XLPE Cable-Current Rating

XLPE Insulated Armored & Unarmored Cables:

1.1 KV SINGLE CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I)

Cross- UN-ARMOURED CABLE


sectional
area
Overall Normal Current Rating in Amps Short Circuit Current
(Sq MM)
Diameter Rating for
(mm) 1Sec.duration in K.
Amps

Aluminums Conductor Copper Conductor Aluminums Copper

Ground Duct Air Ground Duct Air

1cX4 8 — — — 48 47 45 0.376 0.572

1cX 6 9 48 45 45 60 59 57 0.564 0.858

1cX10 10 62 62 61 80 78 77 0.940 1.430

1cX16 11 81 80 83 104 102 106 1.504 2.288

1cX25 12 99 90 115 130 115 145 2.350 3.575

1cX 35 13 117 110 135 155 140 175 3.290 5.005

1cX50 15 138 125 170 185 165 215 4.700 7.150

1cX70 16 168 155 210 225 200 270 6.580 10.01

1cX 95 18 204 185 255 265 235 330 8.930 13.59


1cX120 20 230 210 300 300 265 380 11.28 17.16

1cX150 22 265 230 342 335 300 430 14.10 21.45

1cX185 24 295 260 385 380 335 495 17.39 26.46

1cX240 27 340 300 450 435 385 590 22.56 34.32

1cX300 30 390 335 519 490 430 670 28.20 42.90

1cX400 33 450 380 605 550 480 780 37.60 57.20

1cX 500 36 500 430 700 610 530 900 47.00 71.50

1cX 630 40 555 485 809 680 590 1020 59.22 90.09

1cX800 47 625 530 935 740 630 1140 75.20 114.40

1cX1000 51 690 570 1065 780 660 1250 94.00 143.00

1.1 KV SINGLE CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I)

Cross- ARMOURED CABLE


sectional
area
Overall Normal Current Rating in Amps Short Circuit Current
(Sq MM)
Diameter Rating for
(mm) 1Sec.duration in K.
Amps

Aluminums Conductor Copper Conductor Aluminums Copper

Ground Duct Air Ground Duct Air

1cX4 10 — — — 48 47 45 0.376 0.572

1cX 6 11 45 45 40 60 59 57 0.56 0.858

1cX10 12 59 62 53 80 78 77 0.94 1.43

1cX16 13 76 80 73 104 102 106 1.50 2.29

1cX25 14 99 90 115 130 115 145 2.35 3.58

1cX 35 15 117 110 140 155 140 175 3.29 5.01

1cX50 17 138 125 170 185 165 215 4.70 7.15

1cX70 19 168 155 210 225 200 270 6.58 10.01


1cX 95 22 204 185 255 265 235 330 8.93 13.59

1cX120 24 230 210 300 300 265 380 11.28 17.16

1cX150 25 265 230 342 335 300 430 14.10 21.45

1cX185 28 295 260 385 380 335 495 17.39 26.46

1cX240 30 340 300 450 435 385 590 22.56 34.32

1cX300 33 390 335 519 490 430 670 28.20 42.90

1cX400 38 450 380 605 550 480 780 37.60 57.20

1cX 500 41 500 430 700 610 530 900 47.00 71.50

1cX 630 46 555 485 809 680 590 1020 59.22 90.09

1cX800 51 625 530 935 740 630 1140 75.20 114.40

1cX1000 56 690 570 1065 780 660 1250 94.00 143.00

1.1 KV Two CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)

Cross- UN-ARMOURED CABLE


sectional
area
Overall Normal Current Rating in Amps Short Circuit Current
(Sq MM)
Diameter Rating for
(mm) 1Sec.duration in K.
Amps

Aluminums Conductor Copper Conductor Aluminums Copper

Ground Duct Air Ground Duct Air

2cX4 13 34 28 30 44 37 39 0.376 0.572

2cX 6 14 43 37 40 55 47 50 0.564 0.858

2cX10 17 57 48 53 74 61 67 0.940 1.430

2cX16 17 78 61 70 94 78 85 1.50 2.29

2cX25 19 95 80 99 120 100 125 2.35 3.58

2cX35 20 116 94 117 145 120 155 3.29 5.01

2cX50 22 140 110 140 170 145 190 4.70 7.15


2cX70 25 170 140 176 210 175 235 6.58 10.01

2cX95 28 200 165 221 250 210 290 8.93 13.59

2cX120 31 225 185 258 285 240 330 11.28 17.16

2cX150 33 255 210 294 315 270 375 14.10 21.45

2cX185 37 285 235 339 355 300 435 17.39 26.46

2cX240 41 325 270 402 410 350 510 22.56 34.32

2cX300 44 370 305 461 460 390 590 28.20 42.90

2cX400 48 435 350 542 520 440 670 37.60 57.20

2cX500 54 481 405 624 580 480 750 47.00 71.50

2cX630 62 537 470 723 680 575 875 59.22 90.09

1.1 KV Two CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)

Cross- ARMOURED CABLE


sectional
area
Overall Normal Current Rating in Amps Short Circuit Current
(Sq MM)
Diameter Rating for
(mm) 1Sec.duration in K.
Amps

Aluminums Conductor Copper Conductor Aluminums Copper

Ground Duct Air Ground Duct Air

2cX4 15 34 28 30 44 37 39 0.376 0.572

2cX 6 16 43 37 40 55 47 50 0.564 0.858

2cX10 18 57 48 53 74 61 67 0.940 1.430

2cX16 19 78 61 70 94 78 85 1.50 2.29

2cX25 21 95 80 99 120 100 125 2.35 3.58

2cX35 23 116 94 117 145 120 155 3.29 5.01

2cX50 25 140 110 140 170 145 190 4.70 7.15


2cX70 28 170 140 176 210 175 235 6.58 10.1

2cX95 31 200 165 221 250 210 290 8.93 13.59

2cX120 34 225 185 258 285 240 330 11.28 17.16

2cX150 37 255 210 294 315 270 375 14.10 21.45

2cX185 40 285 235 339 355 300 435 17.39 26.46

2cX240 45 325 270 402 410 350 510 22.56 34.32

2cX300 49 370 305 461 460 390 590 28.20 42.90

2cX400 52 0.33 435 350 542 520 440 670 37.60

2cX500 60 0.34 481 405 624 580 480 750 47.00

2cX630 66 0.36 537 470 723 680 575 875 59.22

1.1 KV Three CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)

Cross- UN-ARMOURED CABLE


sectional
area
Overall Normal Current Rating in Amps Short Circuit Current
(Sq MM)
Diameter Rating for
(mm) 1Sec.duration in K.
Amps

Aluminums Conductor Copper Conductor Aluminums Copper

Ground Duct Air Ground Duct Air

3cX 4 14 34 28 30 44 37 39 0.376 0.572

3cX 6 16 43 37 40 55 47 50 0.564 0.858

3cX 10 18 57 48 53 74 61 67 0.940 1.430

3cX 16 18 78 61 70 94 78 85 1.50 2.29

3cX 25 21 95 80 99 120 100 125 2.35 3.58

3cX 35 22 116 94 117 145 120 155 3.29 5.01

3cX 50 25 140 110 140 170 145 190 4.70 7.15

3cX 70 30 170 140 176 210 175 235 6.58 10.01


3cX 95 32 200 165 221 250 210 290 8.93 13.59

3cX 120 35 225 185 258 285 240 330 11.28 17.16

3cX 150 39 255 210 294 315 270 375 14.10 21.45

3cX 185 43 285 235 339 355 300 435 17.39 26.46

3cX 240 49 325 270 402 410 350 510 22.56 34.32

3cX 300 53 370 305 461 460 390 590 28.20 42.90

3cX 400 59 435 350 542 520 440 670 37.60 57.20

3cX 500 66 481 405 624 580 480 750 47.00 71.50

3cX 630 73 537 470 723 680 575 875 59.22 90.09

1.1 KV Three CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I)

Cross- ARMOURED CABLE


sectional
area
Overall Normal Current Rating in Amps Short Circuit Current
(Sq MM)
Diameter Rating for
(mm) 1Sec.duration in K.
Amps

Aluminums Conductor Copper Conductor Aluminums Copper

Ground Duct Air Ground Duct Air

3cX 4 18 34 28 30 44 37 39 0.376 0.572

3cX 6 19 43 37 40 55 47 50 0.564 0.858

3cX 10 20 57 48 53 74 61 67 0.940 1.430

3cX 16 20 78 61 70 94 78 85 1.50 2.29

3cX 25 23 95 80 99 120 100 125 2.35 3.58

3cX 35 25 116 94 117 145 120 155 3.29 5.01

3cX 50 29 140 110 140 170 145 190 4.70 7.15

3cX 70 32 170 140 176 210 175 235 6.58 10.01

3cX 95 35 200 165 221 250 210 290 8.93 13.59


3cX 120 39 225 185 258 285 240 330 11.28 17.16

3cX 150 43 255 210 294 315 270 375 14.10 21.45

3cX 185 48 285 235 339 355 300 435 17.39 26.46

3cX 240 53 325 270 402 410 350 510 22.56 34.32

3cX 300 58 370 305 460 460 390 590 28.20 42.90

3cX 400 65 435 350 542 520 440 670 37.60 57.20

3cX 500 72 481 405 624 580 480 750 47.00 71.50

3cX 630 81 537 470 723 680 575 875 59.22 90.09

1.1 KV Three CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)

Cross- UN-ARMOURED CABLE


sectional
area (Sq
Overall Normal Current Rating in Amps Short Circuit Current
MM)
Diameter Rating for
(mm) 1Sec.duration in K.
Amps

Aluminums Conductor Copper Conductor Aluminums Copper

Ground Duct Air Ground Duct Air

3.5X25 22 95 80 99 120 100 125 2.35 3.58

3.5X35 24 116 94 117 145 120 155 3.29 5.01

3.5X50 27 140 110 140 170 145 190 4.70 7.15

3.5X70 31 170 140 176 210 175 235 6.58 10.01

3.5X95 34 200 165 221 250 210 290 8.93 13.59

3.5X120 38 225 185 258 285 240 330 11.28 17.16

3.5X150 43 255 210 294 315 270 375 14.10 21.45

3.5X185 46 285 235 339 355 300 435 17.39 26.46

3.5X240 52 325 270 402 410 350 510 22.56 34.32

3.5X300 57 370 305 461 460 390 590 28.20 42.90


3.5X400 65 435 350 542 520 440 670 37.60 57.20

3.5X500 73 481 405 624 580 480 750 47.00 71.50

3.5X630 82 537 470 723 680 575 875 59.22 90.09

1.1 KV Three & Half CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)

Cross- ARMOURED CABLE


sectional
area (Sq
Overall Normal Current Rating in Amps Short Circuit Current
MM)
Diameter Rating for
(mm) 1Sec.duration in K.
Amps

Aluminums Conductor Copper Conductor Aluminums Copper

Ground Duct Air Ground Duct Air

3.5X25 25 95 80 99 120 100 125 2.35 3.58

3.5X35 27 116 94 117 145 120 155 3.29 5.01

3.5X50 30 140 110 140 170 145 190 4.70 7.15

3.5X70 35 170 140 176 210 175 235 6.58 10.01

3.5X95 38 200 165 221 250 210 290 8.93 13.59

3.5X120 42 225 185 258 285 240 330 11.28 17.16

3.5X150 46 255 210 294 315 270 375 14.10 21.45

3.5X185 51 285 235 339 355 300 435 17.39 26.46

3.5X240 56 325 270 402 410 350 510 22.56 34.32

3.5X300 60 370 305 461 460 390 590 28.20 42.90

3.5X400 71 435 350 542 520 440 670 37.60 57.20

3.5X500 79 481 405 624 580 480 750 47.00 71.50

3.5X630 88 537 470 723 680 575 875 59.22 90.09


1.1 KV Four CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I)

Cross- UN-ARMOURED CABLE


sectional
area (Sq
Overall Normal Current Rating in Amps Short Circuit Current
MM)
Diameter Rating for
(mm) 1Sec.duration in K.
Amps

Aluminums Conductor Copper Conductor Aluminums Copper

Ground Duct Air Ground Duct Air

4cX4 17 34 28 30 44 37 39 0.376 0.572

4cX 6 18 43 37 40 55 47 50 0.564 0.858

4cX 10 20 57 48 53 74 61 67 0.940 1.430

4cX16 20 78 61 70 94 78 85 1.50 2.29

4cX 25 24 95 80 99 120 100 125 2.35 3.58

4cX35 26 116 94 117 145 120 155 3.29 5.01

4cX 50 29 140 110 140 170 145 190 4.70 7.15

4cX70 34 170 140 176 210 175 235 6.58 10.01

4cX 95 37 200 165 221 250 210 290 8.93 13.59

4cX 120 41 225 185 258 285 240 330 11.28 17.16

4cX 150 45 255 210 294 315 270 375 14.10 21.45

4cX 185 50 285 235 339 355 300 435 17.39 26.46

4cX 240 56 325 270 402 410 350 510 22.56 34.32

4cX 300 63 370 305 461 460 390 590 28.20 42.90

4cX 400 70 435 350 542 520 440 670 37.60 57.20

4cX 500 79 481 405 624 580 480 750 47.00 71.50

4cX 630 88 537 470 723 680 575 875 59.22 90.09

1.1 KV Four CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I)
Cross- ARMOURED CABLE
sectional
area (Sq
Overall Normal Current Rating in Amps Short Circuit Current
MM)
Diameter Rating for
(mm) 1Sec.duration in K.
Amps

Aluminums Conductor Copper Conductor Aluminums Copper

Ground Duct Air Ground Duct Air

4cX4 18 34 28 30 44 37 39 0.376 0.572

4cX 6 19 43 37 40 55 47 50 0.564 0.858

4cX 10 21 57 48 53 74 61 67 0.940 1.430

4cX16 22 78 61 70 94 78 85 1.50 2.29

4cX 25 26 95 80 99 120 100 125 2.35 3.58

4cX35 28 116 94 117 145 120 155 3.29 5.01

4cX 50 32 140 110 140 170 145 190 4.70 7.15

4cX70 37 170 140 176 210 175 235 6.58 10.01

4cX 95 40 200 165 221 250 210 290 8.93 13.59

4cX 120 44 225 185 258 285 240 330 11.28 17.16

4cX 150 49 255 210 294 315 270 375 14.10 21.45

4cX 185 54 285 235 339 355 300 435 17.39 26.46

4cX 240 65 325 270 402 410 350 510 22.56 34.32

4cX 300 68 370 305 460 460 390 590 28.20 42.90

4cX 400 76 435 350 542 520 440 670 37.60 57.20

4cX 500 86 481 405 624 580 480 750 47.00 71.50

4cX 630 94 537 470 723 680 575 875 59.22 90.09

Rate this:

44 Votes

Share this:
! Facebook " Email # LinkedIn $ More

Like
One blogger likes this.

Related

EHV XLPE – Current Rating PCV Cable-Current Rating Electrical Useful Equations
April 26, 2011 April 24, 2011 July 27, 2013
With 11 comments With 19 comments With 70 comments

April 24, 2011  199 Replies

« Previous Next »

Leave a Reply
Your email address will not be published. Required fields are marked *

Comment

Name

*
Email

*
Website
Post Comment

Notify me of new comments via email.

Notify me of new posts via email.

This site uses Akismet to reduce spam. Learn how your comment data is processed.

Syed Saif Ahmed on May 23, 2011 at 12:15 pm

Dear Sir / Madam,


Post Comment
Please send me the cable size selection chart for Low voltage & Medium voltage. I will be very great full
to you.
Regards
Syed

 Reply

Jignesh.Parmar on May 24, 2011 at 4:02 pm

I have already given in XLPE, PVC Cable section

 Reply

senthil kumar on November 20, 2012 at 6:33 am

Hai good morning, You have done a good job. it’s very useful to me. Thank you

Arul on December 17, 2012 at 9:53 am

Ur information is very useful thank you

Prakash Parmar on June 2, 2016 at 5:14 am

Dear sir, I Prakash Parmar from Suyog Electricals Ltd, 1 query about XLPE cable current
rating base on on which IS standard & its calculation please provide information

Harish chandera Dubey on June 22, 2016 at 10:47 am

Dear sir
please send cable chart – 596.8kw mens how much sq mm required AL /CU
regards
Harish
9850985429

jotin on July 22, 2016 at 10:01 am

plz send the details for cable sizing for primary and secondary side of 250 KVA transformer

sandeep saini on January 10, 2019 at 3:27 pm

Jignesh Ji can you please tell me how to calculate the power loss in single core cable.
regards
sandeep saini

narasimha on June 15, 2015 at 1:38 pm

sir i need list of motor hp fuse amps kw cable size gland size please i Will request you send me my
mail sir.

 Reply

narasimha on June 15, 2015 at 1:40 pm

total ratings previous publishing very nice am seened they

Ramachandra laxman on July 5, 2011 at 6:16 pm

Thank you for this cable selection chart. Thank u verymuch. Do u have any information about
conductor,s DC current carrying capacity .Please help me sir, Thank u.

 Reply

p.vadivel on August 10, 2011 at 3:08 pm

dear sir,
ratinng cable size of 300kva to 450kva trasformer.

 Reply

shafeeq on August 16, 2011 at 10:12 pm


dear sir,
thanks.can you please give details of selecting UPS and generators rating.

 Reply

Ramchandra B Damle on October 12, 2011 at 4:25 am

Dear Sir

Will you please furnish me short time ratings of HT XLPE insulated cables e. g. 10% for XXX Hrs., 20%
for XXX Hrs. and so on ?

 Reply

SHAMAUN HAKIM on October 26, 2011 at 1:52 am

Can a 10 guage XPLE insulated copper wire used as leads for oil immersed CTs withstand around 90
deg C continously in transformer oil? What is the compatability of XPLE wire with transformer oil? What
is the specific density of XLPE insulation?

 Reply

Gnana Reuben on November 2, 2011 at 11:40 am

Can we get the standard from which the XLPE current values are derived / referred.

 Reply

paulson on November 25, 2011 at 11:09 am

can you tell me the voltage drop calcultaion of 11KV XLPE cable around 600m long

 Reply

Jignesh.Parmar on November 27, 2011 at 3:51 pm

Use Excel Base Program to Calculate LT-MV-HT Cable from “Electrical Tool” Page of This Blog

(1) Cable Designing Program:

DOWNLOAD:

Calculate Voltage drop of Cable.


Calculate Size of Cable.
Calculate Current Capacity of Cable.

 Reply

paulson on November 30, 2011 at 6:40 am


Mr Jignesh,

what is the difference between MCCB,ACB and VCB..

I heard that above 630A we should use ACB ,but MCCB’s are available till 1600A.

So can you tell me from which rating we have to go for ACB and VCB

Is there any difference in the operation of MCCB and ACB.

Thanking you,
Paulson

karuppanasamy on January 7, 2014 at 3:50 pm

i am engaged in arecanut leaf plate manufacturing activity which need heaters with die of
8000 watts.what specification of power cable can i put.

Amit Thakur on November 20, 2015 at 10:02 am

Dear Sir,

i what to learn the HT cable sizing. how to calculate it . Can you help me. If you have any
excel Sheet kindly shear with me.

Priya on March 20, 2017 at 8:16 am

Dear Sir,

Really very happy…Your Calculation your explanation are very nice and useful for us.

krishan chand on December 8, 2011 at 1:49 pm

please send details of


1-cable size with current rating data
2- cable gland size & type
3- rating of contractor & over load relay

 Reply

Jignesh.Parmar on December 8, 2011 at 5:18 pm

This Topic is already covered.Read Electrical Notes Carefully


 Reply

nirav shah on August 14, 2013 at 3:13 pm

Dear Jignesh, I am nirav shah from hyderabad. i would like to know what is the difference
between current carrying capacity for xlpe insulated single core copper flexible cables for
AC and Dc applications. Benchmark being single core 240sqmm which can carry upto
550amps in AC application.

Udaikiran on January 18, 2012 at 7:51 am

Dear Sir,

Details furnished by you are excellent.Sir, i need to buy the unlock version .Did you published any books
on cable sizing,busbar calculation, breaker designing etc?My maid id is udai_kiran1983@yahoo.com

 Reply

randy addae junior on October 17, 2012 at 9:53 am

please can i get a copy of your book in ghana?

 Reply

ramkewal on January 29, 2012 at 7:06 pm

sir, i read to this cable size and current rating chart it is very use full for us so i request u please send this
chart in my Email
RAMKEWAL

 Reply

ramkewal on January 29, 2012 at 7:09 pm

i will be hope full with this chart


Thank you.
RAMKEWAL

 Reply

Ronald Mutambiranwa on February 1, 2012 at 1:27 pm

Dear Sir / Madam,


Please send me the cable size selection chart for Low voltage & Medium voltage(single phase and three
phase indicating amps each size can carry. I will be very great full to you
 Reply

Babji Duvva on March 22, 2012 at 10:57 am

can you please provid me for the current rating for 1C X 185 SQ MM copper cables

 Reply

Jignesh.Parmar on March 22, 2012 at 3:48 pm

It is already Given on the following Post


https://electricalnotes.wordpress.com/2011/04/24/xlpe-cable-current-rating/

 Reply

Babji on March 23, 2012 at 4:01 am

sorry i want the current carrying capacity in DC power( 750 V, and 440 V )

Thank you.

Manojkumar on September 11, 2015 at 4:36 am

hi sir will you please tell me the calculation formula fo these & also i want to know the cable
size for 11kv tranfomer to the panel

Manoj Patil on September 20, 2015 at 12:02 pm

Dear

Plz confrim the Load and distance of TR. To panel

Regards Manoj Patil On Sep 20, 2015 5:21 PM, “Electrical Notes & Articles” wrote:

> Manojkumar commented: “hi sir will you please tell me the calculation > formula fo these
& also i want to know the cable size for 11kv tranfomer to > the panel”

nmr on April 1, 2012 at 11:56 am

11kv/433v TFP-1000 kva/500kva/750kva the fl currents on LT side are 1333.3/1000/666.6 amps. what is
size of 4 core xlpe alluminium is used pl tell me.

 Reply
Jignesh.Parmar on April 1, 2012 at 12:33 pm

Download Excel base Sheet to decide Cable Size from “EXCEL TOOL” page.
To decide Cable Size We need two important Data
(1) Load
(2)Distance.

 Reply

vamsi on August 22, 2012 at 7:17 am

this chart about cables is nice but give us some information about OH cables, and underground cables .

 Reply

d s negi on October 5, 2012 at 9:22 am

WHAT IS THE BIS – IS CODE FOR 11 KV CROSS ARMOURED CABLE

 Reply

Azad Anupam on October 16, 2012 at 2:26 pm

Very useful….

 Reply

Mohammed on November 1, 2012 at 4:54 pm

Dear Jignesh,

Your cable selection table is very helpful. But i’ve a question to clarify? how do we determine the cable
current capacity of cables running in parallel? for example if my breaker is rated at 1000A, what size of
cable conductor should be terminating at the terminals per phase, can i terminate 2 x 1c x 400 per
phase or how do we decide the conductor sizing? as i understand there is a derating factor of cables
when connected in parallel? may be you can ellaborate further and may be send me details on the cable
sizing formulation and other useful data on my email : manjarwalla@gmail.com

 Reply

Jignesh.Parmar on November 1, 2012 at 5:03 pm

Use Equation
% Voltage Drop:=(1.732 X (Full Load Current)X(RCosØ+j SinØ)XLengthX100) / Line Voltage X No of
Run X 1000.
Here No of Run cable is Either 1,2 or more in parallel.
You can also use “Cable Design” sheet of the Excel Tool Page of this Blog
 Reply

Mohammed on November 1, 2012 at 5:55 pm

Dear Jignesh,

Thank you for your prompt reply. I’ve also gone through your cable design excel
sheet,wonderful program. On the cable design program how do you determine the starting
and running cos and sin thetha? do you have any thumb rule for calculating the cable runs
in a faster way? for example if my full load current is 1000A as incomer or any feeder load
connected to my panel. As from the program i’ve to input the the respective KW to attain
nearest full load current before i can get the runs of cables?

B.R.Suryawanshi on November 3, 2012 at 8:10 am

Dear Sir,
Plz.tel me this XLPE cables can we use 100% loading? for How much length cables are de rated?
Thanks.

 Reply

Jignesh.Parmar on November 3, 2012 at 5:03 pm

this Rating is as per Standard Cable Catalog and IS. Cable Rating never indicate derating factor.
Because Derating Factor depends upon Your Application.
It is depend upon Type of Laying Cable –
=In Air,Land, at 0.500mt depth at 1 meter depth,
=Air-Land Temperature,
=in bundle,=In separate,Distance between two Cable, etc.
If Cable Rating is 100 Amp It may be 80 Amp or 90 Amp or 100 Amp depend upon Laying of cable.

 Reply

A. A. Mahadik on November 22, 2012 at 7:13 pm

Pl. send me LT cable current carrying capacity charts

 Reply

Jignesh.Parmar on November 23, 2012 at 2:05 pm

Already available on this Blog . Please Refer Post of “PVC Flexible Wire Rating”
I have already Put Cable/Wire Rating Starting from 430V to 66KV (Earthed/Unearthed Cable)

 Reply
lal bahadur chand on December 19, 2012 at 7:35 pm

Varry importent for me this. Site

 Reply

shine on February 26, 2013 at 12:23 pm

Good work, its very useful

 Reply

hariharan.v on March 7, 2013 at 6:44 pm

sir,if i have 7.5kw unit then how can i select cable for that unit with out using chart.give me that formula
for me.

 Reply

Jignesh.Parmar on March 8, 2013 at 2:12 pm

Use Cable Size Program of this Blog. (Formula is given in the Program)

 Reply

zahid on March 10, 2013 at 12:22 pm

well done sir you have a great job and sacrifices for Electrical Engineering.

 Reply

Hareesh R on April 20, 2013 at 7:53 am

Hi,
I really appreciate your effort to share consolidated information..

 Reply

sulaimant on May 3, 2013 at 6:33 pm

dear
sir/madem
pleas send me cebel formula for given voltag and
also send me cabel and amp tebal

 Reply
Jignesh.Parmar on May 4, 2013 at 2:40 pm

Download Cable selection Program from this Blog..here You can find Formulas and Table also…

 Reply

hemant kumar on May 6, 2017 at 11:07 am

i want to this information sir

Jayaprakash.N on May 22, 2013 at 4:34 pm

It is very useful informations… Gr8

 Reply

Ribhu Gaur on May 23, 2013 at 7:39 am

what is the thumb rule for above calcualtions..? please share the formula for approximate current ratings
in 1.1 kv XLPE cables .

 Reply

kuruvilla on June 26, 2013 at 9:38 am

Mr. Jignesh, can you please tell me what size of cable is required for solar installation. My panel rating is
Isc=8.5 A, Voc=36.5 V. I’m using two series panels in 3 arrays, basically an 2×3 system. Thanks. Length
one way will be 30 feet from panels to inverter.

 Reply

parvejahamad on November 3, 2015 at 8:04 am

Electrical Rasio used

 Reply

Nasir on July 9, 2013 at 5:43 pm

400 volt,528 amp and insulation xlpe ,cable size required

 Reply

vinod pol on August 1, 2013 at 10:08 am

hiii sir, thanx for this information but sir pls tell me the formula or any thumb rule for calculating of
cable/wire size as per given load…..

 Reply

Abdul Guffar on August 23, 2013 at 10:51 am

Thank you for this cable selection chart. Do u have any information about conductor,s DC current
carrying capacity .Please mail me sir, Thank u.

 Reply

prabhakar on August 29, 2013 at 5:45 am

sir
can u tell me the formula how to calculate the cable sizes corresponding amps..

 Reply

mintu kumar pandit on September 22, 2013 at 8:15 am

why use mastic tape for 11 kv cable joint,please tell me sir.

 Reply

Mintu Kumar Pandit on September 24, 2013 at 5:24 pm

Dear sir,
what is the function of cable fillers ? please reply.

 Reply

Mintu Kumar Pandit on September 24, 2013 at 7:18 pm

sir ,
difference between round shape cable and delta shape cable please me understand

 Reply

mintu kumar pandit on October 4, 2013 at 10:41 am

whats type of 11kv spout ?

 Reply

Anees Mustafa on October 4, 2013 at 1:18 pm

electrical infrastructure construction Q&A for exp houseing scheme what are requrment of
houesing scheme of all utlates and what are gape electrical serviese between water
,sewg,gas and other serviese in under ground

krishnamurthy on November 2, 2013 at 2:11 pm

How to measure currenraings of armed & unarmed cables

 Reply

krishnamurthy on November 8, 2013 at 3:33 pm

Differance between kw,kvar and kva

 Reply

Anil Thomas on November 16, 2013 at 7:48 am

I want to know that whats the current carrying capacity for 4 runs of 3.5 core 400 Sq.mm Al.
armoured XLPE cable in ground . How it can be calculate. ( please send a copy of tables if
any )

which means if 3.5 core 400sq.mm cable carries 370 amps in ground and when it is 2 runs it
will not be double of 370. it will less than double. how it will calculate ???

Please give me a reply


with regards
By Anil

Jignesh.Parmar on November 16, 2013 at 5:10 pm

You are mixing two different topic ..


(1) If we laid cable in ground,air or trench it’s current capacity will be decrease due to
surrounding temp.
(2) If we laid cable in group / single it’s current capacity will be decrease those effect called
“derating factor of cable..
You find in Electrical Tool page.
If we run two cable for same phase obviously it’s capacity would be double…

KRISHNAMURTHY on November 17, 2013 at 1:57 pm

How to measure capacitance&inductance in A.P.Transco meters and send formula of


KW&KVAR&KVA.
KIRAN PATEL on November 13, 2013 at 11:11 pm

KIRAN PATEL
dear sir what is service factor in motor and which kind machine in use same motor

 Reply

bj vijay on November 15, 2013 at 4:12 pm

Hai …

 Reply

John on November 18, 2013 at 10:02 am

Dear Sir,

My doubt might sound silly to you, but I just wanted to clarify it. From the given cable ampacity ratings in
the tables above, how can we calculate the maximum power rating for the respective multi-core cables.

Thank you.

 Reply

Jignesh.Parmar on November 18, 2013 at 2:38 pm

Given Rating are single and Multi core cable..

 Reply

John on November 18, 2013 at 5:50 pm

For example: for a 4 core 120 sqmm Aluminium conductor cable, what is the maximum
power capacity? Should we multiply the given ampacity with single phase voltage or 3
phase voltage to find out maximum load it can handle?

Jignesh.Parmar on November 21, 2013 at 5:26 pm

Use “Cable Size Calculation” sheet of this Blog

Suresh Chaudhary on November 19, 2013 at 1:35 pm

Dear Jignesh,
pl suggest me regarding cable rating across laying ground 700 running feet for 750A load bearing at
resisdence building there jurk load AC. Pl give cable size.
Regards,
Suresh Chaudhary

 Reply

bikram kaushik on November 20, 2013 at 6:57 pm

there is no any power rating of cable.only current rating of cable are mentioned.power rating is
concerned to the equipment.

 Reply

Shruthi on November 27, 2013 at 7:08 am

Dear Jignesh,
Sir what’s the formula to select the cables sizes for the particular current ratings?

 Reply

Jignesh.Parmar on November 27, 2013 at 2:21 pm

Refer “Cable Size” Excel base program from “Electrical Tools” Page

 Reply

Masoud Bu-Arbyay on December 4, 2013 at 8:08 pm

You did good , its very useful

 Reply

mohamed on December 10, 2013 at 7:58 pm

dear jignesh how to calculate the busbar size in 630amps breaker 3ph ?

 Reply

Manoj Patil on February 10, 2014 at 1:52 pm

Dear Sir

Thanks for this information. this is very usefull for us.

 Reply

sunil on February 13, 2014 at 7:12 am

Dear Sir,
Can you explain that the current rating you have mentioned in Ground ,Air, or duct is quite opposite to
what manufacture state in their product catalogue.

regards

 Reply

Perumalkonar on February 21, 2014 at 8:27 am

how many runs of 3.5C 240 sq.mm al. conductor xlpe pvc insulted cables to be laid to supply to a circuit
which is maximum current draw is 800 A.

 Reply

Jignesh.Parmar on February 21, 2014 at 5:44 pm

Distance !!!! Use Excel Cable Size Calculation sheet of this Blog..

 Reply

shree raja on February 21, 2014 at 2:00 pm

Yes very use full.thank you.

 Reply

venu on February 23, 2014 at 12:01 pm

Sir,

please let me know the current carrying capacity of 3C*2.5 sqmm copper cable in air.

 Reply

karan on March 10, 2014 at 10:36 am

sir,
if i want to select power cable for 2o hp motor. and i am going to use 3 core alluminium cable.
then what will be the cable size?

 Reply

brijmohan on April 25, 2014 at 12:40 pm

sir
3.5core 50 sqmm ki cabel par fes kitana amp legislative

 Reply
manoj singh on April 15, 2014 at 7:58 am

sir,
if i want to select 50sq cable for 11kv. and i am going to use 3 core cable.
then what will be the cable size?

 Reply

Fetsum Asayehegn on April 16, 2014 at 9:32 am

your table is very useful, thank you and I need the cable size of 22 kw, 3ph, 380volt for my deep
well pump motor at a deep distance of 300 metrrs
Thank you & best regards,
Fetsum

 Reply

PETER BIBIN M J on July 23, 2014 at 5:38 am

thanks for this great cable chart…

 Reply

Fadi on July 27, 2014 at 6:23 am

Hi

Can I know how many runs of single core 630 mm are required for a 1000 KVA transformer ?

 Reply

Teshome on August 29, 2014 at 3:14 pm

Dear Sir;
I would like to say thank you so much for the access you made open to get the size of power cables.
Teshome, from Ethiopia

 Reply

shadab uddin on September 8, 2014 at 6:05 am

Dear sir/ Madam


Please send me the cable size selection chart & amps details

 Reply

J.P.Nandaniya on September 13, 2014 at 6:03 am


Dear Sir,
Kindly give me chart for motor hp kw flc relay contactor mccb current carring capacity for all and cu and
gland size.

 Reply

fawad on September 16, 2014 at 2:23 am

hi…. i have find question about how to find current of 132kv,1200mm^2 cross sec area,in flat formation
with 400 mm disc presnt btween them,,is there any formuala ,so guide me plzzzzz,thnkxxxx

 Reply

satish on September 19, 2014 at 10:56 am

Hi — Here 40 kw load 3 ph 415 v and length is 1 km so kindly suggest me which size of aluminum
cable to be laid in ground

 Reply

Virendra Singh on September 20, 2014 at 1:24 am

Hello, what 33 KV cable size should I select for a 2000 KW Load on LT side. Transformer is 2.5 MVA,
33/0.433 KV.

 Reply

sunil kumar on November 9, 2014 at 6:54 am

बहुत अछछी जानकारी िमली।

 Reply

Engineer Habeeb on December 9, 2014 at 12:32 pm

You are such a wonderful Engineer, for the great opportunity you have given to people

 Reply

nishantsharma111 on December 22, 2014 at 10:00 am

UR NOTES IS SUCH WONDERFULL THANK U SO MUCH…

 Reply

Swapnil Mohite on December 24, 2014 at 1:16 pm

Dear Sir,

will you please suggest me from which website i can download Excel Base Program to Calculate LT-MV-
HT Cable from Electrical tools.

 Reply

venkatesh on December 25, 2014 at 4:25 pm

Sir Thanks For your Valuble Information,I want know the Formula for To Measure Current For Any cable
Ex:1x16sq.mm,3x4sqmm,3×16 sqmm

 Reply

Jamshed on January 5, 2015 at 7:49 am

Sir Thanks For your Valuble Information,I want know the Formula for To Measure Current For Any cable
Ex:1x16sq.mm,3x4sqmm,3×16 sqmm

 Reply

SARTHAK on January 9, 2015 at 9:21 am

CAN YOU TELL ME WHEN WE TAKE A 51MM COOPER CABLE THEN THIS COOPER CABLE HOW
MUCH TAKE A LOAD IN HP

 Reply

ali on February 9, 2015 at 10:23 am

please can you tell me if total load is 140 Amp and length is 250 Meter. how much XLPE cable size and
how much voltage drop. how i can calculate.

 Reply

Siddhartha on February 16, 2015 at 7:57 am

please advice which minimum width of 3 core xlpe cable should used for 7 KM long transmission with
connected load of 3000

 Reply

RAM on February 17, 2015 at 5:59 pm

Sir
How much load can be layed on 1 kv line. Please give kv and load relation.

 Reply

sanjay on February 21, 2015 at 7:18 pm

Sir
what’s the advantage of using 4 core cable over 3.5 core cable ? And then, what chang
Powar pf 1

 Reply

Suresh on March 15, 2015 at 6:15 am

sir,
Detail of Transformer primary & secondary testing please said me

 Reply

Obk. on March 16, 2015 at 9:58 am

Hello Sir.
Can a 4C 150mm armoured cable sustain 595A or a total power of 398Kva? If not, what cable size
would be ideal? I seek for expert advice. Thanks.

 Reply

Karan on March 24, 2015 at 2:45 am

Very good can I get this document through mail


It’s very useful for me

 Reply

Mohammad ladlay on March 26, 2015 at 6:09 am

Thank you for this cable selection chart.


Thank u verymuch.

 Reply

mike on March 27, 2015 at 7:24 am

sir can you help me to size the cables for 5000A,3Phase,415Volts and the size of the cables for
2500KVA,415V, 3Phase diesel generator please help me for this

 Reply

Ansh on March 30, 2015 at 5:36 pm

hello Sir,
I’m Ansh from lucknow , i wanted to know when cable insulation test carried out on one end R-N other
end of cables R-N are shorted or not & why….???

 Reply

chauhan Devnarayan on April 2, 2015 at 6:52 am


Sir i
i want to know how to select copper and aluminium busar on current capacity

 Reply

shibu on April 22, 2015 at 7:27 am

Hai
can you please tell me how to make the GRC-Group rating cables,
Regards
Shibu

 Reply

Harekrishna Parida on April 23, 2015 at 5:16 am

Dear Sir,
Kindly share What is the standard parameters to be maintained daily in a transformer for both dry type
and oil type & What is dielectric strength?

 Reply

Vishal Jayprakash Mistry on April 24, 2015 at 3:01 pm

Respected Sir, Thanks For Supporting For Electrical Engineer


Sir i have Question to you sir
Can you give suitable CU. & Al. Cable Size of different rating starter like DOL & Stardelta Starter from
above cable chart.

 Reply

SEBIN on April 27, 2015 at 4:49 am

Dear sir,
i want to know will there be any change inside the conductor when the cable inssulation viltage is
.4/.6kV…

 Reply

Kanchan on April 29, 2015 at 12:25 pm

Dear Sir,
Thanks for the useful chart… can u please guide me if these ratings are available in some standard or u
have calculated the same using IEC 60287.
Regards

 Reply

Abhishek Kumar on May 2, 2015 at 3:06 pm


Dear sir,
Kindly give me how to test six nos of leads of motors to connect in delta.No identification.

 Reply

jayakumar on May 9, 2015 at 6:19 am

Dear sir,
how to messring of current rate of contecter or cables

 Reply

manjunath patil on May 17, 2015 at 9:12 am

tell me the standard formula to calculate current carrying capacity of cable

 Reply

John Lima on May 23, 2015 at 4:04 pm

Sir,
I require 4 core. rubberised cable for 200 HP 3phase motor 380/460 volts 226 amps if possible starter
details.

Regards.
John

 Reply

J Prasad on May 26, 2015 at 4:03 pm

KINDLY SEND ME 33KV XLPE CABLE Current Rating Equivalent to Dog & panther conductor

 Reply

NILABJA BHATTACHARYA on June 1, 2015 at 12:09 pm

Hello Sir,

Please tell me how to calculate the voltage drop of a 4C, 25 Sq. mm. Armoured Aluminium XLPE 1.1kv
rating cable for 80M length having current rating of 200A.

If possible please involve the calculation also in reply.

 Reply

omar on June 2, 2015 at 8:39 am

kindly if I need underground cable I will consider current carrying from above table & proceed or should
be multiply with derating factors also . ??? can you help me.
our site condition :-

ground temp. 35C >>>> factor = 0.89 as per IEC standard tables .
grouping factor >>>>>> 0.75 as per IEC standard tables .
depth laying factor >>>> 1.0 as per IEC standard tables .
soil thermal resistivity factor >>>> 1.17 as per IEC standard tables .

 Reply

Sivakumar on June 7, 2015 at 1:32 pm

Super

 Reply

Sivakumar on June 7, 2015 at 1:36 pm

Pls send me the LT &HT cable amps rating

 Reply

Sivakumar on June 8, 2015 at 5:03 am

Electrical notes are good. Pls send the transformer yard drawings

 Reply

Faizur Rehman on June 9, 2015 at 7:36 am

hI,
Main Cut-Out: 250 Amps
3 – Phases

Red : 163 Amps Incoming Main Load from Qatar Govt. is 105 KW
Yellow : 156 Amps Cable size 95 mm²
Blue : 105 Amps

Please let me know the Total Existing Load and alos tell me remedy to tripping off Problem.

 Reply

Rajesh on June 16, 2015 at 7:10 am

Its very useful data. Highly appreciate you efforts. Thanks

 Reply

gouse on July 12, 2015 at 6:00 am

Sir 3*400sqmm ug cable is laid in trench but cable termination is getting heating tell me reason
 Reply

vanrajsinh on July 30, 2015 at 9:43 am

Dear sir u help me to amp to cable size formula & table send me my email id

 Reply

venkatesh on August 3, 2015 at 11:07 am

Sir
thanks for info
can u provide any data regarding voltage drop by its length

 Reply

azad on August 5, 2015 at 8:58 am

Either the termination is lose or the connected load is more than your estimated load

 Reply

Edwin Iraola on August 18, 2015 at 10:12 am

SIr,

Can you help about how much the maximum outer diameter of can cable can be run in 50 mm 110 mm
160 mm 250 mm dia duct

Thank you

 Reply

Pingback: Quora

Jesper Moeller on September 25, 2015 at 9:11 am

Sir, why cant I find a Multi core cable 3.5 x 240 mm2 ?

 Reply

K Soma Sekhar on October 17, 2015 at 4:14 am

For 140A load (Gas Analyser Heat Tracing System), 3cx150 sq mm 1.1kV Armoured Aluminium cable
shall be sufficient?? Cable to be laid in Air.

 Reply

vineet kumar vishwakarma on November 21, 2015 at 2:05 pm


can you tell me , the size of fuse wire which can be used in 25 kva 3 phase distribution transformer
11/.4kv

 Reply

prabu on December 7, 2015 at 2:37 am

dear sir,

how to calculate the maximum output amps for 4c x 240sqmm size?

 Reply

Siva Prasad K on December 22, 2015 at 9:28 am

can anyone pls help me by sending the current carrying capacity of 3.5×35 Sq.mm aluminium cable ?

 Reply

R K Patel on December 26, 2015 at 10:07 am

Sir, request you to please send excel based calculation sheet for selection

 Reply

kandavel on January 2, 2016 at 8:45 am

Dear Sir
I would like to know the amperes details of 1c,600 SQMM COPPER CABLE…

 Reply

ramjas on January 6, 2016 at 11:47 am

Dear sir ,

cable more type example armored , unarmored , flexible , how calculate running meter weight.
have any formula.

 Reply

ramjas on January 6, 2016 at 11:54 am

Dear sir ,

We have more type cable , armored , unarmored,flexible,instrumentation.


how calculate running mtr weight.
you have any formula.

 Reply
Prashant Jadhav on January 13, 2016 at 8:58 am

Dear sir,

We have got new project. please let us know which cable use to 200KV UPS input

 Reply

rk on February 8, 2016 at 3:00 pm

give details as below..

which size of cables are use in underground network ?


Total load is 200kw

as early as possible

thanks

 Reply

M.B.Parthasarathy on February 13, 2016 at 10:33 am

Why do electricity board keep R N Y B phase wiring in street post and not in R Y B N in order?

 Reply

Junad ur Rehman on February 17, 2016 at 5:30 am

Sir..!
Can you tell me the cable size in mm..
If i have to pass 500 amps of normal current and a surges of 100 amps could come to it..
Voltage is 440 V .
Cable length i need is 100 feet 1 side (single core) .

 Reply

hari on February 21, 2016 at 4:32 pm

please provide the cable sizing for 1000kva DG set…we got information that -4 run of 240 sq mm cable
,single core for each phase is required.Is it like that?why?what is the calculation?

 Reply

AJU on March 1, 2016 at 6:00 am

Sir,

How will calculate the cable size if load A and distance between load and source are known?

 Reply
sanjeev dhiman on April 26, 2016 at 9:19 am

sir plz define. cable size increses current also increase in small dia cables but when dia increase but
current not increase with dia . define this

 Reply

Navin on April 28, 2016 at 3:55 am

Dear Sir kindly help in cable selection on AC side for a solar roof top system.
1).10kw pv system for a two floried villa

2).30 kw pv system for a 12 floried apartment.


Both the above cases ACDB is mounted on the roof.

Also please send me the cable selection chart…

 Reply

Arunpuri on May 11, 2016 at 6:22 am

Thanks!!

 Reply

Maulik on June 8, 2016 at 12:53 pm

Sir,

We have wrongly purchased 3 core x 300 sq mm Aluminium armoured cable for main Incomer. What will
be the solution to convert this cable in 3.5 Core x 300 Sq mm cable. Please help.

 Reply

shiva s. h. on July 1, 2016 at 1:48 pm

sir, for 690 volt vfd application motor is it suitable for 1.1kv xlp cable or shall we required any special
cable

 Reply

rakesh_19781978@rediffmail.com on July 30, 2016 at 8:05 am

sir,
Please tell me if 2x3x400 sqmm XLPE cable maximum current carrying capacity will be same for
11kv,33kv and 66kv voltage level?
What is the maximum current carrying capacity?

 Reply
rakesh_19781978@rediffmail.com on July 30, 2016 at 8:41 am

sir,
Please tell me if 2x3x400 sqmm XLPE cable maximum current carrying capacity is same for
11KV,33KV,66KV?
what is the max current carrying capacity for 4km cable?

 Reply

anil on August 10, 2016 at 8:39 am

Thanks for providing such a list.


May I know the actual difference between LT & HT?
And what is the standard of choosing the LT power cable?

 Reply

Mohd Ahmad on August 20, 2016 at 5:42 am

thanks for its

 Reply

Nitesh on August 22, 2016 at 4:21 am

10sqmm×4core xlpe ug cable is ideal for a three floor building with total capacity of 15kilowatt?

 Reply

Chris on September 11, 2016 at 12:41 pm

This is very informative. Please let me also have table for xlpe cable ratings at 11kv.

 Reply

Sushil on October 24, 2016 at 6:31 am

In Your Electrical notes ( Rev 5,page 10), Thumb rule for cable current capacity says 4 times of cable
size, 4 x 2.5 sq.mm = 9Amp. If I am not wrong then 2.5sq.mm can carry approx 22Amp
Can you please explain the basis of this thumb rule?

 Reply

sukdeb chakraborty on January 4, 2017 at 10:45 am

I need cable glend size chart as per cable size


Thank you

 Reply
kishorv1kishor on February 1, 2017 at 7:38 am

Dear sir.
I am working as Sr. section Engineer in Western Railway zone of Indian Railway.I have to scrutinise
technically all material for traction distribution(Electrical branch) which is purchased by Railway.During
Technically scrutiny I am facing a problem regarding type test certificate provided by firm for IS 7098
part II(2011)or part-I(1988).How can I considered category of cable i.e. 01, C1 or C2

 Reply

papadopoulos Thanasis on February 18, 2017 at 5:26 am

please I want to know what cable diameter I can use for one motor 450 volt 3 ph 60 hz 237 A in one
distance 295 meter , the cable passing from pipe with other cable together.

Thanks

 Reply

Md. Keafayet Ullah on April 18, 2017 at 6:33 pm

How can I use cable size for 440 kW load? Please suggest Me?

 Reply

NIDHI BHUSHAN on May 2, 2017 at 12:12 pm

how to select HT cables ?

 Reply

Ravikant Goswami on May 4, 2017 at 4:33 am

2R*3.5C*240sqmm XLPE, Aluminium cable current carriynig capacity for 630Amp Incomer Feeder
panel?

 Reply

hemant kumar on May 6, 2017 at 11:20 am

please i want to note chemical electrical earthing and were use & its advantages anther earthing system ,
how many cost of instalation of one chemical earthing

 Reply

Rajesh Thapa on May 17, 2017 at 2:13 pm

Can any one tell / explain the purpose of using 1.0 kV grade and 1.1 kV grade rating of PVC/XLPE
insulated cable for low voltage since I am confused with it as some says 1.0 kV n some 1.1 kV. Logically
how do we calculate? or it is differ from country to country?
 Reply

Bornfree Kalunga on June 3, 2017 at 9:02 pm

Kindly send me these charts for cable selection , i will highly appreciate.

 Reply

Bornfree Kalunga on June 3, 2017 at 9:11 pm

Kindly send me the charts for the cable selection, i will highly appreciate.

 Reply

floyd on June 15, 2017 at 6:33 am

Hi Jignesh, I’d like to ask for your permission to reproduce two of your Tables in my blog as I’d need
them for my personal quick reference. Am currently working on a cable installation for a raw water pump.
Thanks in advance.

 Reply

Gautam Ramdas on September 26, 2017 at 8:00 am

Hi Sir,
I want cable joint selection chart because I check its different catalogue number for every manufacturer,
so is there any standard chart for it. Please if you have send me on my email id.
Thank you!

 Reply

Lennox on September 26, 2017 at 2:48 pm

Very well detailed would like to have reference to a chart when paralleling cables

 Reply

Madhukarreddy on October 6, 2017 at 5:12 pm

Good massage

 Reply

Hamsananthan on November 26, 2017 at 6:56 am

What is Laminar insulation on Medium voltage cables, loss on Laminar insulation

 Reply
Pingback: Diameter of 1100 Volts Grade XLPE, Insulated Cable (IS-7098- Part- I)

Sachin on December 12, 2017 at 7:09 am

16sqmm 1100v aluminum armored xlpe cable mai.kitna hp ka motor lode de .

 Reply

Brijesh kumar on February 25, 2018 at 12:23 am

Sir,
For 100 amp load and 150 MTR distance . Single phase .. how many sq mm copper cable required..

 Reply

harsh panchal on March 10, 2018 at 5:52 am

Thank you so much sir your information is very useful..

 Reply

Eng. Abdolgabar Ahmed Mahmood on April 15, 2018 at 9:40 am

Dear Sir .
Please send me the cable size selection chart for Low voltage & Medium voltage(pdf). I will be very great
full to you.
Regards.
Eng. Abdolgabar Ahmed

 Reply

Bishnu Chapagai on May 24, 2018 at 9:17 am

We have 2200 kVA 11/0.415 kV transformer. What would be the proper cable size at 11 kV Side ? is it
simply by current rating or we need to take 2 to 3 times..plz clarify..

 Reply

vishal on August 18, 2018 at 9:02 am

hello,
am planning to set up a factory where i will need load for my machines upto 130 hp. can some one
suggest what copper armour cable should be used??

 Reply

Shubham mishra on April 21, 2019 at 1:04 pm

Good evening sir,


Will you please send the 1.1kv 3core armoured xlpe cable current rating and. Is there any thumb
rule(genral way) for calculating the current capacity (approximate) of the cable at site.(xlpe/pvc/pilca,
1c/2c/3c/3.5c/4c, copper/aluminum).

 Reply

Shashi Vaidya on July 14, 2019 at 6:55 am

hello

can you guide Multi core cable Raw material calculation formula

 Reply

Akinbode Josiah on January 15, 2020 at 12:09 pm

Sir, please what is load capacity can 11kv aluminium xlpe power cable can carry

 Reply

SAMIR PRIYAVADAN on September 11, 2020 at 3:30 pm

Sir I have confused all time in 0ne terms in 3.5*C in any cable amp rating are given per phase

 Reply

dharmesh sapra on February 3, 2021 at 10:55 am

hi
How to calculate derating factor. Give its formula

 Reply

Jignesh.Parmar (B.E,Mtech,MIE,FIE,CEng)

Blog Stats

18,503,912 hits

About Jignesh Parmar:

Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical). He is FIE ,MIE and CEng from
Institution of Engineers,India. Membership No:F-1264873 ,M-1473586.He has more than 19 years experience in
Transmission -Distribution-Electrical Energy theft detection-Electrical Maintenance-Electrical Projects (Planning-
Designing-Technical Review-coordination -Execution). He is Presently associate with one of the leading business
group as a Deputy Manager at Ahmedabad,India. He has published numbers of Technical Articles in “Electrical
Mirror”, “Electrical India”, “Lighting India”,”Smart Energy”, “Industrial Electrix”(Australian Power Publications)
Magazines. He is Freelancer Programmer of Advance Excel and design useful Excel base Electrical Programs as per
IS, NEC, IEC,IEEE codes. He is Technical Blogger and Familiar with English, Hindi, Gujarati, French languages. He
wants to Share his experience & Knowledge and help technical enthusiasts to find suitable solutions and updating
themselves on various Engineering Topics.

Follow Blog via Email

Enter your email address to follow this blog and receive notifications of new posts by email.

Join 12,612 other followers

Enter your email address

Follow This Blog by Email

BUY ELECTRICAL NOTES IN PDF

BUY ELECTRICAL SOFTWARES

BUY ELECTRICAL NOTE IN PDF

BUY ELECTRICAL SOFTWARES.


Proud to be an IndiBlogger
electricalnotes.wordpress.c...

85 /100

Search

Copyright © 2018

The content in electricalnotes.wordpress.com is for personal, non-commercial use only. you can not
reproduce,republish or communicate any of the content , including files downloadable from this website, without the
permission of the copyright owner.The use of this content on any other websites breaches copyright Act. If You find
this content in any other site,it makes the page you are viewing an infringement of the copyright.

Recent Posts

Measurement of LUX Level and Uniformity at Indoor and Outdoor Lighting


Typical Earthing Resistance Value
Difference between Fault Current and Short Circuit Current
Method for Installation of Conceal & Surface Conduits (Part-2)
Method for Installation of Conceal & Surface Conduits (Part-1)
Quick Reference-Fire Fighting (Part-3)
Method for Wrapping Coating & Holiday Test for Fire Fighting Pipe
Method of Statement for Fire Fighting Works (Part-2)
Method of Statement for Fire Fighting Works (Part-1)
Method for Installation of DB or Panel-(Part-2)
Method for Installation of DB or Panel-(Part-1)
Quick Reference -Earthing
Method for Installation of Cable Tray-(PART 2)
Method for Installation of Cable Tray-(PART 1)
Method for Installation of HVAC System (Part-4)
Method for Installation of HVAC System (Part-3)
Method for Installation of HVAC System (Part-2)
Method for Installation of HVAC System (Part-1)
Method for Installation of Cable & Wire (Part-2)
Method for Installation of Cable & Wire (Part-1)

Archives
November 2021 (1)
October 2021 (2)
September 2021 (2)
August 2021 (2)
July 2021 (1)
June 2021 (2)
May 2021 (1)
April 2021 (2)
March 2021 (2)
February 2021 (2)
January 2021 (2)
December 2020 (1)
November 2020 (1)
October 2020 (2)
September 2020 (1)
August 2020 (2)
July 2020 (2)
June 2020 (2)
May 2020 (2)
April 2020 (2)
March 2020 (2)
February 2020 (2)
January 2020 (1)
December 2019 (1)
November 2019 (1)
October 2019 (2)
September 2019 (2)
August 2019 (2)
July 2019 (2)
June 2019 (1)
May 2019 (2)
April 2019 (3)
March 2019 (2)
February 2019 (2)
January 2019 (3)
December 2018 (2)
November 2018 (2)
October 2018 (1)
September 2018 (2)
August 2018 (3)
July 2018 (1)
June 2018 (1)
May 2018 (1)
April 2018 (1)
March 2018 (1)
February 2018 (2)
January 2018 (1)
December 2017 (1)
November 2017 (1)
October 2017 (1)
September 2017 (1)
August 2017 (1)
July 2017 (2)
June 2017 (1)
May 2017 (1)
April 2017 (1)
March 2017 (1)
February 2017 (1)
January 2017 (1)
December 2016 (1)
November 2016 (1)
October 2016 (1)
September 2016 (1)
August 2016 (1)
July 2016 (1)
June 2016 (1)
May 2016 (1)
April 2016 (2)
March 2016 (2)
February 2016 (2)
January 2016 (2)
December 2015 (1)
November 2015 (1)
October 2015 (2)
September 2015 (1)
August 2015 (1)
July 2015 (1)
June 2015 (1)
May 2015 (1)
April 2015 (1)
March 2015 (2)
February 2015 (2)
January 2015 (2)
December 2014 (2)
November 2014 (2)
October 2014 (2)
September 2014 (2)
August 2014 (3)
July 2014 (2)
June 2014 (2)
May 2014 (2)
April 2014 (2)
March 2014 (3)
February 2014 (4)
January 2014 (2)
December 2013 (1)
November 2013 (1)
October 2013 (2)
September 2013 (3)
August 2013 (3)
July 2013 (3)
June 2013 (3)
May 2013 (3)
April 2013 (2)
March 2013 (3)
February 2013 (2)
January 2013 (3)
December 2012 (2)
November 2012 (3)
October 2012 (1)
September 2012 (3)
August 2012 (7)
July 2012 (2)
May 2012 (7)
April 2012 (2)
March 2012 (3)
February 2012 (2)
January 2012 (1)
December 2011 (3)
November 2011 (2)
October 2011 (4)
September 2011 (2)
August 2011 (1)
June 2011 (5)
May 2011 (3)
April 2011 (12)
March 2011 (17)

EEP

Pages

Electrical Calculation
Electrical Notes
Electrical. Q&A
Electrical Q&A Part-1
Electrical Q&A Part-2
Electrical Q&A Part-3
Electrical Q&A Part-4
Electrical.Tools

Top Clicks

instamojo.com/jiguparmar/…
electricalnotes.files.wor…
mediafire.com/file/5040ut…
electricalnotes.files.wor…
gumroad.com/l/inOq
mediafire.com/file/91cpju…
mediafire.com/file/76blr8…
mediafire.com/file/0qu8mt…
electricalnotes.files.wor…
electricalnotes.files.wor…

Recent Comments

shreelekha sahu on Various Factors for Illuminati…


Sumesh V on Quick Reference-Fire Fighting…
piyal on Calculate Numbers of Plate/Pip…
Bhawani Singh on Method of Statement for Fire F…
angelito Cortez on Method for Installation of Cab…
Pradeep Maheta on Method for Installation of DB…
Hemant Sali on Minimum Electrical Clearance.
Muhammad Mohsin Ansa… on Method for Installation of Cab…
Md.Moniruzzaman Khan on Calculate IDMT over Current Re…
Vijay N on Electrical Useful Equations

View Full Site

Close and accept Privacy & Cookies: This site uses cookies. By continuing to use this website, you agree to their
use.
To find out more, including how to control cookies, see here: Cookie Policy

You might also like