The c.s.a. of the circuit protective conductor (c.p.c.) is of great importance since
the level of possible shock in the event of a fault depends on it (as seen in {5.4.4}).
chapter 7
Safety could always be assured if we assessed the size using {Table 5.7} as a basis.
Special Installations
However, this would result in a more expensive installation than necessary because we would often use protective conductors which are larger than those found
to be acceptable by calculation. For example. twin with cpc insulated and sheathed cables larger than 1 mm² would be ruled out because in all other sizes the
CPC is smaller than required by {Table 5.7}.
chapter 8
In very many cases, calculation of the CPC size will show that a smaller size than that detailed in {5.4.4} is perfectly adequate. The formula to be used is:
Testing
S= Ö(Ia²t)
and
k
Inspection
whereS is the minimum protective conductor cross-sectional area (mm2)
chapter 9
Ia is the fault current (A)
Data cabling
k is a factor depending on the conductor material and insulation, and the initial and maximum insulation temperatures.
This is the same formula as in {3.7.3}, the adiabatic equation, but with a change in the subject. To use it, we need to have three pieces of information, Ia, t and k.
1) To find Ia
Contents
We can find t from the time/current characteristics of {Figs 3.13 to 3.19} using the value of Ia already calculated above. For example, if the protective device is a 20
A miniature circuit breaker type I and the fault current is 1000 A, we shall need to consult {Fig 3.16}, when we can read off that operation will be in 0.01 s (10 ms).
(It is of interest here to notice that if the fault current had been 80 A the opening time could have been anything from 0.04 s to 20 s,so the circuit would not have
complied with the required opening times).
3) To find k
k is a constant, which we cannot calculate but must obtain from a suitable table of values. Some values of k for typical protective conductors are given in {Table
5.8}.
It is worth pointing out here that correctly installed steel conduit and trunking will always meet the requirements of the Regulations in terms of protective
conductor impedance.
Although appearing a little complicated, calculation of acceptable protective conductor size is worth the trouble because it often allows smaller sizes than those
shown in {Table 5.7}.
Initial temp.
Final temp
Conductor
- 30 160 Aluminium 95
- 30 160 Steel 52
- 70 160 Aluminium 76
https://www.tlc-direct.co.uk/Book/5.4.5.htm 1/3
8/25/2021 TLC Electrical Supplies
- 30 200 Steel 58
Example 5.2
A load takes 30 A from a 240 V single phase supply and is protected by a 32 A HBC fuse to BS 88. The wiring consists of 4 mm² single core p.v.c. insulated cables
run in trunking, the length of run being 18 m. The earth-fault loop impedance external to the installation is assessed as 0.7 Ohms. Calculate the cross-sectional
area of a suitable p.v.c. sheathed protective conductor.
This is one of those cases where we need to make an assumption of the answer to the problem before we can solve it. Assume that a 2.5 mm² protective
conductor will be acceptable and calculate the combined resistance of the phase and protective conductors from the origin of the installation to the end of the
circuit. From {Table 5.5}, 2.5 mm² cable has a resistance of 7.4 mohms/m and 4 mm² a resistance of 4.6 mOhms/m. Both values must be multiplied by 1.2 to allow
for increased resistance as temperature rises due to fault current.
Thus, R1 + R2 = (7.4 + 4.6) x 1.2 x 18 Ohms = 12.0 x 1.2 x 18 = 0.26 Ohms
1000 1000
This conductor resistance must be added to external loop impedance to give the total earth-fault loop impedance.
Zs = Ze + Rl + R2 = 0.7+ 0.26 Ohms = 0.96 Ohms
We can now calculate the fault current:
la = Uo = 240 = 250A
Zs 0.96
Next we need to find the operating time for a 32 A BS 88 fuse carrying 250 A. Examination of {Fig 3.15} shows that operation will take place after 0.2 s.
Finally, we need a value for k. From {Table 5.8} we can read this off as 115, because the protective conductor will be bunched with others in the trunking.
We now have values for Ia, t and k so we can calculate conductor size.
S= Ö(Ia²t) = Ö(250² x 0.02) mm² = 0.97 mm²
k 115
This result suggests that a 1.0 mm² protective conductor will suffice. However, it may he dangerous to make this assumption because the whole calculation has
been based on the resistance of a 2.5 mm² conductor. Let us start again assuming a 1.5 mm² protective conductor and work the whole thing through again.
The new size protective conductor has a resistance of 18.1 mOhms/m, see {Table 5.5}, and with the 4 mm² phase conductor gives a total conductor resistance,
allowing for increased temperature, of 0.491 Ohms. When added to external loop impedance this gives a total earth-fault loop impedance of 1.191 Ohms and a
fault current at 240 V of 202 A. From {Fig 3.15} operating time will be 0.6 s. The value of k will be unchanged at 115.
S= Ö(Ia²t) = Ö(202² x 0.6) mm² = 1.36 mm²
k 115
Thus, a 1.5 mm² protective conductor can be used in this case. Note that if the size had been assessed rather than calculated, the required size would be 4 mm²,
two sizes larger. A point to notice here is that the disconnection time with a 1.5mm² protective conductor is 0.6 s, which is too long for socket outlet circuits (0.4 s
max.).
Example 5.3
A 240 V, 30 A ring circuit for socket outlets is 45 m long and is to be wired in 2.5 mm² flat twin p.v.c. insulated and sheathed cable incorporating a 1.5 mm² cpc.
The circuit is to be protected by a semi-enclosed (rewirable) fuse to BS 3036, and the earth-fault loop impedance external to the installation has been ascertained
to be 0.3 Ohms. Verify that the 1.5 mm² cpc enclosed in the sheath is adequate.
First use {Table 5.5} to find the resistance of the phase and cpc conductors. These are 7.4 mOhms/m and 12.1 mOhms/m respectively, so for a 45 m length and
allowing for the resistance increase with temperature factor of 1.2.
R1 + R2 = (7.4 + 12.1) x 1.2 x 45 Ohms = 19.5 x 1.2 x 45 Ohms = 1.05 Ohms
1000 1000
A 240 V single-phase circuit is to be wired in p.v.c. insulated single core cables enclosed in plastic conduit. The circuit length is 45 m and the live conductors are
16 mm² in cross-sectional area. The circuit will supply fixed equipment, and is to be protected by a 63 A HBC fuse to BS 88. The earth-fault loop impedance
external to the installation has been ascertained to be 0.58 Ohms. Calculate a suitable size for the circuit protective conductor.
With the information given this time the approach is somewhat different. We know that the maximum disconnection time for fixed equipment is 5 s, so from the
time/current characteristic for the 63 A fuse {Fig 3.15} we can see that the fault current for disconnection will have a minimum value of 280 A.
Thus, Zs = Uo = 240 Ohms = 0.857 Ohms
Ia 280
If we deduct the external loop impedance, we come to the resistance of phase and protective conductors.
R1 +R2 = Zs-Ze = 0.857-0.58Ohms = 0.277 Ohms
Converting this resistance to the combined value of R1 and R2 per metre,
(R1 + R2) per metre = 0.277 x 1000 mOhms/m = 5.13 mOhms/m
45 x 1.2
Consulting {Table 5.5} we find that the resistance of 16 mm² copper conductor is 1.15 mOhms/m, whilst 10 mm² and 6 mm² are 1.83 and 3.08 mOhms/m
respectively. Since 1.15 and 3.08 add to 4.23, which is less than 5.13, it would seem that a 6 mm² protective conductor will be large enough. However, to be sure
we must check with the adiabatic equation.
R1 + R2 = (1.15+3.08) x 1.2 x 45 Ohms = 0.228 Ohms
1000
Ia = Uo = 240 A = 297 A
Zs 0.808
https://www.tlc-direct.co.uk/Book/5.4.5.htm 2/3
8/25/2021 TLC Electrical Supplies
From {Fig 3.15} the disconnection time for a 63 A fuse carrying 297 A is found to he 3.8s.
by John Whitfield