No. Description Unit Requirement Supplier’s Offer

1 Standard IEC‐129‐694‐282

2 Nominal Voltage kV 20

3 Current A 400

4 Maximal voltage kV 24

5 Rated short –time withstand current 1sec kA 16

6 Type of insulators Silicon

7 Insulator creep age distance mm 540


Insulation level, One minute power frequency withstand voltage ( P‐E & P‐P respectively)
8 kV 50‐70
9 Operation mode With handle
10 Disconnector Type With bases

Note: Fuses shall not be included since it depends of the size of transformers and we will supply
separately.