Professional Documents
Culture Documents
FPD17-R1
INSTALLATION MANUAL
ᵲᶆᶇᶑᴾᶋᵿᶌᶓᵿᶊᴾᶇᶑᴾᶄᶍᶐᴾᶎᶐᶍᶄᶃᶑᶑᶇᶍᶌᵿᶊᴾᶑᶃᶐᶔᶇᶁᶃᴾᶃᶌᶅᶇᶌᶃᶃᶐᶑᵌᴾ
ᵧᶒᴾᶀᶃᵿᶐᶑᴾᶌᶍᴾᶐᶃᶊᵿᶒᶇᶍᶌᴾᶒᶍᴾᶒᶆᶃᴾᶓᶑᶓᵿᶊᴾᶍᶎᶃᶐᵿᶒᶇᶍᶌᵌᴾ
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷
WARNING
Please execute work according to the instruction of this manual when
installing and serving.
Safety is the one achieved because of the attention of the worker
individual. Please work according to the safety work standard to
secure the safety of a worker and surrounding people.
Because the repair in the product is dangerous, the person who takes
special training in our company does.
The precautions and prohibitions seen through the manual are classified as
follows:
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷
z GUARANTEE
The guarantee period of this system is one year from the date of purchase. Our
company is not responsible for the following failures and damages.
The servicing after expiration of the guarantee period will be charged. Contact our service
agency nearest to you.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷
Contents
1 Introduction .................................................................................................... 䋱
4 Connection ................................................................................................... 14
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 i
4-5 Connection between Components to PSU and Combination Devices......... 23
4-5-1 Connection on PCU ................................................................................................... 23
4-5-2 Connection on MPC................................................................................................... 24
4-5-3 Connection on Connector7 ........................................................................................ 25
4-5-4 Connection on SwitchingHUB ................................................................................... 26
4-5-5 Connection on DC/HV POWER SUPPLY ................................................................. 27
4-5-6 Connection on GRID CONT ...................................................................................... 28
4-5-7 Connection on FPD COOLING UNIT ........................................................................ 31
4-5-8 FPD............................................................................................................................ 33
4-5-9 DR Console ............................................................................................................... 38
4-5-10 Thermo Meter ............................................................................................................ 39
4-5-11 PSU POWER SUPPLY.............................................................................................. 39
7 Setting PCU................................................................................................... 46
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 ii
8-2 Connection of Thermometer............................................................................62
8-2-1 Parts and Operations................................................................................................. 62
8-2-2 Connection and Installation ....................................................................................... 63
8-2-3 Setting and Operation Check .................................................................................... 64
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 iii
1 Introduction
This manual provides the explanations, methods and precautions as to the installation of
FPD17-R1 and wiring of it.
Before installing the system, read this manual thoroughly in order to operate the system
without the trouble.
In this manual, we use the following abbreviations for explanation.
Abbreviation Definition
PCU Panel Control Unit
PSU Power Supply Unit
MPC Maintenance PC (Remote maintenance PC)
FPD Flat Panel Detector
CIF Console Interface Software
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 䋱/93
1-2 Workflow
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 䋲/93
2 Installation Conditions
2-1 Environment
FPD should be used under the following environmental conditions.
Set the exclusive air-conditioning system in the examination room to meet the environmental
condition by the 24-hour air-conditioning system.
For the cable wiring, prepare the enough size pit which corresponds to the system.
Storage
Device Specified Requirement
Environment
1. Keep in the designated box, use it for
Temperature: transporting.
2. Convey this system under the following
+15° - +30°
FPD condition (This product may be damaged
Humidity: in the environment that is not under the
following conditions).
15% - 75 %
3. Put 100g of desiccant (dry C) into the
sealed package for transporting abroad.
Temperature:
FPD17-R1 -10°- +60°
(Excluding FPD) Humidity:
10%- 95%
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 3/93
3 Installing Units
3-1 Component List
FPD17-R1 system has 2 types of FPDs as “Chart 3-1 FPD17-R1 components”.
One is 1FPD (Stand system or table system) including FPD1, and the other is 2FPD (Stand
and table system) including FPD2.
The FPD17-R1 is operated with the systems in “Chart 3-2 FPD17-R1 combination devices”.
(2& ٤ ٤ BR-120F/FT
(2& ٤ ٤ BK-120F
/2% ٤ ٤ ٤ MPC
GRID controller
٤ ٤
)4+&%106 $4 for BR
(BR)
DC/HV POWER SUPPLY
(BK)
FPD COOLING UNIT
٤ ٤ ٤
FPD COOLING UNIT
%QPPGEVQT ٤ ٤ ٤ Connector7
Switching HUB
٤ ٤ ٤
5YKVEJKPI*7$
PSU
TRANS UNIT ٤ ٤ ٤
POWER SUPPLY
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 4/93
Chart 3-2 FPD17-R1 combination devices
2FPDs
1FPD 1FPD
Componen system
system system Description Remarks
t (STAND &
(STAND) (TABLE)
TABLE)
٤ ٤ BR-120F/FT X-ray radiography stand
$4((6
5# ٤ ٤ ٤ SA-60
٤ ٤ ٤ UD150B-40
Control cabinet
7&$ ٤ ٤ ٤ UD150B-40
operation panel
٤ ٤ ٤ Tower PC
DR console PC
㧔Included keyboard and mouse㧕
DR console
٤ ٤ ٤ Monitor Monitor with touch-panel
㪜㫏㪸㫄㫀㫅㪸㫋㫀㫆㫅㩷㪩㫆㫆㫄
㩿㪈㪋㪀㪚㪟㪄㪉㪇㪇
㪧㪪㪬
㩿㪈㪀㪝㪧㪛㩿㪪㫋㪸㫅㪻㪀
㩿㪈㪐㪀㪪㪘㪄㪍㪇
㩿㪉㪇㪀
㪬㪛㪈㪌㪇㪙㪄㪋㪇
㩿㪉㪀㪝㪧㪛㩿㪫㪸㪹㫃㪼㪀 㩿㪈㪌㪀
㪚㪟㪄㪉㪇㪇
㪚㫆㫅㫋㫉㫆㫃㩷㫌㫅㫀㫋
㩿㪈㪏㪀
㩿㪈㪍㪀㪙㪩㪄㪈㪉㪇㪝㪆㪝㪫 㩿㪈㪎㪀㪙㪢㪄㪈㪉㪇㪝 㪙㪢㪄㪈㪉㪇㪝
㪚㫆㫅㫋㫉㫆㫃㩷㫌㫅㫀㫋
㪪㫆㫃㫀㪻㩷㫃㫀㫅㪼䋺㪝㪧㪛㪈㪎㪄㪩㪈㩷㫊㫐㫊㫋㪼㫄㩷㫌㫅㫀㫋㫊
㪛㪸㫊㪿㪼㪻㩷㫃㫃㫀㫅㪼䋺㪝㪧㪛㪈㪎㪄㪩㪈㩷㪺㫆㫄㪹㫀㫅㪸㫋㫀㫆㫅㩷㪻㪼㫍㫀㪺㪼㫊
㪚㫆㫅㫋㫉㫆㫃㩷㪩㫆㫆㫄
㩿㪉㪈㪀㪬㪛㪈㪌㪇㪙㪄㪋㪇㩷㪺㫆㫅㫋㫉㫆㫃㩷㫇㪸㫅㪼㫃
㩿㪉㪊㪀ᶧ᥏䊝䊆䉺 㩿㪉㪉㪀㪛㪩㩷㪺㫆㫅㫊㫆㫃㪼㩷㪧㪚
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 5/93
(6)
(3)PCU
(5)
(13) (4)MPC
(5)GRID CONT(BR)
(10) (3) (6)GRID CONT(BK)
(7)DC/HV POWER SUPPLY(BR)
(8)DC/HV POWER SUPPLY(BK)
(11)
(9)FPD COOLING UNIT
(8)
(10)Connector7
(7) (4) (11)Switching HUB
(12)TRANS UNIT
(13)RELAY ASSY
(9)
(12)
̪The number in this figure indicates
the number in Chart 3-1.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 6/93
3-3 Components of FPD17-R1
3-3-1 FPD
FPD figure is as follows.
FPD
Ԙ HV CABLE CONNECTOR
ԙ FIBER CABLE
CONNECTOR
Ԛ DC CABLE CONNECTOR
ԛ WATER COOLED HOSE
FPD FRONT
FPD SIDE
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 7/93
3-3-2 PSU
PSU figure is as follows.
PSU
3-3-3 PCU
PCU figure is as follows.
PCU
㽴
㽶
㽳
㽵
PCU FRONT PCU REAR
Ԙ POWER SUPPLY CABLE CONNECTOR
ԙ LAN PORT
Ԛ FIBER CABLE CABLE CONNECTOR㧔TABLE㧕
ԛ FIBER CABLE CABLE CONNECTOR㧔STAND㧕
Ԝ FPDIF CABLE CABLE CONNECTOR
ԝ SERIAL PORT
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 8/93
3-3-4 MPC
MPC figure is as follows.
MPC
㽴 as follows.
㽲 㽳
㽵 Ԝ P1 ĺ COM3
ԝ P2 ĺ COM4
Ԟ P3 ĺ COM5
DISTRIBUTION CABLE
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 9/93
3-3-6 DC/HV POWER SUPPLY
DC/HV POWER SUPPLY configurations are as follows. There are two DC/HV POWER
SUPPLYs, for STAND FPD and TABLE FPD. DC/HV POWER SUPPLY for TABLE is set
that for STAND in the PSU.
DC/HV POWER SUPPLY
㽵 㽳
㽴
㽶
㽲
DC/HV POWER SUPPLY FRONT DC/HV POWER
SUPPLY REAR
Ԙ DC/HV AC CABLE
(a) (b) (c) (d)
ԙ DC CABLE CONNECTOR
Ԛ HV CABLE CONNECTOR
ԛ PS CONT CABLE CONNECTOR
Ԝ INDICATION LIGHT
(a) AC100(HV)
(b) HV
(c) AC100(DC)
(d) DC DC/HV POWER SUPPLY in PSU
㽲 㽴
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 10/93
3-3-8 Connector7
CONNECTOR7 figure is as follows.
Connector7
Ԙ J1
㽵 ԙ J2
Ԛ J3
㽴
㽶 ԛ J4
㽼 Ԝ J5
㽻
ԝ J6
㽷 㽳
Ԟ J7
ԟ J8
Ԡ J9
ԡ J10
㽸 㽲 Ԣ J11
㽹㩷 㽺
㽲
㽳
㽴
㽵
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 11/93
3-4 Setting Units
The ways of setting for each unit are specified as follows:
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 12/93
3-4-3 Setting of MPC
Setting of MPC
Insert the LAN CARD to PC CARD
SLOT, before installation of MPC.
Before setting
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 13/93
4 Connection
4-1 General Precautions when Wiring
Confirm that Distribution board, the breaker for each unit or power switch is
OFF, and then connect the power line. (normally connected at the last)
Connect the each cable surely.
Make sure to ground the either side of the connection part, in case of the
shielded cable.
Connect cables orderly. DO NOT wind small an extra part of the cable. If wind
small, a cable becomes coil, this may cause the malfunction.
There are two cables for DC CABLE, HV CABLE, and WATER COOLED
HOSE respectively. One is the cable for Stand FPD, other is for Table FPD.
Connect cables orderly in the same way.
㽴
㽲
㽵
㽳
㪊㪇
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 14/93
㪉㫅㪻㩷㪺㪸㪹㫀㫅㪼㫋
㾄
㾅 㾃 㪚㪟㪄㪉㪇㪇
㪉㪋 㽼 㪚㪦㪥㪫
㪉㪉 㽹
㪉㪌 㪉㪎 㾁㽿㽶
㪙㪢㪄㪈㪉㪇㪝
㪚㪦㪥㪫
㪉㪈
㪧㪪㪬㩷㪩㪘㪚㪢
㪞㪩㪠㪛㩷㪚㪦㪥㪫 㪞㪩㪠㪛㩷㪚㪦㪥㪫
㩿㪙㪢㪀 㩿㪙㪩㪀
㪉㪍
㽽
㪧㪚㪬
㪝㫃㫆㫎㩷㫊㪼㫅㫊㫆㫉
㪉㪐 㪬㪛㪈㪌㪇㪙㪄㪋㪇
㪚㫆㫅㫅㪼㪺㫋㫆㫉㪎
㪊㪇 㽺
㪟㪬㪙
㽸
㪫㪘㪧
㪛㪚㪆㪟㪭㩷㪙㪦㪯㩿㪙㪢㪀 㪊㪉
㪫㪟㪄㪈㪇㪈
㪤㪧㪚
㪛㪚㪆㪟㪭㩷㪙㪦㪯
㩿㪙㪩㪀
㽾 㽻
㪫㪩㪘㪥㪪
㪬㪥㪠㪫 㪛㪩㩷㪺㫆㫅㫊㫆㫃㪼
㪝㪧㪛㩷㪚㪦㪦㪣㪠㪥㪞㩷㪬㪥㪠㪫
㪧㪦㪮㪜㪩 㪊㪊
㪬㪥㪠㪫
㪊㪋
㪛㫀㫊㫉㫀㪹㫌㫋㫀㫆㫅
㪝㫃㫆㫎㩷㫊㪼㫅㫊㫆㫉 㪹㫆㪸㫉㪻
㪧㪛㪙㪄㪊㪇㪇㪇 㪊㪈
㪉㪊 㽷㾀㾂 㪉㪏
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 15/93
4-3 Cable List
The cables used for connecting between PSU Rack components are shown in “Chart 4-1
Cable list”. Either one of the two cables are used for the cables which are indicated by BR/BK,
in case of 1FPD system.
Connect each devices following to “4-4”. The number of “Prepared cable” corresponds to the
number in “Chart 4-1 Cable list”.
The number of cables in this documents are specilized for this, and these numbers
don’t correspond cable number in other document.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 16/93
Chart 4-1㩷 CABLE LIST
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 17/93
4-4 PSU Internal Connection
Connect each PSU internal unit (PCU, MPC, and other internal devices located) in this
section. Connection diagram is as follows
㪈㪇㪇㪭 㪛㪚
㪈㪇㪇㪭
㪬㪛 㪩 㪛㪚㪆㪟㪭㩿㪙㪢㪀
㪟㪭
㪙㪢㩷㪝㪧㪛
㪦㫇㫋㫀㪺㪸㫃
㪤㪦㪫㪦㪩 㪈㪇㪇㪭
㪚㪟 㪈㪇㪇㪭
㪞㪩㪠㪛㩷㪙㪩 㪟㪬㪙 㪣㪘㪥
㪙㪩
㪙㪩㩿㪧㫆㫎㪼㫉㪀 㫀㫅㩷㪿㫆㫊㫇㫀㫋㪸㫃
㪙㪩㩿㪞㪥㪛㪀
㪤㪦㪫㪦㪩
㪚㪟 㪞㪩㪠㪛㩷㪙㪢 㪘㪩㪚
㪈㪇㪇㪭 㪚㪟
㪙㪢
㪈㪇㪇㪭 㪧㪚㪬 㪛㪩㪺㫆㫅㫊㫆㫃㪼 㪤㫆㫅㫀㫋㫆㫉
㪝㪘㪥
㪈㪇㪇㪭 㪧㫆㫎㪼㫉
㪪㫎㫀㫋㪺㪿
㪛㪚㪉㪋㪭
㪈㪇㪇㪭 㪢㪼㫐㪹㫆㪸㫉㪻 㪤㫆㫌㫊㪼
㪈㪇㪇㪭
㪝㪧㪛㩿㪙㪩㪀 㪮㪘㪫㪜㪩 㪩 㪫㪸㪹㫃㪼㪫㪸㫇
㪚㫆㫅㫅㪼㪺㫋㫆㫉㪎
㪥㪚
㪮㪸㫋㪼㫉
㪺㫆㫆㫃㪼㫉
㪛㪩㪄㪯㪞㪜㪥㩷㪚㪸㪹㫃㪼 㪬㪛
㪈㪇㪇㪭
㪘㪩㪚 㪚㪟
㪝㪧㪛㩿㪙㪢㪀
㪝㫃㫆㫎㩷㫊㪼㫅㫊㫆㫉
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 18/93
Power Supply cable of PCU and MPC are connected to outlet in PSU. Taps are numbered
for the explanation of the connection, as follows.
TAP
Two or three cables are connected
with the tap as shown in the
㽲 㽴 㽶 (No.2): DC/HV POWER SUPPLY(BK)
(No.4): DC/HV POWER SUPPLY (BR)
(No.5): Switching HUB
In the case of 1FPD system, there is
no cable connected with (No.2) and
(No.4).
㽳 㽵 㽷
The following cables are connected
with other empty taps.
TAP (No.1): PCU POWER SUPPLY CABLE
(No.3): EMPTY
(No.6): MPC POWER SUPPLY
CABLE
4-4-1 PCU
(1) Connection of PCU POWER SUPPLY CABLE
PCU POWER SUPPLY CABLE
The CABLE should be connected to the
position enclosed shown in left picture.
PCU REAR
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 19/93
(2) Connection between PCU and SWITCHNG HUB
Prepared CABLE: CABLE,LD-CT/BU2 (No.1)
Connection between PCU and SWITCHING HUB
The CABLE should be connected to the
position enclosed shown in left picture.
PCU REAR
Next, Connect the cable to
SwitchingHUB port No.1.
Switching HUB
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 20/93
(3) Connection between PCU and CONNECTOR7
Prepared CABLE: FPDIF CABLE,OUTER䋨No.4䋩,COM CABLE(No.4)
Connection between PCU and CONNECTOR7
Connect the FPDIF CABLE,OUTER with J1
connector of Connector7 and connect
another side of it with the connector of
PCU.
PCU REAR
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 21/93
4-4-2 MPC
(1) Connection of MPC POWER SUPPLY CABLE
MPC AC CABLE
The CABLE should be connected to the
position enclosed in left picture.
Switching HUB
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 22/93
4-5 Connection between Components to PSU and Combination
Devices
In this section, connection between components of PCU and external configuration devices is
described.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 23/93
4-5-2 Connection on MPC
(1) Connection between MPC and UD150B-40
Prepared CABLE: MAINTENANCE CABLE (No.7)
Connection between MPC and UD150B-40
The DISTRIBUTION CABLE should
be connected to the frame position
shown in left picture. Each cables are
connected to each port of extended
port. (Refer to Chapter 3-3-4)
MPC REAR
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 24/93
(3) Connection between MPC and TH-101
Prepared CABLE: CABLE, AOM6S-20 (No.32)
MPC and TH-101
Connect the CABLE, AOM6S-20 with P3
(COM5).
1FPD system is shipped as a stand system. In the case of the table system, connect
the cable which is connected to the connector-7, to J3.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 25/93
(2) Connection between Connector7 and CH-200
Prepared CABLE: ARC CABLE (No.11)
Connection between Connector7 and CH-200
ARC CABLE should be connected to
the frame position (J5) enclosed
shown in the left picture.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 26/93
4-5-5 Connection on DC/HV POWER SUPPLY
(1) Connection between DC/HV POWER SUPPLY and FPD (No.1)
Prepared CABLE: HV CABLE, FRAD (No.16),(No.17)
Connection between DC/HV POWER SUPPLY and FPD
The HV cable connector is on the side of the
main body of the DC/HV.
The HV CABLE, FRAD should be connected
to the frame position shown in left picture.
Insert the cable so that "Red round sign" on
HV CABLE CONNECTOR the cable side and on the connector side lap
over, when HV CABLE FRAD is connected.
Turn the connector of the cable clockwise after
inserting the cable and fix it.
DC/HV POWER SUPPLY in PSU
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 27/93
4-5-6 Connection on GRID CONT
(1) Connection between GRID CONT and CH-200
Prepared CABLE: SIGNAL CABLE CN7 (No.18) (No.19)
Connection between GRID CONT and CH-200
Connect the cable with the frame position
(CN7) shown in the left picture.
Insert the cable and fix by attachment.
GRID CONT
*The cable for BR and BK are connected
according to a similar procedure.
*The other end of the cable is connected
with
“CH-200 CHC-200 J17” (BR)
“CH-200 CHC-200 J16” (BK)
GRID CONT
*The cable for BR and BK are connected,
according to a similar procedure.
*The other end of the cable is
connected with
“BR-120 CONT BRC-120 J9” (BR)
“BK-120 CONT BKC-120 J2“ (BK)
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 28/93
(3) Connection between GRID CONT and BK-120F/BR-120F (No.2)
Prepared CABLE: GRID MOTOR CABLE (No.22) (No.23)
Connection between GRID CONT and BK-120F/BR-120F
The CABLE should be connected to the
frame position shown in the left picture.
AC SERVO
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 29/93
(5) Connection between interlocking relay for GRID CONT and systems and UD150B-40
㩷 Prepared CABLE: XRAY I/F CABLE PSU(No.26)
Connection between interlocking relay for GRID CONT and systems and UD150B-40
The CABLE should be connected to the
position shown in left picture.
GRID CONT
Output Voltage of UD150B-40 is set at 15V. Please set a output voltage of UD150B-40 at
24V for interlocking relay for GRID CONT and systems.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 30/93
4-5-7 Connection on FPD COOLING UNIT
(1)Connection of water-cooled hose
Prepared CABLE: HOSE ASSY,THERMO CON(No.27),(No.28)
Connection of water-cooled hose
The water-cooled hose on the FPD
COOLING UNIT side and the BR or
Side of Side of
BK side is connected as shown in the
FPD COOLING UNIT BR/BK
left picture.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 31/93
(2)Connection of COOLER WARNING CABLE
V Prepared CABLE: COOLER WARNING CABLE (No.29)(No.30)
Connection of COOLER WARNING CABLE
Connect the cable with the side of
flow sensor of WATER-COOLED
HOSE.
J8
J9
Connector7
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 32/93
4-5-8 FPD
FPD (Flat Panel Detector) and PCU, the DC/HV POWER SUPPLY, and the FPD COOLING
UNIT are connected here. The same connection is done for BR and for BK.
17”FPD
17” Flat Panel Detector
HV CABLE
DC CABLE
WATER-COOLED HOSE
FIBER CABLE
FPD SIDE
During connection of the equipment, avoid tilting, vibration, and sharp impact against
it.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 33/93
(1) Connection between DC/HV POWER SUPPLY and FPD (No.1)
Prepared CABLE: DC MAIN CABLE,FRAD (No.14), (No.15)
Connection between DC/HV POWER SUPPLY and FPD
The PSU side has already been
connected by "Chapter 4-5-5". The FPD
side is connected here.
FPD SIDE
DC CABLE CONNECTOR
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 34/93
(2) Connection between DC/HV POWER SUPPLY and FPD (No.2)
Prepared CABLE: HV CABLE, FRAD (No.16), (No.17)
Connection between DC/HV POWER SUPPLY and FPD
The PSU side has already been
connected by "Chapter 4-5-5". The FPD
side is connected here.
FPD SIDE
HV CABLE CONNECTOR
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 35/93
(1) Connection between PCU and FPD
Prepared CABLE: FIBER CABLE,FRAD (No.5), (No.6)
FIBER CABLE,FRAD
The PSU side has already been
connected by "Chapter 4-5-5". The FPD
side is connected here.
FPD SIDE
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 36/93
(2) Connection of WATER-COOLED HOSE
Prepared CABLE: HOSE ASSY,THERMO CON (No.27), (No.28)
Connection of WATER-COOLED HOSE
ޣBR-120Fޤ ޣBK-120Fޤ
The connector of the water-cooled hose of
BR is at the position shown in the picture on.
The connector of the water-cooled hose of BK
is at the position shown in the picture on.
Connect two hoses.
Confirm the hose is not removed after
connecting it.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 37/93
4-5-9 DR Console
Prepared CABLE: POWER DISTRIBUTER BOX, PDB-3000(No.31)
DR console
The cable is connected with the position of three
circles shown in a left picture.
PDB-3000
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 38/93
4-5-10 Thermo Meter
Prepared CABLE: CABLE, AOM6S-20 (No.32)
Thermo Meter
MPC side has already been
connected. (See "4-5-2"). Connect
another side of the cable with
COM CONNECTOR of TH-101.
COM CONNECTOR
TH-101
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 39/93
(2) Connection of PSU POWER SUPPLY (No.2)
Prepared CABLE: GROUNDING CABLE (No.34)
GROUNDING CABLE
GROUNDING CABLE is connected
with the position of the left picture
frame in the PSU power supply part.
Fix with the screw firmly so that the
cable should not come off.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 40/93
5 Turn On the Power Supply
5-1 Power Input Procedure and Confirmation
Confirm the power on and connection of PSU RACK. Remove the front cover of PSU RACK
and follow the instruction below.
Monitor, keyboard and mouse will not operate after PCU is started, so make sure to
connect them before that. In addition, for PSU, the monitor, the keyboard, and the
mouse are not connected, in case the standard system. Use those components that
are supplied with such as DR console.
(5) After PCU is started, DC power supply and high-voltage power supply can be turned
on from the power control of PCU control software Xcat. FPD cooling unit should be
running during DC power supply is turned on, so do not turn on both DC and
high-voltage power supply when the cooling unit is stopped.
After turn on the power of PSU RACK, check the temperature setting of cooling unit
(see “6-2 Changing Temperature Settings” for details), and refill distilled water (See
“6-3 Refilling of Water” for details) immediately. Temperature is set properly when
shipping, but if not, abnormal setting may damage FPD. Also, the distilled water is not
refilled completely at first. Beware of the temperature malfunction or the damage of
FPD, by the incomplete refill of the distilled water.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 41/93
In case PCU is turned OFF while the power of FPD is ON, or in case the optical fiber
cable between FPD and PCU is disconnected, the setting inside FPD will be abnormal
and will not be operated properly. In this case, turn OFF FPD by the menu of Xcat on
PCU. (See “7-3 FPD Operation Check “ about the power operation).
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 42/93
6 Setting FPD Cooling Unit
The FPD COOLNG UNIT is set in PSU RACK.
Because the temperature setting of the FPD COOLNG UNIT has been adjusted when shipped,
so it is not required to set it normally. Remove the cover of PSU RACK, and operate it
according to this section when it is required.
DISPLAY
POWER SWITCH
WATER INTAKE
Water Temperature
Mode
Software information is displayed for one second, when turning the power switch is ON, and
the temperature, the preset temperature, and the mode are displayed. The FPDCOOLING
UNIT are basically used with normal mode.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 43/93
6-2 Changing Temperature Settings
Temperature Setting
Push theޣSELޤkey and set theޤ<ޣcursor
at [SU].
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 44/93
6-3 Refilling of Water
6-3-1 Refilling Method
Reservoir tank is shown in the fig. 6-1. The spout for refilling distilled water is circled in the
figure. Capacity of the reservoir tank is about 1.2 liters. Distilled water is required,
depends on the length of the hose, because the capacity of a hose is 1.0 liters. First, put
water into the reservoir tank and turn on the power supply. When water starts circulating,
water in the reservoir tank decreases. So keep refilling water. When decreasing is
stopped, keep working the system for about 10 minutes in that condition. Bubble in the
tube will decrease. In case the bubble does not decrease, the current will go wrong. In
this case, turn the power OFF and ON to decrease the bubble. Confirm the connection
part for the water leakage.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 45/93
7 Setting PCU
In standard version, PCU is not connected to display, keyboard and mouse. When PCU is
operated by a single FPD17-R1, connect the display like DR console, the keyboard, and the
mouse directly to PCU. Or connect PCU from DR console by a remote desktop, according to
the description in this chapter.
In the case of Table single panel system or Stand and Table one X-ray tube system,
change the system configuration setting according to the following procedures.
mn<return>
C <return> indicates inputting Enter key. (Hereinafter, same)
D The input part is indicated with the under line. (Hereinafter, same)
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 46/93
User Name :
Menu :
Menu : 6<return>
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 47/93
99 - Main Menu
Menu :
Menu : 1<return>
Menu :
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 48/93
In case of “Over Sampling”, selecting “1” means the function OFF, selecting “3”
means the function ON, and selecting “3” means the value in the initial condition.
Input ”1” to select “Over Sampling OFF”. Following 2 inquiry continues, Input “y” in
the both inquiries.
- Do you start (Y/N) [N]?
- Dou you update (Y/N) [N]?
Menu :
Menu : 1 <return>
Execute
------------------------------------------------------------------------
1 - FPGA F/W (CIF)
2 - Maintenance S/W
3 - Board Check S/W
11 - FPGA F/W (CIF) from the Backup Memory
12 - Maintenance S/W from the Backup Memory
13 - Board Check S/W from the Backup Memory
99 - Main Menu
Menu : 1<return>
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 49/93
19:31:2
3)
Copyright (C) 2000-2003 by Embedded and Real-Time Systems Laboratory
Toyohashi Univ. of Technology, JAPAN
7-1-2 Xcat
System configuration for FPD17-R1 is shown as “Chart 7-1 FPD17-R1 System
Configuration”. And for Xcat, there are Stand 1FPD system, Table 1FPD system, and
Stand and Table 2FPD system.
Here, set Xcat according to the system. Following is the setting Table 1FPD system for
example.
1) End Xcat and Temperature Monitor on PCU, and open [Utility folder] of
[C?tools?Xcat_Rev2.0.1.0?Utility]from [My Computer] of Windows Start menu.
There are some files in the folder, and confirm there are the following 3 files in the
folder.
- SetStandSystem.vbs
-SetTableSystem.vbs
-SetStandTableSystem.vbs
2) These files are setting files of each system. In case of Stand 1FPD system,
double-click [SetStandSystem.vbs].
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 50/93
3) When the system setting is completed, the following message is displayed. Click
[OK].
When this message is displayed, the setting is completed. In case the following message
is displayed, Xcat or Temperature Monitor is ON. So, end it once, and set it again.
4) Start Xcat to confirm the operation, after setting is completed. Select [Tool]-[Options]
from Xcat menu, and open [Options] window. [Stand] is valid, confirming by [Calib]
tab.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 51/93
7-2 Loading FPD Shipping Parameters
It is necessary to set the information of the defect etc. that FPD has in the initial state to
PCU to get an image by using various corrections in FPD. It explains the setting method
here.
1) Select [Tool]-[All Load] from Xcat menu, [All Load] window is opend.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 52/93
2) Remove the check of [Image Quality Information].
3) Set the file of FPD initial data that has extension of [.cb1] from CD-ROM at the [FPD
Specific Information].
Example of reading
file form CD-ROM
䂓 䂓
䂓
(4) Click [OK], so FPD initial data is set, and following message is displayed. Confirm
loaded data is the data of FPD which is set. Serial number of FPD is described in a
product label.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 53/93
7-3 FPD Operation Check
Follow the instructions below to confirm the low and high voltage power supply setting and
operation.
1) Click the [Tool] from Xcat menu and select the [POWER]. [Power Control] window is
opened.
2) Remove the check marks from [Synchronize with the host system] and [Enable
timer control] of [HV Power Control].
3) Warning shown Fig.7-13 is displayed. Close [Power Control] window, and open
[Power Control] window again as the same procedure before.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 54/93
Fig.7-13 Warning
*These checks are put in initial state. This is not used this time, these functions are
used to synchronizes with the system such as DR consoles and the power supply is
controlled (See "Chapter 7-6").
4) Turn the power ON of (1)[DC Power Control], then turn the power ON of (2)[HV
Power Control].
(1) (3)
(2) (4)
*In the case of 2FPD system, turn the power ON (3) and then, (4). It takes about 15
seconds until DC power gets ON. It takes about 1 minute until HV power gets ON.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 55/93
(5) Next, confirm the operation. Select [Tool] - [Options], and [Options] window is
opened.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 56/93
Fig.7-18 RADsp TAB
(10) There is no problem in the connection if it is possible to capture the image which has
about 14000 pixel value. (Fig.7 -19)
*In the case of 2FPD system, put the check in Table, and test the image capture.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 57/93
7-4 Setting PCU LAN Port IP Address
Standard IP address of LAN port is set as “Chart 7-2 IP address list”. In case of changing IP
address, see “Appendix2 Setting IP address of LAN port”.
ID/Password ʊ ʊ
Administrator / Shimadzu ʊ ʊ
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 58/93
7-5 PCU Remote Maintenance (XCAT) Setting
Fig.7-20Xcat Menu (Options)
2) Open [MPC] tab, and check [Enable remote maintenance] and [HV power off by
host system synchronization].
*Select [After calibration] after contacting the remote maintenance center, in the case of the
device to which the HV power supply is not turned OFF by 24-hour power distribution.
Fig.7-21 MPC TAB
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 59/93
7-6 Setting Power Supply
Setting of the power supply is required, when it interlocks the system such as DR consoles,
setting power ON and OFF.
1) Select [Tool] - [Power] form Xcat menu. [Power Control] window is opened.
2) When both of DC power and HV power are ON, turn OFF both. Turn OFF both of
them in reverse order of (4) in “7-3 FPD Operation Check“.
3) Check [Synchronize with the host system] of [HV Power Control] in [Power
Control] window.
Fig.7-23 Power Control window (Check Synchronize with the host system)
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 60/93
4) Check [Synchronize with the host system], and the following message is displayed.
Click [OK].
6) Set the time when the power is ON by [hour] and [min]. Normally, [hour: 8] and
[min:0] are set. Confirm the user’s status of use, and set it about 1 hour before the
operation is started.
*If the operation is started at 8 a.m., turn the power ON at 7 a.m.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 61/93
8 Setting MPC
In standard version, MPC is not connected to display, keyboard and mouse. When MPC is
operated by a single FPD17-R1, connect the display like DR console, the keyboard, and the
mouse directly to MPC. Or connect MPC from DR console by a remote desktop, set the
described items in this chapter.
When you connect a monitor, keybord and mous to MPC directly, there is a case not
to display anything on the moniotr after start up Windows. In that case, input
Ctrl+Alt+F1 to display on the monitor.
Standard IP address of LAN port is set as “7-2 IP address list”. In case of changing IP
address, see “Appendix 2 Setting IP Address of LAN Port".
Also, when the ID, the password, and IP address of MPC are changed, the setting of Xcat
and CIF on PCU is required. See “Appendix3 Remote Maintenance“.
Set the thermometer TH-101 (Microtechno Co.Ltd) as follows to record the data every 10
minutes.
㽷
㽹
㽲
㽳 㽴 㽵 㽶
TH-101
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 62/93
1) POWER Switch
The power switch for the data logger TH-101.
Slide the switch knob in the window at the lateral side of the case using a
ballpoint pen.
When the knob is set to OFF position, the power is OFF, when ON position
the power is ON
2) RECORD Switch
Switch to execute the recording for each mode.
3) lNTERVAL Switch
Switch to change the parameters for each mode.
4) MODE Switch
Switch the mode.
5) COM connector
Connect to PC.
Used connecting to the specified accessory cable, in order to set the time and
the measurement conditions and obtain the data.
6) ALARM connector
When any two terms of settings such as temperature, humidity and dew point
achieved at the upper or lower limit, the contact point becomes ON.
7) Display
Display switching the temperature or humidity mode. Besides, show the
display indicating the data status, the measurement, replacement of the
battery and alarm (upper or lower limit) etc.
8) Sensor
Installed the thermometer or humidity sensor.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 63/93
3. Turn ON the data logger.
Slide the knob of the power switch
[POWERON/OFF] for the data logger
TH-101 to set ON position using the
ballpoint pen.
4. Fix this thermometer at the proper
place in the examination room.
䊶The thermometer can be fixed by
hook and loop fastener as the
following picture.
䊶Fix it at near and the same height
as FPD.
䊶Connect a cable to avoid disturbing
the study.
Battery life is about 6 months. Battery mark is shown at display of the main body
indicating the shortage of the battery life. In this case, replace 2 AAA(cell) batteries
seeing “Appendix1 Periodic Parts Replacement” .
2) Select [Communication]-[Serial port setting] in the main menu and set the setting
of the communication port as follows.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 64/93
٨ Port 㧩 COM5
٨ Baud Rate 㧩 9600
٨ Parity 㧩 odd
٨ Stop 㧩 1
Fig.88-2 Setting of communicaton port
3) Click [OK], after setting. Because [It was set up] message is opened, click [OK]
again.
2. Various settings
Fig.8 -4 Communication error
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 65/93
<Confirmation>
Confirm whether the REC mark is displayed in the display part of TH-101. In that
case the record has already been begun and stop recording according to the
following procedures.
[REC] mark
2) Setting window [Various setup] is displayed. Select [Time] tab, check [Adjust to the
PC time], and click [Setting].
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 66/93
Fig.8-7 Measuring condition tab
5) Select [Dew point alarm] tab and set as follows, click [Setting].
ƔUpper limit = No
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 67/93
Fig.8-9 Dew point alarm tab
3. Record start
1) Select [Communication]-[Start recording] from the main menu.
2) The following messages are shown to confirm the record start, click [Yes].
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 68/93
Fig.8 -11 Record start
3) The following messages are shown to confirm the record stop, click [OK].
4. Stop recording
1) Select [Communication]-[Terminate recording] from the main menu.
2) The following messages are shown to confirm the record stop, click [Yes].
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 69/93
3) The following messages to show that the record was stopped are displayed, click
[OK].
4) Setting window is opened. Select [Time] tab, and check [Adjust to the PC time]. Next,
click [Setting].
5. Confirmation
Start recording once, and stop recording after more than 30 minutes is passed, then
check㩷 whether the data is recorded per 30 minutes. (By using 2. Various settings)
1) Select [Communication]-[Loading the data] from the main menu 30 minutes after
recording. Following chart is displayed. Check the box of the desired data, and click
[Loading].
*The following message is displayed, when this operation is done without stopping recording,
and stop recording according to the procedure of “4. Stop recording”.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 70/93
Fig.8 -18 Graph
3) When [File]-[Properties] of the main menu is selected, the data logging beginning
time ([Start Time]), final data acquisition time (End Time), and data logging intervals
(Interval) is displayed as follows.
Logging every 30 minutes can be confirmed by the graph or a detail of the data.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 71/93
8-3 Confirmation of Log Alert Storage Folder
MPC is designed for acquiring Logs and alerts which are required for the remote
maintenance. When shipped, each setting like creating folders to save the logs and the alerts
have been already set. Here, confirm these folders.
See the following list which shows the required folders to send and save the logs and the
alerts. See “Appendix3 Remote Maintenance” about the details of the remote maintenance.
DefectMap_1_3.cab(Table: Error)
1
DefectMap_1_4.cab(Stand: Error)
ApplicationLog.txt
TempLog_1.txt
*1: When the remote maintenance function enable on the Internet, log files sent to log server were
moved to folder for saving sent files. Log files of Xcat and CIF were not moved.
*2: In the case of log file of Xcat, Only latest one is saved at folder.
*3: When the remote maintenance function enable, log file retention period is 40 days.
Automatically removed log file older 40 days from MPC.
*4: When a number of log files of CH-200 or CH-200 second are made in a day, the number is
added to head of file’s name. (Ex. 2_CH_log(2008-01-01).log)
*5: When PCU issue a warning, alert file is made other than log file.
*6: When a log file is made, data stored at a thermometer are deleted.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 72/93
1) Open [My Computer]-[Local Disc(C):] from start menu to see all of the folders in the
local disc.
2) Double-click [Diag] folder in the local disk, and double-click [PCU] folder.
Further, confirm [C:?Diag?PCU?log] in the same way as “alert”. Confirm [C:?CIF_rlog] and
[C:?DRC_rlog] are the share folders from Fig.8-20.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 73/93
9 Transmitting Confirmation of Log and
Alert Files
Confirm the logs are actually transmitted to the folder which is confirmed in “8-3 Confirmation
of Log Alert Storage Folder“.
However, confirm only the components of FPD17-R1. (Except FPD17-R1)
Items which need to be confirmed are as follows.
Confirm transmitting the log and the alert. For the details of the transmitting units, the saving
folders, the uploading files, and details for the creation date, see “Appendix3 Remote
Maintenance“.
Confirm transmitting the alert and the log, from PCU(Xcat) to MPC. In case FPD peripheral
device malfunction is occurred, PCU notifies the warnings to MPC (Transmitting the alert
files), and the related files. (Including Log files)
To confirm it, unconnect COOLER WARNING CABLE (See “4-5-7㩷 Connection of FPD
COOLING UNIT“.), and let the FPD malfunction of stand side occurr on purpose, to see if
the alert file and the logfiles are properly transmitted.
1) Open the PCU alert file saving folder ([C:?Diag?PCU?Alert]) and PCU log file saving
folder ([C:?Diag?PCU?log]). In case some files are in the folder, delete them.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 74/93
㩷
Fig.9 -1 Alert Saving folder and log saving folder
2) Unconnect COOLER WARNING CABLE which is connected to J8 of Connector7,
open each folder again to confirm there is each file for sure. Alert files and log files
only for the stand are created, because the only cables for the stand are removed.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 75/93
Operation is normal when these files are transmitted for sure. After confirming it, restore the
cables to the original state. When the content of the alert file is browsed by Notepad, the
previous alert remains as the error of FPD COOLING UNIT, as follows.
3) Let the folder be empty state by deleting the created files in the folder, finally.
Confirm transmitting the logs from PCU (CIF) to MPC. CIF runs constantly, and it is set to
transfer the logs at normal appointed time. (2:30) Here, end running CIF (TeraTerm) on
PCU, to confirm transmitting logs from CIF.
1) Open CIF log file saving folder ([C:?CIF_rlog?logs]), and in case there are some files
in the folder, delete them.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 76/93
2) End TeraTerm on PCU. Open CIF log saving folder again, and confirm there is a CIF
log file. Operation is normal when the CIF log file is created, as Fig.9-5.
3) Let the folder be empty state by deleting the created files in the folder, finally.
Confirm transmitting the logs from TH-101 to MPC. TH-101 is also set to transfer the logs at
normal appointed time. (2:30) Execute the batch file (templog_output.bat)
1) Open CIF log file saving folder ([C:?Temp_rlog?logs]), and in case there are some
files in the folder, delete them.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 77/93
2) Double-click [templog_output.bat] in [Temp_rlog] folder. MS-DOS window is
displayed for a moment, and disappeared immediately after the batch file is executed.
After that, open TH-101 log saving folder again, to confirm TH-101 log file is created.
When there is no log file in that folder, check [C:¥Temp_rlog¥sent_log] if there is a
log file. Operation is normal when TH-101 log file is created in which folder.
3) Let the folder be empty state by deleting the created files in the folder, finally.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 78/93
Appendix 1 Periodic Parts Replacement
Replace periodically the following components.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 79/93
Appendix 2 Setting IP Address of LAN Port
PCU
Because the onboard network adaptor of PCU is not used, it is set to the onboard network
adaptor of PCU that not specific Internet Protocol address but the one automatically allotted
is acquired.
It is set to the network adaptor of extending LAN board that Internet Protocol address of
LAN for remote maintenance is acquired.
3) Right-click on the [Local Area Connction Intel(R) PRO/100 VE Network connection] icon
and select [Properties].
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 80/93
4) Click on the [Internet Protocol (TCP/IP)] at the [General] tab window. Click on the
[Properties] and open the [Internet Protocol (TCP/IP) Properties] window.
5) Click on the [Obtain an IP address automatically] and click on the [OK] button.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 81/93
6) Click on the [OK] button at the [Local Area Connection Properties] window. The window
is closed and the settings will be saved and available.
7) Right-click on the [Local Area Connection Intel(R) PRO/1000 GT Desktop Adapter] icon
at the [Network Connections] window and select [Properties].
8) Click on the [Internet Protocol (TCP/IP)] at the [General] tab window. Click on the
[Properties] .
9) [Internet Protocol (TCP/IP) Properties] window is opened. Click on the [Use the
following IP address].
10) Enter the [IP address] and the [Subnet mask], seeing IP address of PCU in “Chart 7-2 IP
address list”.
Leave blank at the [Default gateway]. Delete an IP address if any address is diplayed
here.
Click here
Enter the address
Leave blank
11) Click on [OK] button at the [Local Area Connection Properties] window. The window is
closed and the settings will be saved and available.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 82/93
MPC
The onboard network adaptor of MPC is set to acquire Internet Protocol address of LAN for
remote maintenance.
4) Click on the [Internet Protocol (TCP/IP)] at the [General] tab window. Click on the
[Properties], and open the the [Internet Protocol (TCP/IP) Properties] window.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 83/93
Fig.B-8 Local Area Connection Properties window
6) See IP address of MPC in “Chart 7-2 IP address list”, and input [IP address] and [Subnet
mask].
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 84/93
Enter the address
Leave blank
Leave blank at the [Default gateway]. Delete an IP address if any address is diplayed here.
7) Click on [OK] button at the [Local Area Connection Properties] window. The window is
closed and the settings will be saved and available.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 85/93
Appendix 3 Remote Maintenance
PCU remote maintenance retains the function of transmitting the logs (Application log, FPD
temperature log, FPD defect map) to MPC. Also, It retains the function of transmitting the
alert content to MPC when the alert (FPD peripheral condition malfunction) is occurred.
Here, confirm the required settings to operate these functions normally.
1. Functions
Browse and load
Periodic logs which are uploaded to the server by remote maintenance are as follows.
Blowsing log files directly and downloading are available.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 86/93
Alert
When the following errors are occurred, the alert will be notified, and the related file is
simultaneously uploaded. On the server, the list of “System that the alert is occurred” is
displayed, so early response is available.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 87/93
2. Setting remote maintenance tool of PCU
When IP address, ID, and password of MPC are changed, [Remote Maintenance Config
Tool] of PCU is required to changed. Set it as follows.
3) When the setting of the system that installs is different from the default value, set each I
tem.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 88/93
4) When the input of all items is completed, click the [Check] and confirm the connection with
MPC.When the connection to the folder for Rimomen of MPC succeeds, [Check
completed [OK] is opened and click [OK] to close this dialog.
*Review the setting again when failing in the check.
*When setting of MPC doesn't complete, confirm it after setup of MPC.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 89/93
3. Method of setting MPC log transmitting of CIF
It is necessary to change the setting of the CIF log transmitting program that operates by
PCU, in case that IP address setting of MPC is changed from the factory setting
(192.168.100.10). Change the setting, according to the following procedures.
1) When the Teraterm is operated, shut down Teraterm and program of sending a CIF log is
stopped.
2) Startup [Notepad] on PCU.
3) Open the following file by Notepad.
C:?CIF_rlog?remolog.ini
*In case of opening the file from [File menu], set the ”File of type” to ”ALL Files”.
4) Save the file after editing the part shown in the following, and end Notepad.
=4'/1.1)?
5[UVGO0COG
5[UVGO0COG%+(
/WVGZ0COG
/WVGZ0COG4GOQNQI%+(
/CETQ0COG
/CETQ0COG%+(ANQIVVN
6GTOKPCN(KNG0COG
6VGTO(KNG%+(VGTOKPK
/2%7UGT0COG
/RE7UGT0COG#FOKPKUVTCVQT
Change the MPC IP address
/2%2CUUYCTF
/RCE2CUU9QTF5JKOCF\W
/2%0GVYQTMHQNFGTRCVJ
/RE0GV2CVJ???%+(ATNQI
/2%.QIIKPIHQNFGTRCVJ
/RE.QI2CVJ?NQIU
/2%.QIIKPIHKNGPCOG
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 90/93
/RE.QI(KNG
/2%%QPPGEVKQP4GVT[6KOGU
/RE4GVT[6KOGU
/2%%QPPGEVKQP4GVT[+PVGTXCN OUGE
/RE4GVT[+PVGTXCN
$CEM7R.QI6KOG *QWT
*QWT
$CEM7R.QI6KOG /KPWVG
/KPWVG
$CEM7R.QI/#:PWODGT
.QI4GO0WO
6GTC6GTOHQNFGTRCVJ
6VGTO2CVJ%?2TQITCO(KNGU?66'4/241
When a program of sending a CIF log is started, changed setting become effective.
If you change setting, be sure to perform procedure 1 and 5.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 91/93
Revision History
is added.
(f) Method of setting system configuration is added.
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 92/93
(c) Following Charts are changed.
*Chart 3-1 FPD17-R1 components (p9)
(p46)
(k) Statement for WakeOnLAN Tool is deleted in Appendix2.
(p85,88)
No.7. (p19)
(p71,75,76)
(q) Figure8-18 and Figure8-19 are changed.
E 2008/01/21 (a) The way of connection interlocking relay for GRID CONT and T. Sasaki
systems to UD150B-40 is added.(p31)
(b) Log and alert file transmission folder is changed. (p73)
M517-E483E㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 93/93