1.1 KV SINGLE CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I)
1cX 500 36 500 430 700 610 530 900 47.00 71.50
1cX 630 40 555 485 809 680 590 1020 59.22 90.09
1.1 KV SINGLE CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I)
1cX 500 41 500 430 700 610 530 900 47.00 71.50
1cX 630 46 555 485 809 680 590 1020 59.22 90.09
3cX 120 35 225 185 258 285 240 330 11.28 17.16
3cX 150 39 255 210 294 315 270 375 14.10 21.45
3cX 185 43 285 235 339 355 300 435 17.39 26.46
3cX 240 49 325 270 402 410 350 510 22.56 34.32
3cX 300 53 370 305 461 460 390 590 28.20 42.90
3cX 400 59 435 350 542 520 440 670 37.60 57.20
3cX 500 66 481 405 624 580 480 750 47.00 71.50
3cX 630 73 537 470 723 680 575 875 59.22 90.09
1.1 KV Three CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I)
3cX 150 43 255 210 294 315 270 375 14.10 21.45
3cX 185 48 285 235 339 355 300 435 17.39 26.46
3cX 240 53 325 270 402 410 350 510 22.56 34.32
3cX 300 58 370 305 460 460 390 590 28.20 42.90
3cX 400 65 435 350 542 520 440 670 37.60 57.20
3cX 500 72 481 405 624 580 480 750 47.00 71.50
3cX 630 81 537 470 723 680 575 875 59.22 90.09
1.1 KV Three & Half CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)
4cX 120 41 225 185 258 285 240 330 11.28 17.16
4cX 150 45 255 210 294 315 270 375 14.10 21.45
4cX 185 50 285 235 339 355 300 435 17.39 26.46
4cX 240 56 325 270 402 410 350 510 22.56 34.32
4cX 300 63 370 305 461 460 390 590 28.20 42.90
4cX 400 70 435 350 542 520 440 670 37.60 57.20
4cX 500 79 481 405 624 580 480 750 47.00 71.50
4cX 630 88 537 470 723 680 575 875 59.22 90.09
1.1 KV Four CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I)
Cross- ARMOURED CABLE
sectional
area (Sq
Overall Normal Current Rating in Amps Short Circuit Current
MM)
Diameter Rating for
(mm) 1Sec.duration in K.
Amps
4cX 120 44 225 185 258 285 240 330 11.28 17.16
4cX 150 49 255 210 294 315 270 375 14.10 21.45
4cX 185 54 285 235 339 355 300 435 17.39 26.46
4cX 240 65 325 270 402 410 350 510 22.56 34.32
4cX 300 68 370 305 460 460 390 590 28.20 42.90
4cX 400 76 435 350 542 520 440 670 37.60 57.20
4cX 500 86 481 405 624 580 480 750 47.00 71.50
4cX 630 94 537 470 723 680 575 875 59.22 90.09
Rate this:
44 Votes
Share this:
! Facebook " Email # LinkedIn $ More
Like
One blogger likes this.
Related
EHV XLPE – Current Rating PCV Cable-Current Rating Electrical Useful Equations
April 26, 2011 April 24, 2011 July 27, 2013
With 11 comments With 19 comments With 70 comments
« Previous Next »
Leave a Reply
Your email address will not be published. Required fields are marked *
Comment
Name
*
Email
*
Website
Post Comment
This site uses Akismet to reduce spam. Learn how your comment data is processed.
Reply
Reply
Hai good morning, You have done a good job. it’s very useful to me. Thank you
Dear sir, I Prakash Parmar from Suyog Electricals Ltd, 1 query about XLPE cable current
rating base on on which IS standard & its calculation please provide information
Dear sir
please send cable chart – 596.8kw mens how much sq mm required AL /CU
regards
Harish
9850985429
plz send the details for cable sizing for primary and secondary side of 250 KVA transformer
Jignesh Ji can you please tell me how to calculate the power loss in single core cable.
regards
sandeep saini
sir i need list of motor hp fuse amps kw cable size gland size please i Will request you send me my
mail sir.
Reply
Thank you for this cable selection chart. Thank u verymuch. Do u have any information about
conductor,s DC current carrying capacity .Please help me sir, Thank u.
Reply
dear sir,
ratinng cable size of 300kva to 450kva trasformer.
Reply
Reply
Dear Sir
Will you please furnish me short time ratings of HT XLPE insulated cables e. g. 10% for XXX Hrs., 20%
for XXX Hrs. and so on ?
Reply
Can a 10 guage XPLE insulated copper wire used as leads for oil immersed CTs withstand around 90
deg C continously in transformer oil? What is the compatability of XPLE wire with transformer oil? What
is the specific density of XLPE insulation?
Reply
Can we get the standard from which the XLPE current values are derived / referred.
Reply
can you tell me the voltage drop calcultaion of 11KV XLPE cable around 600m long
Reply
Use Excel Base Program to Calculate LT-MV-HT Cable from “Electrical Tool” Page of This Blog
DOWNLOAD:
Reply
I heard that above 630A we should use ACB ,but MCCB’s are available till 1600A.
So can you tell me from which rating we have to go for ACB and VCB
Thanking you,
Paulson
i am engaged in arecanut leaf plate manufacturing activity which need heaters with die of
8000 watts.what specification of power cable can i put.
Dear Sir,
i what to learn the HT cable sizing. how to calculate it . Can you help me. If you have any
excel Sheet kindly shear with me.
Dear Sir,
Really very happy…Your Calculation your explanation are very nice and useful for us.
Reply
Dear Jignesh, I am nirav shah from hyderabad. i would like to know what is the difference
between current carrying capacity for xlpe insulated single core copper flexible cables for
AC and Dc applications. Benchmark being single core 240sqmm which can carry upto
550amps in AC application.
Dear Sir,
Details furnished by you are excellent.Sir, i need to buy the unlock version .Did you published any books
on cable sizing,busbar calculation, breaker designing etc?My maid id is udai_kiran1983@yahoo.com
Reply
Reply
sir, i read to this cable size and current rating chart it is very use full for us so i request u please send this
chart in my Email
RAMKEWAL
Reply
Reply
can you please provid me for the current rating for 1C X 185 SQ MM copper cables
Reply
Reply
sorry i want the current carrying capacity in DC power( 750 V, and 440 V )
Thank you.
hi sir will you please tell me the calculation formula fo these & also i want to know the cable
size for 11kv tranfomer to the panel
Dear
Regards Manoj Patil On Sep 20, 2015 5:21 PM, “Electrical Notes & Articles” wrote:
> Manojkumar commented: “hi sir will you please tell me the calculation > formula fo these
& also i want to know the cable size for 11kv tranfomer to > the panel”
11kv/433v TFP-1000 kva/500kva/750kva the fl currents on LT side are 1333.3/1000/666.6 amps. what is
size of 4 core xlpe alluminium is used pl tell me.
Reply
Jignesh.Parmar on April 1, 2012 at 12:33 pm
Download Excel base Sheet to decide Cable Size from “EXCEL TOOL” page.
To decide Cable Size We need two important Data
(1) Load
(2)Distance.
Reply
this chart about cables is nice but give us some information about OH cables, and underground cables .
Reply
Reply
Very useful….
Reply
Dear Jignesh,
Your cable selection table is very helpful. But i’ve a question to clarify? how do we determine the cable
current capacity of cables running in parallel? for example if my breaker is rated at 1000A, what size of
cable conductor should be terminating at the terminals per phase, can i terminate 2 x 1c x 400 per
phase or how do we decide the conductor sizing? as i understand there is a derating factor of cables
when connected in parallel? may be you can ellaborate further and may be send me details on the cable
sizing formulation and other useful data on my email : manjarwalla@gmail.com
Reply
Use Equation
% Voltage Drop:=(1.732 X (Full Load Current)X(RCosØ+j SinØ)XLengthX100) / Line Voltage X No of
Run X 1000.
Here No of Run cable is Either 1,2 or more in parallel.
You can also use “Cable Design” sheet of the Excel Tool Page of this Blog
Reply
Dear Jignesh,
Thank you for your prompt reply. I’ve also gone through your cable design excel
sheet,wonderful program. On the cable design program how do you determine the starting
and running cos and sin thetha? do you have any thumb rule for calculating the cable runs
in a faster way? for example if my full load current is 1000A as incomer or any feeder load
connected to my panel. As from the program i’ve to input the the respective KW to attain
nearest full load current before i can get the runs of cables?
Dear Sir,
Plz.tel me this XLPE cables can we use 100% loading? for How much length cables are de rated?
Thanks.
Reply
this Rating is as per Standard Cable Catalog and IS. Cable Rating never indicate derating factor.
Because Derating Factor depends upon Your Application.
It is depend upon Type of Laying Cable –
=In Air,Land, at 0.500mt depth at 1 meter depth,
=Air-Land Temperature,
=in bundle,=In separate,Distance between two Cable, etc.
If Cable Rating is 100 Amp It may be 80 Amp or 90 Amp or 100 Amp depend upon Laying of cable.
Reply
Reply
Already available on this Blog . Please Refer Post of “PVC Flexible Wire Rating”
I have already Put Cable/Wire Rating Starting from 430V to 66KV (Earthed/Unearthed Cable)
Reply
lal bahadur chand on December 19, 2012 at 7:35 pm
Reply
Reply
sir,if i have 7.5kw unit then how can i select cable for that unit with out using chart.give me that formula
for me.
Reply
Use Cable Size Program of this Blog. (Formula is given in the Program)
Reply
well done sir you have a great job and sacrifices for Electrical Engineering.
Reply
Hi,
I really appreciate your effort to share consolidated information..
Reply
dear
sir/madem
pleas send me cebel formula for given voltag and
also send me cabel and amp tebal
Reply
Jignesh.Parmar on May 4, 2013 at 2:40 pm
Download Cable selection Program from this Blog..here You can find Formulas and Table also…
Reply
Reply
what is the thumb rule for above calcualtions..? please share the formula for approximate current ratings
in 1.1 kv XLPE cables .
Reply
Mr. Jignesh, can you please tell me what size of cable is required for solar installation. My panel rating is
Isc=8.5 A, Voc=36.5 V. I’m using two series panels in 3 arrays, basically an 2×3 system. Thanks. Length
one way will be 30 feet from panels to inverter.
Reply
Reply
Reply
hiii sir, thanx for this information but sir pls tell me the formula or any thumb rule for calculating of
cable/wire size as per given load…..
Reply
Thank you for this cable selection chart. Do u have any information about conductor,s DC current
carrying capacity .Please mail me sir, Thank u.
Reply
sir
can u tell me the formula how to calculate the cable sizes corresponding amps..
Reply
Reply
Dear sir,
what is the function of cable fillers ? please reply.
Reply
sir ,
difference between round shape cable and delta shape cable please me understand
Reply
Reply
electrical infrastructure construction Q&A for exp houseing scheme what are requrment of
houesing scheme of all utlates and what are gape electrical serviese between water
,sewg,gas and other serviese in under ground
Reply
Reply
I want to know that whats the current carrying capacity for 4 runs of 3.5 core 400 Sq.mm Al.
armoured XLPE cable in ground . How it can be calculate. ( please send a copy of tables if
any )
which means if 3.5 core 400sq.mm cable carries 370 amps in ground and when it is 2 runs it
will not be double of 370. it will less than double. how it will calculate ???
KIRAN PATEL
dear sir what is service factor in motor and which kind machine in use same motor
Reply
Hai …
Reply
Dear Sir,
My doubt might sound silly to you, but I just wanted to clarify it. From the given cable ampacity ratings in
the tables above, how can we calculate the maximum power rating for the respective multi-core cables.
Thank you.
Reply
Reply
For example: for a 4 core 120 sqmm Aluminium conductor cable, what is the maximum
power capacity? Should we multiply the given ampacity with single phase voltage or 3
phase voltage to find out maximum load it can handle?
Dear Jignesh,
pl suggest me regarding cable rating across laying ground 700 running feet for 750A load bearing at
resisdence building there jurk load AC. Pl give cable size.
Regards,
Suresh Chaudhary
Reply
there is no any power rating of cable.only current rating of cable are mentioned.power rating is
concerned to the equipment.
Reply
Dear Jignesh,
Sir what’s the formula to select the cables sizes for the particular current ratings?
Reply
Refer “Cable Size” Excel base program from “Electrical Tools” Page
Reply
Reply
dear jignesh how to calculate the busbar size in 630amps breaker 3ph ?
Reply
Dear Sir
Reply
Dear Sir,
Can you explain that the current rating you have mentioned in Ground ,Air, or duct is quite opposite to
what manufacture state in their product catalogue.
regards
Reply
how many runs of 3.5C 240 sq.mm al. conductor xlpe pvc insulted cables to be laid to supply to a circuit
which is maximum current draw is 800 A.
Reply
Distance !!!! Use Excel Cable Size Calculation sheet of this Blog..
Reply
Reply
Sir,
please let me know the current carrying capacity of 3C*2.5 sqmm copper cable in air.
Reply
sir,
if i want to select power cable for 2o hp motor. and i am going to use 3 core alluminium cable.
then what will be the cable size?
Reply
sir
3.5core 50 sqmm ki cabel par fes kitana amp legislative
Reply
manoj singh on April 15, 2014 at 7:58 am
sir,
if i want to select 50sq cable for 11kv. and i am going to use 3 core cable.
then what will be the cable size?
Reply
your table is very useful, thank you and I need the cable size of 22 kw, 3ph, 380volt for my deep
well pump motor at a deep distance of 300 metrrs
Thank you & best regards,
Fetsum
Reply
Reply
Hi
Can I know how many runs of single core 630 mm are required for a 1000 KVA transformer ?
Reply
Dear Sir;
I would like to say thank you so much for the access you made open to get the size of power cables.
Teshome, from Ethiopia
Reply
Reply
Reply
hi…. i have find question about how to find current of 132kv,1200mm^2 cross sec area,in flat formation
with 400 mm disc presnt btween them,,is there any formuala ,so guide me plzzzzz,thnkxxxx
Reply
Hi — Here 40 kw load 3 ph 415 v and length is 1 km so kindly suggest me which size of aluminum
cable to be laid in ground
Reply
Hello, what 33 KV cable size should I select for a 2000 KW Load on LT side. Transformer is 2.5 MVA,
33/0.433 KV.
Reply
Reply
You are such a wonderful Engineer, for the great opportunity you have given to people
Reply
Reply
Dear Sir,
will you please suggest me from which website i can download Excel Base Program to Calculate LT-MV-
HT Cable from Electrical tools.
Reply
Sir Thanks For your Valuble Information,I want know the Formula for To Measure Current For Any cable
Ex:1x16sq.mm,3x4sqmm,3×16 sqmm
Reply
Sir Thanks For your Valuble Information,I want know the Formula for To Measure Current For Any cable
Ex:1x16sq.mm,3x4sqmm,3×16 sqmm
Reply
CAN YOU TELL ME WHEN WE TAKE A 51MM COOPER CABLE THEN THIS COOPER CABLE HOW
MUCH TAKE A LOAD IN HP
Reply
please can you tell me if total load is 140 Amp and length is 250 Meter. how much XLPE cable size and
how much voltage drop. how i can calculate.
Reply
please advice which minimum width of 3 core xlpe cable should used for 7 KM long transmission with
connected load of 3000
Reply
Sir
How much load can be layed on 1 kv line. Please give kv and load relation.
Reply
Sir
what’s the advantage of using 4 core cable over 3.5 core cable ? And then, what chang
Powar pf 1
Reply
sir,
Detail of Transformer primary & secondary testing please said me
Reply
Hello Sir.
Can a 4C 150mm armoured cable sustain 595A or a total power of 398Kva? If not, what cable size
would be ideal? I seek for expert advice. Thanks.
Reply
Reply
Reply
sir can you help me to size the cables for 5000A,3Phase,415Volts and the size of the cables for
2500KVA,415V, 3Phase diesel generator please help me for this
Reply
hello Sir,
I’m Ansh from lucknow , i wanted to know when cable insulation test carried out on one end R-N other
end of cables R-N are shorted or not & why….???
Reply
Reply
Hai
can you please tell me how to make the GRC-Group rating cables,
Regards
Shibu
Reply
Dear Sir,
Kindly share What is the standard parameters to be maintained daily in a transformer for both dry type
and oil type & What is dielectric strength?
Reply
Reply
Dear sir,
i want to know will there be any change inside the conductor when the cable inssulation viltage is
.4/.6kV…
Reply
Dear Sir,
Thanks for the useful chart… can u please guide me if these ratings are available in some standard or u
have calculated the same using IEC 60287.
Regards
Reply
Reply
Dear sir,
how to messring of current rate of contecter or cables
Reply
Reply
Sir,
I require 4 core. rubberised cable for 200 HP 3phase motor 380/460 volts 226 amps if possible starter
details.
Regards.
John
Reply
KINDLY SEND ME 33KV XLPE CABLE Current Rating Equivalent to Dog & panther conductor
Reply
Hello Sir,
Please tell me how to calculate the voltage drop of a 4C, 25 Sq. mm. Armoured Aluminium XLPE 1.1kv
rating cable for 80M length having current rating of 200A.
Reply
kindly if I need underground cable I will consider current carrying from above table & proceed or should
be multiply with derating factors also . ??? can you help me.
our site condition :-
ground temp. 35C >>>> factor = 0.89 as per IEC standard tables .
grouping factor >>>>>> 0.75 as per IEC standard tables .
depth laying factor >>>> 1.0 as per IEC standard tables .
soil thermal resistivity factor >>>> 1.17 as per IEC standard tables .
Reply
Super
Reply
Reply
Electrical notes are good. Pls send the transformer yard drawings
Reply
hI,
Main Cut-Out: 250 Amps
3 – Phases
Red : 163 Amps Incoming Main Load from Qatar Govt. is 105 KW
Yellow : 156 Amps Cable size 95 mm²
Blue : 105 Amps
Please let me know the Total Existing Load and alos tell me remedy to tripping off Problem.
Reply
Reply
Sir 3*400sqmm ug cable is laid in trench but cable termination is getting heating tell me reason
Reply
Dear sir u help me to amp to cable size formula & table send me my email id
Reply
Sir
thanks for info
can u provide any data regarding voltage drop by its length
Reply
Either the termination is lose or the connected load is more than your estimated load
Reply
SIr,
Can you help about how much the maximum outer diameter of can cable can be run in 50 mm 110 mm
160 mm 250 mm dia duct
Thank you
Reply
Pingback: Quora
Sir, why cant I find a Multi core cable 3.5 x 240 mm2 ?
Reply
For 140A load (Gas Analyser Heat Tracing System), 3cx150 sq mm 1.1kV Armoured Aluminium cable
shall be sufficient?? Cable to be laid in Air.
Reply
Reply
dear sir,
Reply
can anyone pls help me by sending the current carrying capacity of 3.5×35 Sq.mm aluminium cable ?
Reply
Sir, request you to please send excel based calculation sheet for selection
Reply
Dear Sir
I would like to know the amperes details of 1c,600 SQMM COPPER CABLE…
Reply
Dear sir ,
cable more type example armored , unarmored , flexible , how calculate running meter weight.
have any formula.
Reply
Dear sir ,
Reply
Prashant Jadhav on January 13, 2016 at 8:58 am
Dear sir,
We have got new project. please let us know which cable use to 200KV UPS input
Reply
as early as possible
thanks
Reply
Why do electricity board keep R N Y B phase wiring in street post and not in R Y B N in order?
Reply
Sir..!
Can you tell me the cable size in mm..
If i have to pass 500 amps of normal current and a surges of 100 amps could come to it..
Voltage is 440 V .
Cable length i need is 100 feet 1 side (single core) .
Reply
please provide the cable sizing for 1000kva DG set…we got information that -4 run of 240 sq mm cable
,single core for each phase is required.Is it like that?why?what is the calculation?
Reply
Sir,
How will calculate the cable size if load A and distance between load and source are known?
Reply
sanjeev dhiman on April 26, 2016 at 9:19 am
sir plz define. cable size increses current also increase in small dia cables but when dia increase but
current not increase with dia . define this
Reply
Dear Sir kindly help in cable selection on AC side for a solar roof top system.
1).10kw pv system for a two floried villa
Reply
Thanks!!
Reply
Sir,
We have wrongly purchased 3 core x 300 sq mm Aluminium armoured cable for main Incomer. What will
be the solution to convert this cable in 3.5 Core x 300 Sq mm cable. Please help.
Reply
sir, for 690 volt vfd application motor is it suitable for 1.1kv xlp cable or shall we required any special
cable
Reply
sir,
Please tell me if 2x3x400 sqmm XLPE cable maximum current carrying capacity will be same for
11kv,33kv and 66kv voltage level?
What is the maximum current carrying capacity?
Reply
rakesh_19781978@rediffmail.com on July 30, 2016 at 8:41 am
sir,
Please tell me if 2x3x400 sqmm XLPE cable maximum current carrying capacity is same for
11KV,33KV,66KV?
what is the max current carrying capacity for 4km cable?
Reply
Reply
Reply
10sqmm×4core xlpe ug cable is ideal for a three floor building with total capacity of 15kilowatt?
Reply
This is very informative. Please let me also have table for xlpe cable ratings at 11kv.
Reply
In Your Electrical notes ( Rev 5,page 10), Thumb rule for cable current capacity says 4 times of cable
size, 4 x 2.5 sq.mm = 9Amp. If I am not wrong then 2.5sq.mm can carry approx 22Amp
Can you please explain the basis of this thumb rule?
Reply
Reply
kishorv1kishor on February 1, 2017 at 7:38 am
Dear sir.
I am working as Sr. section Engineer in Western Railway zone of Indian Railway.I have to scrutinise
technically all material for traction distribution(Electrical branch) which is purchased by Railway.During
Technically scrutiny I am facing a problem regarding type test certificate provided by firm for IS 7098
part II(2011)or part-I(1988).How can I considered category of cable i.e. 01, C1 or C2
Reply
please I want to know what cable diameter I can use for one motor 450 volt 3 ph 60 hz 237 A in one
distance 295 meter , the cable passing from pipe with other cable together.
Thanks
Reply
How can I use cable size for 440 kW load? Please suggest Me?
Reply
Reply
2R*3.5C*240sqmm XLPE, Aluminium cable current carriynig capacity for 630Amp Incomer Feeder
panel?
Reply
please i want to note chemical electrical earthing and were use & its advantages anther earthing system ,
how many cost of instalation of one chemical earthing
Reply
Can any one tell / explain the purpose of using 1.0 kV grade and 1.1 kV grade rating of PVC/XLPE
insulated cable for low voltage since I am confused with it as some says 1.0 kV n some 1.1 kV. Logically
how do we calculate? or it is differ from country to country?
Reply
Kindly send me these charts for cable selection , i will highly appreciate.
Reply
Kindly send me the charts for the cable selection, i will highly appreciate.
Reply
Hi Jignesh, I’d like to ask for your permission to reproduce two of your Tables in my blog as I’d need
them for my personal quick reference. Am currently working on a cable installation for a raw water pump.
Thanks in advance.
Reply
Hi Sir,
I want cable joint selection chart because I check its different catalogue number for every manufacturer,
so is there any standard chart for it. Please if you have send me on my email id.
Thank you!
Reply
Very well detailed would like to have reference to a chart when paralleling cables
Reply
Good massage
Reply
Reply
Pingback: Diameter of 1100 Volts Grade XLPE, Insulated Cable (IS-7098- Part- I)
Reply
Sir,
For 100 amp load and 150 MTR distance . Single phase .. how many sq mm copper cable required..
Reply
Reply
Dear Sir .
Please send me the cable size selection chart for Low voltage & Medium voltage(pdf). I will be very great
full to you.
Regards.
Eng. Abdolgabar Ahmed
Reply
We have 2200 kVA 11/0.415 kV transformer. What would be the proper cable size at 11 kV Side ? is it
simply by current rating or we need to take 2 to 3 times..plz clarify..
Reply
hello,
am planning to set up a factory where i will need load for my machines upto 130 hp. can some one
suggest what copper armour cable should be used??
Reply
Reply
hello
can you guide Multi core cable Raw material calculation formula
Reply
Sir, please what is load capacity can 11kv aluminium xlpe power cable can carry
Reply
Sir I have confused all time in 0ne terms in 3.5*C in any cable amp rating are given per phase
Reply
hi
How to calculate derating factor. Give its formula
Reply
Jignesh.Parmar (B.E,Mtech,MIE,FIE,CEng)
Blog Stats
18,503,912 hits
Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical). He is FIE ,MIE and CEng from
Institution of Engineers,India. Membership No:F-1264873 ,M-1473586.He has more than 19 years experience in
Transmission -Distribution-Electrical Energy theft detection-Electrical Maintenance-Electrical Projects (Planning-
Designing-Technical Review-coordination -Execution). He is Presently associate with one of the leading business
group as a Deputy Manager at Ahmedabad,India. He has published numbers of Technical Articles in “Electrical
Mirror”, “Electrical India”, “Lighting India”,”Smart Energy”, “Industrial Electrix”(Australian Power Publications)
Magazines. He is Freelancer Programmer of Advance Excel and design useful Excel base Electrical Programs as per
IS, NEC, IEC,IEEE codes. He is Technical Blogger and Familiar with English, Hindi, Gujarati, French languages. He
wants to Share his experience & Knowledge and help technical enthusiasts to find suitable solutions and updating
themselves on various Engineering Topics.
Enter your email address to follow this blog and receive notifications of new posts by email.
85 /100
Search
Copyright © 2018
The content in electricalnotes.wordpress.com is for personal, non-commercial use only. you can not
reproduce,republish or communicate any of the content , including files downloadable from this website, without the
permission of the copyright owner.The use of this content on any other websites breaches copyright Act. If You find
this content in any other site,it makes the page you are viewing an infringement of the copyright.
Recent Posts
Archives
November 2021 (1)
October 2021 (2)
September 2021 (2)
August 2021 (2)
July 2021 (1)
June 2021 (2)
May 2021 (1)
April 2021 (2)
March 2021 (2)
February 2021 (2)
January 2021 (2)
December 2020 (1)
November 2020 (1)
October 2020 (2)
September 2020 (1)
August 2020 (2)
July 2020 (2)
June 2020 (2)
May 2020 (2)
April 2020 (2)
March 2020 (2)
February 2020 (2)
January 2020 (1)
December 2019 (1)
November 2019 (1)
October 2019 (2)
September 2019 (2)
August 2019 (2)
July 2019 (2)
June 2019 (1)
May 2019 (2)
April 2019 (3)
March 2019 (2)
February 2019 (2)
January 2019 (3)
December 2018 (2)
November 2018 (2)
October 2018 (1)
September 2018 (2)
August 2018 (3)
July 2018 (1)
June 2018 (1)
May 2018 (1)
April 2018 (1)
March 2018 (1)
February 2018 (2)
January 2018 (1)
December 2017 (1)
November 2017 (1)
October 2017 (1)
September 2017 (1)
August 2017 (1)
July 2017 (2)
June 2017 (1)
May 2017 (1)
April 2017 (1)
March 2017 (1)
February 2017 (1)
January 2017 (1)
December 2016 (1)
November 2016 (1)
October 2016 (1)
September 2016 (1)
August 2016 (1)
July 2016 (1)
June 2016 (1)
May 2016 (1)
April 2016 (2)
March 2016 (2)
February 2016 (2)
January 2016 (2)
December 2015 (1)
November 2015 (1)
October 2015 (2)
September 2015 (1)
August 2015 (1)
July 2015 (1)
June 2015 (1)
May 2015 (1)
April 2015 (1)
March 2015 (2)
February 2015 (2)
January 2015 (2)
December 2014 (2)
November 2014 (2)
October 2014 (2)
September 2014 (2)
August 2014 (3)
July 2014 (2)
June 2014 (2)
May 2014 (2)
April 2014 (2)
March 2014 (3)
February 2014 (4)
January 2014 (2)
December 2013 (1)
November 2013 (1)
October 2013 (2)
September 2013 (3)
August 2013 (3)
July 2013 (3)
June 2013 (3)
May 2013 (3)
April 2013 (2)
March 2013 (3)
February 2013 (2)
January 2013 (3)
December 2012 (2)
November 2012 (3)
October 2012 (1)
September 2012 (3)
August 2012 (7)
July 2012 (2)
May 2012 (7)
April 2012 (2)
March 2012 (3)
February 2012 (2)
January 2012 (1)
December 2011 (3)
November 2011 (2)
October 2011 (4)
September 2011 (2)
August 2011 (1)
June 2011 (5)
May 2011 (3)
April 2011 (12)
March 2011 (17)
EEP
Pages
Electrical Calculation
Electrical Notes
Electrical. Q&A
Electrical Q&A Part-1
Electrical Q&A Part-2
Electrical Q&A Part-3
Electrical Q&A Part-4
Electrical.Tools
Top Clicks
instamojo.com/jiguparmar/…
electricalnotes.files.wor…
mediafire.com/file/5040ut…
electricalnotes.files.wor…
gumroad.com/l/inOq
mediafire.com/file/91cpju…
mediafire.com/file/76blr8…
mediafire.com/file/0qu8mt…
electricalnotes.files.wor…
electricalnotes.files.wor…
Recent Comments
Close and accept Privacy & Cookies: This site uses cookies. By continuing to use this website, you agree to their
use.
To find out more, including how to control cookies, see here: Cookie Policy