) (31.8) (30.5) (7.9) (20.3) (38.1) (1.8)
Steel Ties
ON CENTERLINE
1x2 1.14 2.06 1.25 1.63 .31 .80 2.00 .07
(25.4) x (50.8) (29.0) (52.3) (31.8) (41.4) (7.9) (20.3) (50.8) (1.8)
C1. 1x3 1.14 3.06 1.25 2.63 .31 1.00 3.00 .07
Wiring For 1", 1.5", 2", 3",
(25.4) x (76.2) (29.0) (77.7) (31.8) (66.8) (7.9) (25.4) (76.2) (1.8)
Duct 4" and 5" high duct.
1x4 1.14 4.06 1.25 3.63 .31 1.00 4.00 .08
F C (25.4) x (101.6) (29.0) (103.1) (31.8) (92.2) (7.9) (25.4) (101.6) (2.0)
C2. 1.5 x 1.5 1.64 1.62 1.75 1.20 .31 .80 1.50 .07
Surface D (38.1) x (38.1) (41.7) (41.1) (44.5) (30.5) (7.9) (20.3) (38.1) (1.8)
Raceway H B T
1.5 x 2 1.64 2.06 1.75 1.63 .31 .80 2.00 .07
(38.1) x (50.8) (41.7) (52.3) (44.5) (41.4) (7.9) (20.3) (50.8) (1.8)
E A
C3. 1.5 x 3 1.64 3.06 1.75 2.63 .31 1.00 3.00 .07
Abrasion (38.1) x (76.2) (41.7) (77.7) (44.5) (66.8) (7.9) (25.4) (76.2) (1.8)
Protection
1.5 x 4 1.64 4.06 1.75 3.63 .31 1.00 4.00 .08
(38.1) x (101.6) (41.7) (103.1) (44.5) (92.2) (7.9) (25.4) (101.6) (2.0)
C4. 2x1 2.14 1.06 2.25 .75 .31 .80 1.00 .50 .06
Cable Mounting Hole Dimensions
For .5", .75", 1" and 1.5" wide duct. (50.8) x (25.4) (54.4) (26.9) (57.2) (19.1) (7.9) (20.3) (25.4) (12.7) (1.5)
Management
2x2 2.14 2.06 2.25 1.63 .31 .80 2.00 .50 .07
.50 TYP (50.8) x (50.8) (54.4) (52.3) (57.2) (41.4) (7.9) (20.3) (50.8) (12.7) (1.8)
[12.7]
D1. .195 TYP
2x3 2.14 3.06 2.25 2.63 .31 1.00 3.00 .50 .07
Terminals [5.0] (50.8) x (76.2) (54.4) (77.7) (57.2) (66.8) (7.9) (25.4) (76.2) (12.7) (1.8)
2x4 2.14 4.06 2.25 3.63 .31 1.00 4.00 .50 .08
C
L (50.8) x (101.6) (54.4) (103.1) (57.2) (92.2) (7.9) (25.4) (101.6) (12.7) (2.0)
D2. 3x1 3.14 1.06 3.25 .75 .31 .80 1.00 1.00 .06
Power 4.0 [101.6] TYP 2.0 (76.2) x (25.4) (79.8) (26.9) (82.6) (19.1) (7.9) (20.3) (25.4) (25.4) (1.5)
Connectors [50.8]
3x2 3.14 2.06 3.25 1.63 .31 .80 2.00 1.00 .07
(76.2) x (50.8) (79.8) (52.3) (82.6) (41.4) (7.9) (20.3) (50.8) (25.4) (1.7)
D3. For 2.0", 2.5", 3" and 4" wide duct. 3x3 3.14 3.06 3.25 2.63 .31 1.00 3.00 1.00 .07
Grounding (76.2) x (76.2) (79.8) (77.7) (82.6) (66.8) (7.9) (25.4) (76.2) (25.4) (1.8)
Connectors
3x4 3.14 4.06 3.25 3.63 .31 1.00 4.00 1.00 .08
K (76.2) x (101.6) (79.8) (103.1) (82.6) (92.2) (7.9) (25.4) (101.6) (25.4) (2.0)
C
L
E1. K 3x5 3.14 5.06 3.25 4.63 .38 1.33 5.00 1.00 .09
Labeling
(76.2) x (127.0) (79.8) (128.5) (82.6) (117.6) (9.7) (33.8) (127.0) (25.4) (2.3)
Systems
4x2 4.14 2.06 4.25 1.63 .31 .80 2.00 1.50 .07
4.0 [101.6] TYP 2.0
[50.8] (101.6) x (50.8) (105.2) (52.3) (108.0) (41.4) (7.9) (20.3) (50.8) (38.1) (1.8)
E2. 4x3 4.14 3.06 4.25 2.63 .31 1.00 3.00 1.50 .07
Labels (101.6) x (76.2) (105.2) (77.7) (108.0) (66.8) (7.9) (25.4) (76.2) (38.1) (1.8)
4x4 4.14 4.06 4.25 3.63 .31 1.00 4.00 1.50 .08
(101.6) x (101.6) (105.2) (103.1) (108.0) (92.2) (7.9) (25.4) (101.6) (38.1) (2.0)
E3.
Pre-Printed 4x5 4.14 5.06 4.25 4.63 .38 1.33 5.00 1.50 .09
& Write-On (101.6) x (127.0) (105.2) (128.5) (108.0) (117.6) (9.7) (33.8) (127.0) (38.1) (2.3)
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
On CL
(38.1) x (50.8) (44.5) (50.3) (47.8) (41.4) (7.9) (20.3) (48.8) (2.0)
1.5 x 3 1.75 3.06 1.88 2.63 .31 1.00 3.00 .10 B2.
(38.1) x (76.2) (44.5) (77.7) (47.8) (66.8) (7.9) (25.4) (76.2) (2.5) Cable
Accessories
2x2 2.17 1.98 2.29 1.57 .31 .80 1.92 .50 .08
B (50.8) x (50.8) (55.1) (50.3) (58.2) (39.9) (7.9) (20.3) (48.8) (12.7) (2.0)
T 2x3 2.17 3.06 2.29 2.63 .31 1.00 3.00 .50 .10 B3.
(50.8) x (76.2) (55.1) (77.7) (58.2) (66.8) (7.9) (25.4) (76.2) (12.7) (2.5) Stainless
2x4 2.17 4.1 2.29 3.63 .31 1.00 4.00 .50 .10 Steel Ties
(50.8) x (101.6) (55.1) (104.1) (111.3) (92.2) (7.9) (25.4) (101.6) (12.7) (2.7)
A
3x3 3.25 3.06 3.38 2.63 .31 1.00 3.00 1.00 .10
C1.
(76.2) x (76.2) (82.6) (77.7) (85.9) (66.8) (7.9) (25.4) (76.2) (25.4) (2.5) Wiring
3x4 3.25 4.1 3.38 3.63 .31 1.00 4.00 1.00 .11 Duct
F
(76.2) x (101.6) (82.6) (104.1) (85.9) (92.2) (7.9) (25.4) (101.6) (25.4) (2.8)
4x4 4.25 4.1 4.38 3.63 .31 1.00 4.00 1.50 .11
C2.
(101.6) x (101.6) (108.0) (104.1) (111.3) (92.2) (7.9) (25.4) (101.6) (38.1) (2.8) Surface
Raceway
D
H
For 2", 3", and 4" wide duct.
C3.
Abrasion
K
Protection
C
L
E K
C4.
E F
For 2" duct height: .31" [7.9] .80" [20.3] Cable
3" to 4" duct height: .31" [7.9] 1.00" [25.4] 4.0 [101.6] TYP 2.0 Management
[50.8]
D1.
Terminals
Panduct Type HN Wiring Duct Dimensions
®
Dimensions are shown for reference only. Contact Panduit Customer Service at 800-777-3300 for specific dimensional needs.
D2.
Duct Size Dimensions – Inches (mm) Power
(W x H) A B C D E F H K T Connectors
100°
1.5 x 2 1.75 1.98 1.88 1.63 .20 .50 1.92 .08
On CL
(38.1) x (50.8) (44.5) (50.3) (47.8) (41.4) (5.0) (12.7) (48.8) (2.0)
D3.
C 1.5 x 3 1.75 3.06 1.88 2.63 .20 .50 3.00 .10 Grounding
(38.1) x (76.2) (44.5) (77.7) (47.8) (66.8) (5.0) (12.7) (76.2) (2.5) Connectors
2x2 2.17 1.98 2.29 1.57 .20 .50 1.92 .50 .08
(50.8) x (50.8) (55.1) (50.3) (58.2) (39.9) (5.0) (12.7) (48.8) (12.7) (2.0)
2x3 2.17 3.06 2.29 2.63 .20 .50 3.00 .50 .10 E1.
B
Labeling
(50.8) x (76.2) (55.1) (77.7) (58.2) (66.8) (5.0) (12.7) (76.2) (12.7) (2.5) Systems
2x4 2.17 4.1 4.38 3.63 .20 .50 4.00 .50 .10
T
(50.8) x (101.6) (55.1) (104.1) (111.3) (92.2) (5.0) (12.7) (101.6) (12.7) (2.7)
3x3 3.25 3.06 3.38 2.63 .20 .50 3.00 1.00 .10 E2.
(76.2) x (76.2) (82.6) (77.7) (85.9) (66.8) (5.0) (12.7) (76.2) (25.4) (2.5) Labels
A
3x4 3.25 4.1 3.38 3.63 .20 .50 4.00 1.00 .11
(76.2) x (101.6) (82.6) (104.1) (85.9) (92.2) (5.0) (12.7) (101.6) (25.4) (2.8)
4x4 4.25 4.1 4.38 3.63 .20 .50 4.00 1.50 .11
E3.
E
Pre-Printed
(101.6) x (101.6) (108.0) (104.1) (111.3) (92.2) (5.0) (12.7) (101.6) (38.1) (2.8) & Write-On
Markers
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.41
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
E L E C T R I C A L S O LU T I O N S
A.
System
Overview Panduct ® Type FL Wiring Duct Dimensions
Dimensions are shown for reference only.
Dimensions are in mm (in.). Contact Panduit Customer Service at 800-777-3300 for specific dimensional needs.
B1.
Mounting Hole Dimensions
Cable Ties
For FL12X12LG-A
Nominal Duct Size Dimensions –
25.0 TYP
(W x H) mm (In.)
[.98]
B2. 5.0 TYP mm A B
Cable [.20] 8.0 TYP
Accessories [.31] 12 x 12 12.4 12.4
12.5
[.49] (.49) x (.49) (.49) (.49)
A C 25 x 25 24.9 24.9
L
B3.
(.98) x (.98) (.98) (.98)
Stainless
Steel Ties 4.0 TYP
6.2 TYP [.16] 50 x 50 50 50
[.25] (1.97) x (1.97) (1.97) (1.97)
For FL25X25LG-A and FL50X50LG-A
C1. Note: Type FL wiring duct has factory applied
Wiring 12.5 TYP
[.49] adhesive. For 50 x 50 two strips of tape are used;
Duct A otherwise, only one strip is centered on the part.
12.5
[.49]
C2.
Surface B C
L
Raceway
E3.
Panduct ® Type H, HN, and HS Wiring Duct – Wirefill Capacity
Pre-Printed Electrical Communication
& Write-On 8 10 12 14 16 18 22 23 23/24 24 Fiber
Markers AWG AWG AWG AWG AWG AWG AWG AWG AWG AWG Cable
Nominal Duct
Size Nominal .216 .164 .130 .141 .152 .111 .124 .133 .096 .111 .118 .084 .100 .106 .085 .330 .250 .190 .118
E4. (W x H) Area Cat. Cat. Cat.
Permanent In. In.² THHN THHN THHN MTW MTW THHN MTW MTW TFFN MTW MTW TFFN MTW MTW MTW 6A 6 5e 3.0 mm
Identification 1.50 x 2.00 3.000 34 60 95 81 70 131 105 91 175 131 116 229 162 144 224 14 25 44 116
1.50 x 3.00 4.500 52 90 143 122 105 197 158 137 263 197 174 344 243 216 336 22 38 67 174
E5.
Lockout/ 2.00 x 2.00 4.000 46 80 127 108 93 175 140 122 234 175 155 306 216 192 299 19 34 59 154
Tagout 2.00 x 3.00 6.000 69 120 191 163 140 263 210 183 351 263 232 459 324 288 448 29 51 89 232
& Safety 2.00 x 4.00 8.000 92 160 255 217 187 350 281 244 469 350 310 612 432 384 598 39 69 119 309
Solutions 3.00 x 3.00 9.000 104 180 287 244 210 394 316 275 527 394 349 689 486 432 673 44 77 134 348
3.00 x 4.00 12.000 139 241 383 326 280 526 421 366 703 526 465 919 648 577 897 59 103 179 464
F. 4.00 x 4.00 16.000 185 321 511 435 374 701 562 488 938 701 621 1225 864 769 1197 79 138 239 619
Index Table shows maximum wirefill based on 50% of duct internal cross sectional area. Formula = nominal area/1.85 x D2. See page C1.48 for wiring duct color
and size availability. AWG dimensions represent typical outer cable diameter in inches.
C1.42 Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
E L E C T R I C A L S O LU T I O N S
A.
System
Panduct Type D, G, F and FS Wiring Duct – Wirefill Capacity
®
Overview
Electrical Communication
8 10 12 14 16 18 22 23 23/24 24 Fiber B1.
AWG AWG AWG AWG AWG AWG AWG AWG AWG AWG Cable Cable Ties
Nominal Duct
Size Nominal .216 .164 .13 .141 .152 .111 .124 .133 .096 .111 .118 .084 .100 .106 .085 .330 .25 .190 .118
(W x H) Area Cat. Cat. Cat. 3.0
In. In.² THHN THHN THHN MTW MTW THHN MTW MTW TFFN MTW MTW TFFN MTW MTW MTW 6A 6 5e mm B2.
Cable
0.50 x 0.50 0.250 3 5 8 7 6 11 9 8 15 11 10 20 14 12 19 1 2 3 10 Accessories
0.50 x 1.00 0.500 6 10 16 14 12 23 18 16 31 23 20 40 28 25 39 2 4 7 20
0.50 x 2.00 1.000 12 21 33 28 24 46 37 32 62 46 41 80 57 50 79 5 9 15 40
B3.
0.75 x 0.75 0.563 6 11 19 16 13 26 20 18 34 26 23 45 32 28 44 2 5 8 23
Stainless
0.75 x 1.00 0.750 9 15 25 21 18 34 27 24 46 34 30 60 42 38 59 3 6 11 30 Steel Ties
0.75 x 1.50 1.125 13 23 38 32 27 52 41 36 69 52 46 91 64 57 88 5 10 17 46
0.75 x 2.00 1.500 18 31 50 43 37 69 55 48 93 69 61 121 85 76 118 7 13 23 61
C1.
1.00 x 1.00 1.000 12 21 33 28 24 46 37 32 62 46 41 80 57 50 79 5 9 15 40 Wiring
1.00 x 1.50 1.500 18 31 50 43 37 69 55 48 93 69 61 121 85 76 118 7 13 23 61 Duct
1.00 x 2.00 2.000 24 42 67 57 49 92 74 64 124 92 82 161 114 101 158 10 18 31 81
1.00 x 3.00 3.000 36 63 101 86 74 139 111 96 186 139 123 242 171 152 237 15 27 47 122 C2.
1.00 x 4.00 4.000 48 84 135 114 98 185 148 129 248 185 164 323 228 203 316 20 36 63 163 Surface
1.50 x 1.00 1.500 18 31 50 43 37 69 55 48 93 69 61 121 85 76 118 7 13 23 61 Raceway
1.50 x 1.50 2.250 27 47 76 64 55 104 83 72 139 104 92 182 128 114 177 11 20 35 92
1.50 x 2.00 3.000 36 63 101 86 74 139 111 96 186 139 123 242 171 152 237 15 27 47 122 C3.
1.50 x 3.00 4.500 55 95 152 129 111 208 167 145 279 208 184 364 257 228 355 23 41 71 184 Abrasion
Protection
1.50 x 4.00 6.000 73 127 202 172 148 278 222 193 372 278 246 485 342 305 474 31 54 94 245
2.00 x 1.00 2.000 24 42 67 57 49 92 74 64 124 92 82 161 114 101 158 10 18 31 81
2.00 x 1.50 3.000 36 63 101 86 74 139 111 96 186 139 123 242 171 152 237 15 27 47 122 C4.
Cable
2.00 x 2.00 4.000 48 84 135 114 98 185 148 129 248 185 164 323 228 203 316 20 36 63 163 Management
2.00 x 3.00 6.000 73 127 202 172 148 278 222 193 372 278 246 485 342 305 474 31 54 94 245
2.00 x 4.00 8.000 97 169 270 229 197 371 297 258 496 371 328 647 457 406 632 41 73 126 327
2.00 x 5.00 10.000 122 212 338 287 247 463 371 323 620 463 410 809 571 508 790 52 91 158 409 D1.
2.50 x 3.00 7.500 91 159 253 215 185 347 278 242 465 347 307 607 428 381 593 39 68 118 307 Terminals
3.00 x 1.00 3.000 36 63 101 86 74 139 111 96 186 139 123 242 171 152 237 15 27 47 122
3.00 x 2.00 6.000 73 127 202 172 148 278 222 193 372 278 246 485 342 305 474 31 54 94 245
D2.
3.00 x 3.00 9.000 110 191 304 258 222 417 334 290 558 417 369 728 514 457 711 47 82 142 368 Power
3.00 x 4.00 12.000 146 254 405 344 296 556 445 387 744 556 492 971 685 610 949 62 109 189 491 Connectors
3.00 x 5.00 15.000 183 318 507 431 370 695 557 484 930 695 615 1214 857 762 1186 78 137 237 614
4.00 x 1.50 6.000 73 127 202 172 148 278 222 193 372 278 246 485 342 305 474 31 54 94 245 D3.
4.00 x 2.00 8.000 97 169 270 229 197 371 297 258 496 371 328 647 457 406 632 41 73 126 327 Grounding
4.00 x 3.00 12.000 146 254 405 344 296 556 445 387 744 556 492 971 685 610 949 62 109 189 491 Connectors
4.00 x 4.00 16.000 195 339 540 459 395 742 594 516 992 742 656 1295 914 813 1265 83 146 253 655
4.00 x 5.00 20.000 244 424 676 574 494 927 743 646 1240 927 820 1619 1142 1017 1581 104 182 316 819 E1.
6.00 x 4.00 24.000 293 509 811 689 593 1113 891 775 1488 1113 984 1943 1371 1220 1898 125 219 379 983 Labeling
Systems
Table shows maximum wirefill based on 50% of duct internal cross sectional area. Formula = nominal area/1.75 x D2. See page C1.48 for wiring duct color
and size availability. Not all sizes available for each duct type.
AWG dimensions represent typical outer cable diameter in inches.
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.43
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
E L E C T R I C A L S O LU T I O N S
A.
System
Overview Panduct ® Type MC and NNC Wiring Duct – Wirefill Capacity
Electrical Communication
B1. 8 10 12 14 16 18 22 23 23/24 24 Fiber
Cable Ties AWG AWG AWG AWG AWG AWG AWG AWG AWG AWG Cable
Nominal Duct
Size Nominal 5.5 4.2 3.3 3.6 3.9 2.8 3.1 3.4 2.4 2.8 3 2.1 2.5 2.7 2.2 8.4 6.4 4.8 3
(W x H) Area Cat. Cat. Cat. 3.0
B2. mm mm² THHN THHN THHN MTW MTW THHN MTW MTW TFFN MTW MTW TFFN MTW MTW MTW 6A 6 5e mm
Cable 25 x 25 625 11 20 32 27 23 44 36 31 60 44 39 78 55 49 76 5 8 15 39
Accessories
25 x 37 925 17 30 48 41 35 66 53 46 88 66 58 116 81 72 113 7 13 22 58
25 x 50 1250 23 41 65 55 47 89 72 62 120 89 79 156 110 98 153 10 17 30 79
B3. 25 x 62 1550 29 51 81 69 59 111 89 77 148 111 98 194 137 122 190 12 21 38 98
Stainless
Steel Ties 25 x 75 1875 35 61 98 83 71 134 108 93 180 134 119 235 166 147 229 15 26 46 119
37 x 37 1369 25 45 71 60 52 98 78 68 131 98 87 171 121 107 167 11 19 33 86
37 x 50 1850 35 60 96 82 70 132 106 92 177 132 117 232 163 145 226 15 26 45 117
C1.
Wiring 37 x 62 2294 43 75 120 102 87 164 132 114 220 164 145 287 203 180 281 18 32 56 145
Duct 37 x 75 2775 52 91 145 123 106 199 159 138 266 199 176 348 245 218 340 22 39 68 176
50 x 50 2500 47 82 131 111 95 179 144 125 240 179 159 313 221 197 306 20 35 61 158
50 x 75 3750 71 123 196 167 143 269 216 187 360 269 238 470 332 295 459 30 53 92 238
C2.
Surface 50 x 100 5000 94 164 262 222 191 359 288 250 480 359 318 627 442 394 612 40 70 122 317
Raceway 62 x 62 3844 72 126 201 171 147 276 221 192 369 276 244 482 340 303 471 31 54 94 244
75 x 50 3750 71 123 196 167 143 269 216 187 360 269 238 470 332 295 459 30 53 92 238
C3. 75 x 62 4650 88 153 243 207 178 334 267 232 446 334 295 583 411 366 570 37 65 114 295
Abrasion 75 x 75 5625 106 185 294 250 215 404 324 281 540 404 357 706 498 443 689 45 79 138 357
Protection
75 x 100 7500 142 246 393 334 287 539 432 375 720 539 477 941 664 591 919 60 106 184 476
100 x 50 5000 94 164 262 222 191 359 288 250 480 359 318 627 442 394 612 40 70 122 317
C4. 100 x 75 7500 142 246 393 334 287 539 432 375 720 539 477 941 664 591 919 60 106 184 476
Cable 100 x 100 10000 189 329 524 445 383 718 576 500 961 718 636 1255 885 788 1225 81 141 245 634
Management
Table shows maximum wirefill based on 50% of duct internal cross sectional area. Formula = nominal area/1.75 x D2. See page C1.48 for wiring duct color
and size availability. Not all sizes available for each duct type.
AWG dimensions represent typical outer cable diameter in millimeters.
D1.
Terminals
D2.
Power
Connectors
D3.
Grounding
Connectors
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
C1.44
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
E L E C T R I C A L S O LU T I O N S
A.
System
Panduct Type NE Wiring Duct – Wirefill Capacity
®
Overview
Electrical Communication
8 10 12 14 16 18 22 23 23/24 24 Fiber B1.
AWG AWG AWG AWG AWG AWG AWG AWG AWG AWG Cable Cable Ties
Nominal Duct
Size Nominal .216 .164 .130 .141 .152 .111 .124 .133 .096 .111 .118 .084 .100 .106 .085 .330 .25 .190 .118
(W x H) Area Cat. Cat. Cat. 3.0
In. In.² THHN THHN THHN MTW MTW THHN MTW MTW TFFN MTW MTW TFFN MTW MTW MTW 6A 6 5e mm B2.
Cable
0.50 x 0.50 0.250 2 4 7 6 5 10 8 7 13 10 8 17 12 11 17 1 2 3 8
Accessories
0.50 x 1.00 0.500 5 9 14 12 10 20 16 14 27 20 17 35 25 22 34 2 4 6 17
1.00 x 1.00 1.000 10 18 29 25 21 40 32 28 54 40 35 70 50 44 69 4 8 13 35
1.00 x 1.50 1.500 16 27 44 37 32 60 48 42 81 60 53 106 75 66 103 6 12 20 53 B3.
Stainless
1.00 x 2.00 2.000 21 37 59 50 43 81 65 56 108 81 71 141 100 88 138 9 16 27 71 Steel Ties
1.00 x 3.00 3.000 32 55 88 75 64 121 97 84 162 121 107 212 150 133 207 13 24 41 107
1.00 x 4.00 4.000 42 74 118 100 86 162 130 113 217 162 143 283 200 177 276 18 32 55 143
C1.
1.50 x 1.50 2.250 24 41 66 56 48 91 73 63 122 91 80 159 112 100 155 10 18 31 80 Wiring
1.50 x 2.00 3.000 32 55 88 75 64 121 97 84 162 121 107 212 150 133 207 13 24 41 107 Duct
1.50 x 3.00 4.500 48 83 133 113 97 182 146 127 244 182 161 318 225 200 311 20 36 62 161
1.50 x 4.00 6.000 64 111 177 150 129 243 195 169 325 243 215 425 300 266 415 27 48 83 215
C2.
2.00 x 1.00 2.000 21 37 59 50 43 81 65 56 108 81 71 141 100 88 138 9 16 27 71 Surface
2.00 x 2.00 4.000 42 74 118 100 86 162 130 113 217 162 143 283 200 177 276 18 32 55 143 Raceway
2.00 x 3.00 6.000 64 111 177 150 129 243 195 169 325 243 215 425 300 266 415 27 48 83 215
2.00 x 4.00 8.000 85 148 236 201 173 324 260 226 434 324 287 566 400 355 553 36 64 110 286 C3.
3.00 x 1.00 3.000 32 55 88 75 64 121 97 84 162 121 107 212 150 133 205 13 24 41 107 Abrasion
Protection
3.00 x 2.00 6.000 64 111 177 150 129 243 195 169 325 243 215 425 300 266 415 27 48 83 215
3.00 x 3.00 9.000 96 167 266 226 194 365 292 254 488 365 323 637 450 400 622 41 72 124 322
3.00 x 4.00 12.000 128 223 355 301 259 486 390 339 651 486 430 850 600 533 830 55 96 166 430 C4.
Cable
3.00 x 5.00 15.000 160 278 443 377 324 608 487 423 813 608 538 1062 750 667 1038 68 120 207 537
Management
4.00 x 2.00 8.000 85 148 236 201 173 324 260 226 434 324 287 566 400 355 553 36 64 110 286
4.00 x 3.00 12.000 128 223 355 301 259 486 390 339 651 486 430 850 600 533 830 55 96 166 430
4.00 x 4.00 16.000 171 297 473 402 346 649 520 452 868 649 574 1133 800 711 1107 73 128 221 573 D1.
4.00 x 5.00 20.000 214 371 591 502 432 811 650 565 1085 811 718 1417 1000 889 1384 91 160 277 716 Terminals
Table shows maximum wirefill based on 50% of duct internal cross sectional area. Formula = nominal area/2.00 x D2.
AWG dimensions represent typical outer cable diameter in inches.
D2.
Power
Connectors
Table shows maximum wirefill based on 50% of duct internal cross sectional area. Formula = nominal area/2.50 x D2.
AWG dimensions represent typical outer cable diameter in millimeters. E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.45
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
E L E C T R I C A L S O LU T I O N S
A.
System
Overview Wirefill Formula
B2.
Cable
Accessories
B3.
Stainless Why use a 50% Wirefill?
Steel Ties As specified in NFPA79-2007 section 13.5.2, Percentage Fills of Raceways (Ducts), a 50% wirefill is given as
the maximum wirefill capacity in all Panduit Wiring Ducts. This helps ensure general safe wiring practices
C1. are followed. In actual practice, a 50% wirefill is the maximum amount of wiring the duct can hold given the
Wiring
Duct
additional airspace created between cables by non-uniform cable shapes, cable interlacing, and cable
packing factors.
C2.
Surface What is the Usable Duct Area?
Raceway
The usable area we define as the calculation of internal area that can be occupied by wires or cables.
E2.
Labels
Formula Derivation
E3. Inserting the elements from above into the Simplifying this formula results in the formula
Pre-Printed used for wirefill calculation (Note 2):
& Write-On general formula results in the following:
Markers
E4.
Permanent
Identification
E5.
Lockout/ Note: When calculating wirefill capacity using the above formula, variables W, H, and D must be expressed in
Tagout same units (i.e. mm or inches).
& Safety
Solutions 1 This calculation does not account for additional airspace created between cables by non-uniform cable shapes, cable interlacing, and cable packing factors.
2 The resulting formula is used for all Panduit flush cover ducts, this excludes type NE duct which has a different profile design that results in a
F. divisor of 2.0 x D 2 (rather than 1.75 x D 2 as shown here) and type H and HS wiring duct with a profile design that results in a divisor of 1.85 x D 2 and
Index corner wiring duct which uses calculated internal area and a divisor of 2.0 x D 2.
C1.46
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
E L E C T R I C A L S O LU T I O N S
A.
System
Panduct Wiring Duct and Raceway – Material Specifications
®
Overview
B1.
Cable Ties
Halogen-Free
Lead-Free Modified PPO Polypropylene
Properties Units Test Method PVC (NNC, NE) (FL) B2.
General Cable
Accessories
Specific gravity g/cc ASTM D 792 1.45 1.09 0.95
Heat deflection temperature @264 psi °F ASTM D 648 156 215 117
B3.
Thermal expansion 10-5 in/in/°F ASTM D 696 3.7 3.8 N/A Stainless
Thermal conductivity (BTU-in/hr-ft²)°F ASTM C 177 1.3 1.3 N/A Steel Ties
Burning Characteristics
Flammability class — UL 94 V-0 V-0 V-2 C1.
Wiring
Smoke density @ 4 minutes — ASTM E 662 538 513 N/A Duct
Limited oxygen index (LOI) — ASTM D 2863 35 30 25
Peak heat release rate kW/m2 ASTM E 1354 N/A N/A N/A
C2.
Hardness Surface
Raceway
Durometer hardness "D" ASTM D 2240 78 N/A N/A
Rockwell hardness "R" ASTM D 785 111 116 N/A
Tensile C3.
Abrasion
Yield Strength psi ASTM D 638 6,200 7,700 3,770 Protection
Modulus psi ASTM D 638 390,000 350,000 172,000
Flexural C4.
Yield Strength psi ASTM D 790 8,700 11,500 4,350 Cable
Management
Modulus psi ASTM D 790 325,000 340,000 181,250
Impact strength
Notched Izod (.125") D1.
Terminals
23°C (73°F) ft-lb/in 4.0 5.0 1.8
ASTM D 256
0°C (32°F) ft-lb/in 1.6 2.0 N/A
Electrical Properties D2.
Power
Power factor: Connectors
60 Hz @30°C (86°F) — 2.90 N/A N/A
ASTM D 150
1 MHz @30°C (86°F) — 4.00 N/A N/A
D3.
Dielectric constant: Grounding
60 Hz @30°C (86°F) — 3.90 N/A N/A Connectors
ASTM D 150
1 MHz @30°C (86°F) — 3.30 N/A N/A
Dielectric strength: E1.
Unconditioned volts/mil 690 N/A N/A Labeling
ASTM D 149 Systems
Conditioned volts/mil 700 N/A N/A
Note: To the best of our knowledge the above information is accurate.
Panduit assumes no liability for the accuracy or completeness of this information. E2.
Labels
E3.
Rigid Polyvinyl Chloride Halogen-Free Polypropylene Pre-Printed
& Write-On
(PVC) (Modified Polyphenylene Oxide) A flexible material with a UL 94 Markers
A general purpose material for use A special purpose flammability rating of V-2 and UL
in indoor applications. PVC has a material for use in halogen-free Recognized for continuous use
temperatures up to 149°F (65°C). E4.
UL 94 flammability rating of V-0 or high temperature applications. Permanent
and is UL Recognized for continuous Modified PPO has a UL 94 flammability Identification
use temperatures up to 122°F (50°C). rating of V-0 and is UL Recognized for
PVC is an economical wiring continuous use temperatures up to 203°F E5.
duct material. (95°C), and is 20% lighter than PVC. Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.47
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
E L E C T R I C A L S O LU T I O N S
A.
System
Overview Panduct ® Wiring Duct and Raceway – Color and Size Selection
B1.
Cable Ties
Duct Size
IB IG
WxH
LG WH BL Intrs. Intl.
In. mm Light Gray White Black Blue* Gry.
B2.
Cable .5 x .5 12 x 12 G F FS FL G F FS NE
Accessories .5 x 1 G F FS G F NE
.5 x 2 G G
.75 x .75 G F FS G F
B3. .75 x 1 G G
Stainless
Steel Ties .75 x 1.5 G F G F
.75 x 2 G G G
1x1 25 x 25 G F FS NNC FL G F FS NE NNC MC G FS G F MC
C1. 1 x 1.5 25 x 37 G F FS NNC G F NE NNC MC G G F MC
Wiring 1x2 25 x 50 G F FS D NNC G F NE NNC MC G D G F MC
Duct
1 x 2.5 25 x 62 MC MC
1x3 25 x 75 G F FS D NNC G F D NE NNC MC G D G F MC
C2. 1x4 25 x 100 G F FS D G F D NE G D G F
Surface 1.5 x 1 G F FS G F FS
Raceway 1.5 x 1.5 37 x 37 G F FS NNC G F FS NE NNC MC G FS G F MC
1.5 x 2 37 x 50 G F FS D H HN HS NNC G F NE H HN HS NNC MC G D H HS G F MC
C3. 1.5 x 2.5 37 x 62 MC MC
Abrasion 1.5 x 3 37 x 75 G F FS D H HN HS NNC G F D NE H HN HS NNC MC G D H HS G F MC
Protection 1.5 x 4 G F D G F D NE G D G F
2x1 G F FS G F FS NE G
2 x 1.5 G F FS G F FS
C4.
Cable 2x2 50 x 50 G F FS D H HN HS NNC FL G F FS D NE H HN HS NNC MC G FS D H HS G F MC
Management 2x3 50 x 75 G F FS D H HN HS NNC G F FS D NE H HN HS NNC MC G D H HS G F MC
2x4 50 x 100 G F FS D H HN HS NNC G F D NE H HN HS NNC MC G D H HS G F MC
2x5 G F G F
D1. 2.5 x 2.5 62 x 62 MC MC
Terminals 2.5 x 3 G F D G F G
3x1 G F FS G F FS NE
3x2 75 x 50 G F FS D G F FS NE MC G FS MC
D2. 3 x 2.5 75 x 62 MC MC
Power
3x3 75 x 75 G F FS D H HN HS NNC G F FS D NE H HN HS NNC MC G FS D H HS G F MC
Connectors
3x4 75 x 100 G F FS D H HN HS G F FS D NE H HN HS MC G D H HS G F MC
3x5 G F FS G F FS NE
D3. 4 x 1.5 G FS G
Grounding 4x2 100 x 50 G F FS D NNC G F FS NE NNC MC G D MC
Connectors
4x3 100 x 75 G F FS D NNC G F FS NE NNC MC G G F MC
4x4 100 x G F FS D H HN HS NNC G F FS D NE H HN HS NNC MC G FS D H HS G F MC
100
E1.
Labeling 4x5 G F FS G F NE G
Systems 6x4 G F FS G F FS
4.40 x 111.8 x CWD CWD
3.57* 90.7
E2. 5.33 x 135.3 x CWD CWD
Labels 4.58* 115.7
6.25 x 156.7 x DRD DRD
2.12** 54.0
E3. 7.25 x 184.1 x DRD DRD
Pre-Printed 3.12** 79.4
& Write-On 8.25 x 209.5 x DRD DRD
Markers 4.12** 104.8
*Corner Duct Profile
E4. **DIN Rail Duct Profile
Permanent
Identification
*Intrinsic Blue Color – IB
E5.
Lockout/ Intrinsic blue wiring duct is made from the same lead-free PVC material as our standard PVC duct. Intrinsic blue is an internationally
Tagout recognized standard blue color that identifies the wiring duct as “incapable of releasing sufficient electrical or thermal energy under normal
& Safety or abnormal conditions to cause ignition of a specific hazardous atmospheric mixture in its most easily ignited concentrations.”
Solutions
*ISA-RD12.6 (Instrument Society of America)
F.
Index
C1.48
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
E L E C T R I C A L S O LU T I O N S
A.
System
Installation Tips: Overview
4. Apply the desired topcoat of latex paint and allow to dry. C1.
Wiring
Duct
5. Install the wiring duct/raceway and covers.
• Amines
• Ethers D2.
Power
• Organic, inorganic and oxidizing acids Connectors
• Petrol
D3.
Note: Panduit assumes no liability for the accuracy or completeness of this list. Grounding
Connectors
E1.
Part Number System for Panduct ® Wiring Duct Labeling
Systems
G .5 X .5 LG 6 -A
E2.
Labels
Type Nominal Width Nominal Height Color Length -A = Adhesive Backed
= Without Adhesive
G = Wide Slot In. or mm In. or mm LG = Light Ft. or m (leave blank) E3.
Flush Design Gray Pre-Printed
NM = No Mounting Holes & Write-On
F = Narrow Slot WH = White Markers
Flush Design BL = Black
FL = Flexible Duct IB = Intrinsic Blue
E4.
FS = Solid Wall Flush Design IG = International Permanent
H = Wide Slot Hinged Design Gray Identification
HN = Narrow Slot Hinged Design
HS = Solid Wall Hinged Design E5.
D = Round Hole Flush Design Lockout/
Tagout
NNC = Halogen-Free Design & Safety
NE = Halogen-Free Wide Slot Design Solutions
MC = Metric Narrow Slot Design
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.49
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
E L E C T R I C A L S O LU T I O N S
A.
System
Overview Part Number System for Panduct ® PanelMax™ DIN Rail Wiring Duct
DRD 22 LG 6
B1.
Cable Ties
Type Size Color Length
C1. Part Number System for Panduct ® PanelMax™ Corner Wiring Duct
Wiring
Duct
CWD 3 LG 6
C2.
Surface Type
Raceway
Capability Height Color Length
C4.
Cable
Management
D1.
Terminals
D2.
Power
Connectors
D3.
Grounding
Connectors
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
C1.50
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
E L E C T R I C A L S O LU T I O N S
A.
System
Panduit Wiring Duct Approvals and Compliances Overview
B1.
Cable Ties
Logo
(Symbol) Agency Complies with: Requirement Applicable Products B2.
Cable
UL 1565 Accessories
Underwriters Wiring duct types:
File No. E147128 CSA C22.2 No.18.5-02
Laboratories, Inc. H, HS, HN, and DRD
“Positioning Devices.”
B3.
Stainless
Underwriters Steel Ties
File No. E147128 UL 1565 All types of wiring duct
Laboratories, Inc.
C1.
Canadian Standards CSA C22.2 No.18.5-02 All types of wiring duct Wiring
File No. 016446 Duct
Association “Positioning Devices.” (except DRD, H, HN, HS)
Logo D1.
(Symbol) Agency Complies with: Requirement Applicable Products Terminals
This European standard specifies
dimensions for slotted trunkings that will
be used in electrical switchgear D2.
assemblies and that conform to the Power
DIN (Deutsches corresponding requirements in DIN VDE Connectors
Institut fur Normung), 060 Part 506. The dimensions specified Wiring duct types:
DIN 43 659
German Institute with the standard include: MC and NNC
for Standardization • The channel mounting hole pattern, D3.
Grounding
slot dimensions, pitch, and location Connectors
• The distance from the first to last
like size mounting hole
• Minimum overall product length E1.
Labeling
“Non-metallic ducts shall be permitted Systems
(inside enclosures) only when they are Wiring duct types:
NFPA 79-2007,
made with a flame retardant material.” H, G, F, D, MC, NNC,
section 13.3.1
Flame-retardant material is defined in the CWD, HN, and NE
standard by the IEC 60332-1 test method. E2.
Labels
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com C1.51
E L E C T R I C A L S O LU T I O N S
A.
System
Overview Panduit Wiring Duct Approvals and Compliances (continued)
B1.
Cable Ties
Logo
(Symbol) Agency Complies with: Requirement Applicable Products
B2.
Cable UL 508, An insulating barrier material shall comply
PVC divider wall
Accessories section 15 with the properties indicated in Table 15.1.
Underwriters
Laboratories, Inc.
B3. UL 508, Shall comply with minimum thickness
SD*EMI metal barrier
Stainless sections 34, 181 as required in section 6.3.
Steel Ties
D1.
Terminals
D2.
Power
Connectors
D3.
Grounding
Connectors
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
C1.
Wiring
Duct
• Two system sizes available: 2x2 and 4x4
• Minimum 2 inch (50.8mm) bend radius fittings C2.
Surface
protect against signal loss due to excessive Raceway
cable bends
C3.
• Snap-on non-slip covers Abrasion
Protection
• Compatible with Panduit® FiberRunner® 12x4, 6x4,
4x4 and 2x2 Routing Systems C4.
Cable
Management
D1.
Terminals
The 2x2 and 4x4 Fiber-Duct ™ Routing Systems are comprised of channel, fittings, and brackets designed D2.
Power
to segregate, route, and protect fiber optic and copper cabling to and between racks within the Connectors
telecommunications room.
D3.
Grounding
Connectors
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.53
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview 2x2 and 4x4 Fiber-Duct ™ Routing Systems Roadmap
B1.
Cable Ties
B2.
Cable
Accessories 7
B3.
Stainless
Steel Ties
6
5 11
C1.
Wiring 10
Duct 8
C2. 4 12
Surface
Raceway
3
9
C3.
Abrasion
Protection
C4.
14
Cable
Management
D1.
Terminals
2
13
D2.
Power
1
Connectors
E1.
Labeling
Systems
E2.
Labels FTRBE12 – FTRBN12 – FUSB – Underfloor F2PCLB12 – Two-Piece Ladder Rack
Existing Threaded Rod Bracket New Threaded Pedestal Bracket Bracket for Attaching Threaded Rod to
E3. (page C1.60) Rod Bracket (page C1.60) (page C1.60) 1 1/2" – 2" Ladder Rack (page C1.61)
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout FLRB – Ladder FLB – “L” Wall FZBA1.5X4 – Adjustable FZBLP – Low Profile
& Safety Rack Bracket Mount Bracket “Z” Bracket “Z” Bracket
Solutions
(page C1.60) (page C1.60) (page C1.60) (page C1.60)
F.
Index
C1.54
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview
B1.
Cable Ties
B2.
Cable
Accessories
1 FCF2X2** and FCF4X4** – Coupler Fitting (see page C1.56)
B3.
Stainless
2 FEC2X2** and FEC4X4** – End Cap Fitting (see page C1.57) Steel Ties
C1.
Wiring
Duct
3 FFWC2X2** and FFWC4X4** – 4-Way Cross Fitting (see page C1.57)
C2.
Surface
4 FIVRA2X2** and FIVRA4X4** – Inside Vertical Right Angle (see page C1.57) Raceway
C3.
Abrasion
5 FOVRA2X2** and FOVRA4X4** – Outside Vertical Right Angle (see page C1.57) Protection
C4.
Cable
6 FIV452X2** and FIV454X4** – Inside Vertical 45° Angle (see page C1.57) Management
D1.
Terminals
7 FOV452X2** and FOV454X4** – Outside Vertical 45° Angle (see page C1.57)
D2.
Power
8 FT2X2** and FT4X4** – Horizontal Tee Fitting (see page C1.57) Connectors
D3.
Grounding
9 FVT4X4** – 4x4 Vertical Tee (see page C1.58) Connectors
E1.
Labeling
10 FRA2X2** – FRA4X4** – Right Angle Fitting (see page C1.56) Systems
E2.
FRF42** – 4x4 to 2x2 Fiber-Duct ™ Reducer Fitting (see page C1.57) Labels
11
E3.
Pre-Printed
12 ™
S2X2**6NM and S4X4**6NM Fiber-Duct Channel (see page C1.56) & Write-On
Markers
E4.
Permanent
13 ™
E2X2**6 and E4X4**6 Fiber-Duct Slotted Channel (see page C1.56) Identification
E5.
Lockout/
Tagout
14 TRC2BL and TRC4BL – Bend Radius Control Trumpet (see page C1.59) & Safety
Solutions
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.55
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview 2x2 and 4x4 Fiber-Duct ™ Routing Systems
B1. • Channel, covers, fittings and other non-metallic system • Compatible with Panduit® FiberRunner ® 2x2, 4x4,
Cable Ties components made from V-0 flame class rated material 6x4 and 12x4 Routing Systems
• Snap-on non-slip covers
B2. Std. Std.
Cable System Pkg. Ctn.
Accessories Part Number Part Description Size Qty. Qty.
Fiber-Duct ™
Channel
B3. S2X2YL6NM Used to carry the cables throughout the 2x2 6 120
Stainless Fiber-Duct ™ Routing System. Accepts cover C2YL6.
Steel Ties S2X2 Cover sold separately.
S4X4
S4X4YL6NM Used to carry the cables throughout the 4x4 6 60
C1. Fiber-Duct ™ Routing System. Accepts cover C4YL6.
Wiring Cover sold separately.
Duct
Fiber-Duct ™ Slotted Channel
E2X2YL6 Used to carry the cables vertically to the front or 2x2 6 120
C2.
Surface the back of equipment racks throughout the system.
Raceway Accepts cover C2YL6. Extra supports required
when used in horizontal applications.
Cover sold separately.
C3.
Abrasion E4X4YL6 Used to carry the cables vertically to the front or 4x4 6 60
E2X2 the back of equipment racks throughout the system.
Protection
E4X4 Accepts cover C4YL6. Extra supports required
when used in horizontal applications.
C4. Cover sold separately.
Cable
Management Fiber-Duct ™ Cover
C2YL6 Cover for Fiber-Duct ™ Channel and Fiber-Duct ™ 2x2 6 120
Slotted Channel. Non-slip cover design incorporates
D1. integral high friction lining to inhibit cover movement.
Terminals
C4YL6 Cover for Fiber-Duct ™ Channel and Fiber-Duct ™ 4x4 6 120
Slotted Channel. Non-slip cover design incorporates
integral high friction lining to inhibit cover movement.
D2. C2
Power C4
Connectors Note: Available with mounting holes. To order, delete NM from the part number.
For fastest installation use NR2WH-L or NR4BL-L snap rivets.
For other colors replace YL (Yellow) with OR (Orange) or BL (Black).
D3.
Order number of feet required, in multiples of standard 6' length increments.
Grounding
Connectors
E1.
Labeling Fiber-Duct ™ System Fittings
Systems
Std. Std.
System Pkg. Ctn.
E2.
Part Number Part Description Size Qty. Qty.
Labels
FCF2X2 Coupler Fitting
E3. FCF4X4 FCF2X2YL Used to join two sections of duct together. 2x2 1 5
Pre-Printed Fiber-Duct ™ Coupler is not required at each
& Write-On FCF4X4YL fitting connection. 4x4 1 5
Markers
Horizontal Right Angle Fitting
E4. FRA2X2YL Attaches to channel to create a 90° horizontal turn 2x2 1 5
Permanent FRA2X2
FRA4X4YL from a straight horizontal run. Cover included. 4x4 1 5
Identification FRA4X4
For other colors replace suffix YL (Yellow) with OR (Orange) or BL (Black).
E5. Fittings include 5/16" assembly holes for fast mechanical fastening.
Lockout/
Tagout
& Safety
Solutions
F.
Index
C1.56 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in BOLD.
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Fiber-Duct ™ System Fittings (continued) Overview
B1.
Std. Std. Cable Ties
System Pkg. Ctn.
Part Number Part Description Size Qty. Qty.
B2.
Horizontal Tee Fitting Cable
FT2X2
FT2X2YL Attaches to channel to create a 90° horizontal 2x2 1 5 Accessories
FT4X4
branch from a straight horizontal run.
FT4X4YL Cover included. 4x4 1 5
B3.
Four Way Cross Fitting Stainless
Steel Ties
FFWC2X2YL Attaches to channel to create a horizontal four 2x2 1 5
way cross intersection. Cover included.
FFWC2X2 FFWC4X4YL 4x4 1 5
C1.
FFWC4X4 Wiring
End Cap Fitting Duct
FEC2X2YL Used for closing off open ends of the channel. 2x2 1 5
No coupler required. Push-on installation.
C2.
FEC2X2 FEC4X4YL 4x4 1 5 Surface
FEC4X4 Raceway
Inside Vertical 45° Angle Fitting
FIV452X2YL Attaches to channel to create a 45° upward angle 2x2 1 5
from a straight horizontal run. Used with outside C3.
vertical 45° angle fitting FOV452X2YL or Abrasion
FIV454X4YL 4x4 1 5 Protection
FOV454X4YL to change level of straight
horizontal runs. Cover included.
FIV452X2 C4.
FIV454X4 Outside Vertical 45° Angle Fitting Cable
FOV452X2YL Attaches to channel to create a 45° downward 2x2 1 5 Management
angle from a straight horizontal run. Used with
inside vertical 45° angle fitting FIV452X2YL or
FOV454X4YL FIV454X4YL to change level of straight 4x4 1 5 D1.
horizontal runs. Cover included. Terminals
FOV452X2
FOV454X4 Inside Vertical Right Angle Fitting
FIVRA2X2YL Attaches to channel to create a 90° upward angle 2x2 1 5 D2.
from a straight horizontal run. Used with outside Power
vertical 90° angle fitting FOVRA2X2YL or Connectors
FIVRA4X4YL FOVRA4X4YL to change level of straight 4x4 1 5
horizontal runs. Cover included.
D3.
Grounding
FIVRA2X2 Outside Vertical Right Angle Fitting Connectors
FIVRA4X4 FOVRA2X2YL Attaches to channel to create a 90° downward 2x2 1 5
angle from a straight horizontal run. Used with
inside vertical 90° angle fitting FIVRA2X2YL or E1.
FOVRA4X4YL FIVRA4X4YL to change level of straight 4x4 1 5 Labeling
horizontal runs. Cover included. Systems
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com C1.57
ELECTRICAL SOLUTIONS
A.
System
Overview Fiber-Duct ™ Spillouts
B1.
Cable Ties Std. Std.
System Pkg. Ctn.
Part Number Part Description Size Qty. Qty.
B2. 2x2 Vertical Tee
Cable
Accessories FVTHD2X2YL Attaches to 2x2 channel to create a 90° vertical drop 2x2 1 5
from a horizontal run. Hinged door included. Accepts
channel cover in conjunction with channel. Use
B3. QuikLock ™ Coupler FBC2X2YL with HS2X2YL6 or
Stainless H2X2YL6 channels. Use snap rivets NR2WH-L or
Steel Ties bolts F14PN-L with S2X2YL6 or E2X2YL6 channels.
FVTHD2X2 Also accepts FIDT2X2YL.
C1.
Wiring 3-Sided BRC Trumpet Spillout for 2x2 Exit
Duct FTR2X2YL Used to limit the bend radius of the cable to 2" 2x2 1 5
(50.8mm) when exiting from a spill-over junction with
a 2x2 exit or from 2x2 Fiber-Duct ™ Channel.
C2.
Surface
Raceway FTR2X2
1-Port Spillout to 1.5" (38mm) Inside Diameter Corrugated Tubing
C3. FIDT2X2YL Used to route cable into one piece of 1.5" (38mm) 2x2 1 5
Abrasion diameter split corrugated tubing. Used with a spill-over
Protection junction with a 2x2 exit, 2x2 Fiber-Duct ™ Fittings, and
the 2x2 FiberRunner ® Hinged Channel. Securely holds
split corrugated tubing to ensure system integrity and
C4. easy access to add or remove cables.
Cable
Management FIDT2X2
E2. FIDT4X4BL
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
C1.58 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in BOLD.
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Fiber-Duct ™ Bend Radius Control Trumpets Overview
• Provide method to transition cabling into rack system •Maintain 1 inch (25.4mm) bend radius control
B1.
Cable Ties
Std. Std.
Pkg. Ctn.
Part Number Part Description System Size Qty. Qty.
B2.
TRC2BL Bend radius control trumpet for exiting at the 2x2 1 10 Cable
sidewall of 2" wall heights of type G, FS, E, or S Accessories
Fiber-Duct ™ Channels.
TRC2BL
TRC4BL Bend radius control trumpet for exiting at the 4x4 1 10 B3.
sidewall of 4" wall heights of type G, FS, E, or S Stainless
Steel Ties
Fiber-Duct ™ Channels.
C1.
TRC4BL Wiring
Duct
C2.
Surface
Raceway
C3.
Abrasion
Fiber-Duct ™ Accessories Protection
Std. Std.
System Pkg. Ctn. C4.
Part Number Part Description Size Qty. Qty. Cable
Snap Rivets Management
NR2WH-L Snap rivet fastens channel and fittings together for 2x2 50 500
NR2WH - L added strength and rigidity. Snap rivet mounts flush
NR4BL-L to surfaces. 4x4 50 500 D1.
NR4BL - L Terminals
Plastic Bolts and Nuts
F14PWN-L 1/4" plastic bolts and wing nuts fastens channel and 2x2 50 500
fittings together for added strength and rigidity. 4x4 D2.
Power
Plastic Bolts and Nuts Connectors
F14PN-L 1/4" plastic bolts and hex nuts fastens channel and 2x2 50 500
F14PWN-L F14PN - L fittings together for added strength and rigidity. 4x4
D3.
Grounding
Connectors
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.59
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview Fiber-Duct ™ Mounting Brackets
B1.
Cable Ties For Std. Std.
Threaded Pkg. Ctn.
Part Number Part Description Rod Size Qty. Qty.
B2. Existing Threaded Rod Bracket for Fiber-Duct ™ System
Cable FTRBE12 Used for supporting the 2x2 and 4x4 Fiber-Duct ™ 1/2" 1 10
Accessories FTRBE12, FTRBE58 Systems from existing threaded rod installations.
FTRBE12M FTRBE58 Bracket is secured to threaded rod with two split nuts. 5/8" 1 10
Contains hardware for attaching to threaded rods
B3. FTRBE12M and hardware for mounting channel to bracket. 12mm 1 10
Stainless
Steel Ties
New Threaded Rod Bracket for Fiber-Duct ™
System
FTRBN12 Used for supporting the 2x2 and 4x4 Fiber-Duct ™ 1/2" 1 10
C1. Systems from new threaded rod installations. Bracket
Wiring FTRBN12, FTRBN58 FTRBN58 is secured to threaded rod with two nuts. Contains 5/8" 1 10
Duct FTRBN12M hardware for attaching to threaded rods and hardware
FTRBN12M for mounting channel to bracket. 12mm 1 10
E2.
Labels FZBLP
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
C1.60 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in BOLD.
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Fiber-Duct ™ Mounting Brackets (continued) Overview
B1.
For Std. Std. Cable Ties
Threaded Pkg. Ctn.
Part Number Part Description Rod Size Qty. Qty.
Two-Piece Ladder Rack Bracket for Attaching Threaded Rod to 1 1/2" – 2" B2.
Ladder Rack Cable
F2PCLB12 Two-piece bracket attaches to 3/8" (9.5mm) wide x 1/2" 1 10 Accessories
1 1/2" (38.1mm) or 3/8" (9.5mm) wide x 2" (50.8mm)
ladder rack rail. Bracket halves slide into position and
clamp together on the ladder rack rail, which allows B3.
Stainless
F2PCLB58 for a one-handed assembly of the threaded rod 5/8" 1 10 Steel Ties
(not included). Contains bracket and hardware
F2PCLB12
for attaching bracket to ladder rack.
F2PCLB58
C1.
Two-Piece Framing Clip for Attaching 5/8" Threaded Rod to 2" x 9/16" C-Channel Wiring
Auxiliary Framing Bars Duct
FRAFC58 Two-piece framing clip attaches to auxiliary framing 5/8" 1 10
bars. Framing clip halves slide into position and C2.
interlock on the auxiliary framing bars, allowing Surface
easier assembly of the threaded rod to bars. Raceway
Contains two-piece framing clip and hardware
for attaching framing clip to auxiliary framing bars.
FRAFC58 (5/8” threaded rod not included.) C3.
Abrasion
Protection
C4.
Cable
Management
D1.
Terminals
D2.
Power
Connectors
D3.
Grounding
Connectors
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.61
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview 2x2 and 4x4 Fiber-Duct ™
Routing Systems
B1. Cable Fills for 2x2 and 4x4 Fiber-Duct ™ Cable Routing Systems
Cable Ties
The maximum amounts may vary according to the cable fill installation methods,
straightness of cables, etc.
B2.
Cable 2x2 Fiber-Duct ™ Cable Routing System
Accessories
Fiber Optic
Flat Ribbon Category 6A Cat. 6
B3. Diameter Diameter Diameter Interconnect Cable Diameter Diameter
Stainless Internal 1.6mm 2.0mm 3.0mm 5.20mm 7.57mm 6.35mm
Steel Ties Fill/Pile Up Area In.2 .063" .079" .118" .205" .298" .250"
2.25"
(57.1mm) 40% Fill
W
C1. 2" Pile Up 3.5 449 288 128 42 20 29
Wiring 2.10" 50% Fill
Duct A = 3.5 in.
2
H
(53.3mm) 2" Pile Up 3.5 562 359 160 53 25 36
(2258mm2)
60% Fill
2" Pile Up 3.5 674 431 192 64 30 43
C2.
Surface Channel cutting instructions: For optimum results, use a miter box and saw. For larger quantities use a plastic cutting saw
Raceway blade for clean, burr-free cuts. Recommend: Carbide 80T and 100T; .090" thickness, .125" kerf.
C3.
Abrasion
Protection
C4.
Cable
Management
4x4 Fiber-Duct ™ Cable Routing System
D2.
40% Fill
4.10"
A = 14.6 in.2 2" Pile Up 7.6 976 624 277 92 44 62
Power (9419mm2)
(104.1mm)
Connectors 3" Pile Up 11.3 1450 928 413 137 65 92
4" Pile Up 14.6 1874 1199 533 177 84 119
50% Fill
D3.
2" Pile Up 7.6 1219 780 347 115 54 77
Grounding
Connectors 3" Pile Up 11.3 1813 1160 516 171 81 115
4" Pile Up 14.6 2343 1499 666 221 105 149
60% Fill
E1. 2" Pile Up 7.6 1463 936 416 138 65 93
Labeling
3" Pile Up 11.3 2176 1392 619 205 97 138
Systems
4" Pile Up 14.6 2811 1799 800 265 126 178
Channel cutting instructions: For optimum results, use a miter box and saw. For larger quantities use a plastic cutting saw
E2. blade for clean, burr-free cuts. Recommend: Carbide 80T and 100T; .090" thickness, .125" kerf.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
C1.62 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in BOLD.
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com
ELECTRICAL SOLUTIONS
A.
System
Overview
NOTES B1.
Cable Ties
B2.
Cable
Accessories
B3.
Stainless
Steel Ties
C1.
Wiring
Duct
C2.
Surface
Raceway
C3.
Abrasion
Protection
C4.
Cable
Management
D1.
Terminals
D2.
Power
Connectors
D3.
Grounding
Connectors
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
E4.
Permanent
Identification
E5.
Lockout/
Tagout
& Safety
Solutions
F.
Index
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) C1.63
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com