You are on page 1of 2

Nr.

KEDS-DIV-F-DPP-12
NJËSIA PËR PLANIFIKIM DHE PROJEKTIM
Faqe Faqe 1 nga 2
SPECIFIKIMI TEKNIK I MATERIALIT Versioni 1.1

20.4.1 SPECIFICATION FOR HORIZONTAL INSTALLATION DISCONNECTOR


20 kV, 630 A

Description Unit Requirement Offer


1 Standard IEC 265 ,IEC 129
2 Conductor material Copper
3 Fitting position of disconnector horizontal
4 Standard rated voltage kV 20
5 Number of poles 3
6 Type of insulators Silicon
7 Rated normal current Ir A 630
8 Rated frequency Hz 50
Rated lighting impulse withstand voltage:
145
9 - across the isolating distance kV
125
– to earth and between phases
Rated power frequency withstand
voltage in wet conditions 70
10 kV
- across the isolating distance 55
- to earth and between phases
11 Min. distance between phases mm 260
12 Min. isolating distance mm 200
12]3 Rated short-time withstand current 1 sec kA 16
14 Rated peak withstand current kA 40
15 Mechanical endurance-operation 2000
16 Ambient temperature limits °C -40 +50
17 Installation Outdoor

Epoxy INSULATOR
1 Rated voltage kV 20
2 Insulation material
3 Creepage arcing distance mm 740/272
4 Nominal tensile strenght kN 25
5 Routine tensile load kN 12.5
6 Nominal bending strenght kN 4

REMARKS Includes:
- Breaking whips
- Manual operating mechanism UEKE 3A1
- Operating tubes NPTOT 383 length 2 x 4 mm and two tube supports
- Control shaft - cross arm
Nr. KEDS-DIV-F-DPP-12
NJËSIA PËR PLANIFIKIM DHE PROJEKTIM
Faqe Faqe 2 nga 2
SPECIFIKIMI TEKNIK I MATERIALIT Versioni 1.1

2
Insulator 20 kV