Tag no 13-WS-610
Area HLSB
Permit no.
Isolation no.
CHECK TACHO FOR APPROPRIATE SENSING GAP VISUAL CHECK PROPER MUST BE
2 SENSING GAP CLEANED OK
CHECK FOR WOOBLING OF TACHO MOUNT. WHEEL VISUAL CHECK PROPER MUST BE
3 MOUNTING ALLINGE OK
CHECK CLEANLINESS & FREENESS OF WEIGHING IDLERS VISUAL CHECK MUST BE CABLE GLANDING
4 CLEANED OK
CHECK THE CLEANLNESS, TIGHTNESS AND COVER OF SCREW DRIVER TIGHTENED TIGHTENED
5 LOAD CELL JB OK
CHECK BELTWEIGHER ZERO INDI. AT NO-LOAD READING IN DISPLAY ZERO(+/-1%) MUST BE SENSE
10 OK
MUST BE
CHECK CONTROLLER OUTPUT MULTIMETER 3.8-21mA INDICATE
11 OK
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant -3.75 MTPA
Tag no 13-WS-605
Area HLSB
Permit no.
Isolation no.
CHECK TACHO FOR APPROPRIATE SENSING GAP VISUAL CHECK PROPER MUST BE
2 SENSING GAP CLEANED OK
CHECK FOR WOOBLING OF TACHO MOUNT. WHEEL VISUAL CHECK PROPER MUST BE
3 MOUNTING ALLINGE OK
CHECK CLEANLINESS & FREENESS OF WEIGHING IDLERS VISUAL CHECK MUST BE CABLE GLANDING
4 CLEANED OK
CHECK THE CLEANLNESS, TIGHTNESS AND COVER OF SCREW DRIVER TIGHTENED TIGHTENED
5 LOAD CELL JB OK
CHECK BELTWEIGHER ZERO INDI. AT NO-LOAD READING IN DISPLAY ZERO(+/-1%) MUST BE SENSE
10 OK
MUST BE
CHECK CONTROLLER OUTPUT MULTIMETER 3.8-21mA INDICATE
11 OK
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant-3.75 MTPA
Tag no 11-WS-514
Permit no.
Isolation no.
CHECK TACHO FOR APPROPRIATE SENSING GAP VISUAL CHECK PROPER MUST BE
2 SENSING GAP CLEANED OK
CHECK FOR WOOBLING OF TACHO MOUNT. WHEEL VISUAL CHECK PROPER MUST BE
3 MOUNTING ALLINGE OK
CHECK CLEANLINESS & FREENESS OF WEIGHING IDLERS VISUAL CHECK MUST BE CABLE GLANDING
4 CLEANED OK
CHECK THE CLEANLNESS, TIGHTNESS AND COVER OF SCREW DRIVER TIGHTENED TIGHTENED
5 LOAD CELL JB OK
CHECK BELTWEIGHER ZERO INDI. AT NO-LOAD READING IN DISPLAY ZERO(+/-1%) MUST BE SENSE
10 OK
MUST BE
CHECK CONTROLLER OUTPUT MULTIMETER 3.8-21mA INDICATE
11 OK
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant -3.75 MTPA
Tag no 10-WS-509
Permit no.
Isolation no.
CHECK TACHO FOR APPROPRIATE SENSING GAP VISUAL CHECK PROPER MUST BE
2 SENSING GAP CLEANED OK
CHECK FOR WOOBLING OF TACHO MOUNT. WHEEL VISUAL CHECK PROPER MUST BE
3 MOUNTING ALLINGE OK
CHECK CLEANLINESS & FREENESS OF WEIGHING IDLERS VISUAL CHECK MUST BE CABLE GLANDING
4 CLEANED OK
CHECK THE CLEANLNESS, TIGHTNESS AND COVER OF SCREW DRIVER TIGHTENED TIGHTENED
5 LOAD CELL JB OK
CHECK BELTWEIGHER ZERO INDI. AT NO-LOAD READING IN DISPLAY ZERO(+/-1%) MUST BE SENSE
10 OK
MUST BE
CHECK CONTROLLER OUTPUT MULTIMETER 3.8-21mA INDICATE
11 OK
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant -3.75 MTPA
Tag no 03-WS-251
Area ABG
Permit no.
Isolation no.
CHECK TACHO FOR APPROPRIATE SENSING GAP VISUAL CHECK PROPER MUST BE
2 SENSING GAP CLEANED OK
CHECK FOR WOOBLING OF TACHO MOUNT. WHEEL VISUAL CHECK PROPER MUST BE
3 MOUNTING ALLINGE OK
CHECK CLEANLINESS & FREENESS OF WEIGHING IDLERS VISUAL CHECK MUST BE CABLE GLANDING
4 CLEANED OK
CHECK THE CLEANLNESS, TIGHTNESS AND COVER OF SCREW DRIVER TIGHTENED TIGHTENED
5 LOAD CELL JB OK
CHECK BELTWEIGHER ZERO INDI. AT NO-LOAD READING IN DISPLAY ZERO(+/-1%) MUST BE SENSE
10 OK
MUST BE
CHECK CONTROLLER OUTPUT MULTIMETER 3.8-21mA INDICATE
11 OK
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant -3.75 MTPA
Tag no 09-WS-361
Area MIXER
Permit no.
Isolation no.
CHECK TACHO FOR APPROPRIATE SENSING GAP VISUAL CHECK PROPER MUST BE
2 SENSING GAP CLEANED OK
CHECK FOR WOOBLING OF TACHO MOUNT. WHEEL VISUAL CHECK PROPER MUST BE
3 MOUNTING ALLINGE OK
CHECK CLEANLINESS & FREENESS OF WEIGHING IDLERS VISUAL CHECK MUST BE CABLE GLANDING
4 CLEANED OK
CHECK THE CLEANLNESS, TIGHTNESS AND COVER OF SCREW DRIVER TIGHTENED TIGHTENED
5 LOAD CELL JB OK
CHECK BELTWEIGHER ZERO INDI. AT NO-LOAD READING IN DISPLAY ZERO(+/-1%) MUST BE SENSE
10 OK
MUST BE
CHECK CONTROLLER OUTPUT MULTIMETER 3.8-21mA INDICATE
11 OK
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant -3.75 MTPA
Tag no 08-WS-171
Area FILTRATION
Permit no.
Isolation no.
CHECK TACHO FOR APPROPRIATE SENSING GAP VISUAL CHECK PROPER MUST BE
2 SENSING GAP CLEANED OK
CHECK FOR WOOBLING OF TACHO MOUNT. WHEEL VISUAL CHECK PROPER MUST BE
3 MOUNTING ALLINGE OK
CHECK CLEANLINESS & FREENESS OF WEIGHING IDLERS VISUAL CHECK MUST BE CABLE GLANDING
4 CLEANED OK
CHECK THE CLEANLNESS, TIGHTNESS AND COVER OF SCREW DRIVER TIGHTENED TIGHTENED
5 LOAD CELL JB OK
CHECK BELTWEIGHER ZERO INDI. AT NO-LOAD READING IN DISPLAY ZERO(+/-1%) MUST BE SENSE
10 OK
MUST BE
CHECK CONTROLLER OUTPUT MULTIMETER 3.8-21mA INDICATE
11 OK
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant -3.75 MTPA
Tag no 02-WS-108B
Area IOBG
Permit no.
Isolation no.
CHECK TACHO FOR APPROPRIATE SENSING GAP VISUAL CHECK PROPER MUST BE
2 SENSING GAP CLEANED OK
CHECK FOR WOOBLING OF TACHO MOUNT. WHEEL VISUAL CHECK PROPER MUST BE
3 MOUNTING ALLINGE OK
CHECK CLEANLINESS & FREENESS OF WEIGHING IDLERS VISUAL CHECK MUST BE CABLE GLANDING
4 CLEANED OK
CHECK THE CLEANLNESS, TIGHTNESS AND COVER OF SCREW DRIVER TIGHTENED TIGHTENED
5 LOAD CELL JB OK
CHECK BELTWEIGHER ZERO INDI. AT NO-LOAD READING IN DISPLAY ZERO(+/-1%) MUST BE SENSE
10 OK
MUST BE
CHECK CONTROLLER OUTPUT MULTIMETER 3.8-21mA INDICATE
11 OK
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant -3.75 MTPA
Tag no 02-WS-108A
Area IOBG
Permit no.
Isolation no.
CHECK TACHO FOR APPROPRIATE SENSING GAP VISUAL CHECK PROPER MUST BE
2 SENSING GAP CLEANED OK
CHECK FOR WOOBLING OF TACHO MOUNT. WHEEL VISUAL CHECK PROPER MUST BE
3 MOUNTING ALLINGE OK
CHECK CLEANLINESS & FREENESS OF WEIGHING IDLERS VISUAL CHECK MUST BE CABLE GLANDING
4 CLEANED OK
CHECK THE CLEANLNESS, TIGHTNESS AND COVER OF SCREW DRIVER TIGHTENED TIGHTENED
5 LOAD CELL JB OK
CHECK BELTWEIGHER ZERO INDI. AT NO-LOAD READING IN DISPLAY ZERO(+/-1%) MUST BE SENSE
10 OK
MUST BE
CHECK CONTROLLER OUTPUT MULTIMETER 3.8-21mA INDICATE
11 OK
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant -3.75 MTPA
Tag no 02-WS-102
Permit no.
Isolation no.
CHECK TACHO FOR APPROPRIATE SENSING GAP VISUAL CHECK PROPER MUST BE
2 SENSING GAP CLEANED OK
CHECK FOR WOOBLING OF TACHO MOUNT. WHEEL VISUAL CHECK PROPER MUST BE
3 MOUNTING ALLINGE OK
CHECK CLEANLINESS & FREENESS OF WEIGHING IDLERS VISUAL CHECK MUST BE CABLE GLANDING
4 CLEANED OK
CHECK THE CLEANLNESS, TIGHTNESS AND COVER OF SCREW DRIVER TIGHTENED TIGHTENED
5 LOAD CELL JB OK
CHECK BELTWEIGHER ZERO INDI. AT NO-LOAD READING IN DISPLAY ZERO(+/-1%) MUST BE SENSE
10 OK
MUST BE
CHECK CONTROLLER OUTPUT MULTIMETER 3.8-21mA INDICATE
11 OK
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant -3.75 MTPA
Tag no 02-WS-101
Permit no.
Isolation no.
CHECK TACHO FOR APPROPRIATE SENSING GAP VISUAL CHECK PROPER MUST BE
2 SENSING GAP CLEANED OK
CHECK FOR WOOBLING OF TACHO MOUNT. WHEEL VISUAL CHECK PROPER MUST BE
3 MOUNTING ALLINGE OK
CHECK CLEANLINESS & FREENESS OF WEIGHING IDLERS VISUAL CHECK MUST BE CABLE GLANDING
4 CLEANED OK
CHECK THE CLEANLNESS, TIGHTNESS AND COVER OF SCREW DRIVER TIGHTENED TIGHTENED
5 LOAD CELL JB OK
CHECK BELTWEIGHER ZERO INDI. AT NO-LOAD READING IN DISPLAY ZERO(+/-1%) MUST BE SENSE
10 OK
MUST BE
CHECK CONTROLLER OUTPUT MULTIMETER 3.8-21mA INDICATE
11 OK
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant -3.75 MTPA
Tag no 09-LIW-338
Area MIXER
Permit no.
Isolation no.
MUST BE
CHECK ALLINGEMENT OF HOPPER WATER LEVEL 3 ALLINGE
3
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant -3.75 MTPA
Tag no 09-LIW-310
Area MIXER
Permit no.
Isolation no.
MUST BE
CHECK ALLINGEMENT OF HOPPER WATER LEVEL 3 ALLINGE
3
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant -3.75 MTPA
Tag no 09-LIW-311
Area MIXER
Permit no.
Isolation no.
MUST BE
CHECK ALLINGEMENT OF HOPPER WATER LEVEL 3 ALLINGE
3
RML RML
site incharge INSTRUMENT INCHARGE
DIVISION
Rungta Mines Limited Jharabhandh,
Dhenkanal, Odisha-759121 pellet plant -3.75 MTPA
Tag no 09-LIW-352
Area MIXER
Permit no.
Isolation no.
MUST BE
CHECK ALLINGEMENT OF HOPPER WATER LEVEL 3 ALLINGE
3
RML RML
site incharge INSTRUMENT INCHARGE