conform with the rules and regulations laid down by LLOYD'S REGISTER OF SHIPPING for a Class
LR 100A1 Double Hull Oil and Chemical Tanker, Ship type 2, CSR, ESP,
*✩WS, LI, SPM4, LMC, UMS, IGS, S.G.1,23, NAV1, ECO, CAC3
Descriptive notes: ETA, COW, SHIPRIGHT (CM)
Cargo Tanks Deck Area means the maximum breadth of the ship multiplied by the longitudinal
extent of the cargo tank space.Measurement referred below are taken from the drawing
No. 101-302 General Arrangement.
B1 = 32,2 m
L1 = 138,55 m
A1 = B1 . L1
A1 = 32,2 . 138,55
A1 = 4461,3 m2
1.2 Horizontal deck area of the single tank having the largest such area, A2
B2 = 14,1 m
L2 = 14,5 m
A2 = B2 . L2
A2 = 14,1 . 14,5
A2 = 204,5 m2
B3 = 32,2 m
Title: Fixed deck foam fire fighting Drawing No.: Page: Rev.
system calculaction 816-132 1 1
Proračun sustava pjene za gašenje Yard Nos.:
požara na palubi 722, 723
Length of the area betwen the two furthest monitors , L3
L3 = 27,5 m
A3 = B3 . L3
A3 = 32,2 . 27,5
A3 = 885,5 m2
The rate of supply of the foam solution should not be less than the greatest of the following:
Q1 = q1 . A1
q1 – cargo tank deck area supply rate coefficient
q1 = 2 l/m2 min as per LR Rules and Regulations of ship for the Carriage of Liquid
.
Q1 = 2 4461,3 Chemicals in Bulk, Chapter 11.3.5.1
Q1 = 8922,6 l/min
Q2 = q2 . A2
q2 – largest single tank area supply rate coefficient
q2 = 20 l/m2 min as per LR Rules and Regulations of ship for the Carriage of Liquid
Q2 = 20 . 204,5 Chemicals in Bulk, Chapter 11.3.5.2
Q2 = 4090 l/min
Q3 = q3 . A3
q3 – largest distance between monitors supply rate coefficient
q3 = 10 l/m2 min as per LR Rules and Regulations of ship for the Carriage of Liquid
Q3 = 10 . 885,5 Chemicals in Bulk, Chapter 11.3.5.3
Q3 = 8855 l/min
Required supply rate is the largest figure of the criteria mentioned above
Q = Q1 = 8923 l/min
Sufficient foam concentrate is to be supplied to ensure at least 30 minutes of foam generation when
using the highest of the solution supply rate defined above
Duration of foam application t = 30 min
Foam liquid concentration selected 3 %
Title: Fixed deck foam fire fighting Drawing No.: Page: Rev.
system calculaction 816-132 2 1
Proračun sustava pjene za gašenje Yard Nos.:
požara na palubi 722, 723
Mixing Ratio to sea water, M
M=3%
G=Q.t.M
G = 8923 . 30 . 3/100
G = 8030,7 l
Due to fact that fire main and foam main are common line, foam concentrate amount is increased
for consumption of 2 water jets working simultanously with one foam monitor.
Capacity for these 2 water jets is 32 m3/h and calculated in needed amount of foam concentrate
results in 480 l/min of additional foam concentrate.
Foam concentrate type is alcohol resistant fluoroprotein UNIVEX 3-3%, supplier Wilhelmsen.
V≥G
T
V ≥ 8510,7
V = 8,6 m3
Or, the capacity of any monitor should be at least 10 l/min of foam solution per square metre of
deck area protected by that monitor, such area being entirely forward of that monitor. Such
capacity is to be not less than 1250 l/min.
QM = qM . A3
QM = 10 . 885,5
QM = 8855 l/min
Title: Fixed deck foam fire fighting Drawing No.: Page: Rev.
system calculaction 816-132 3 1
Proračun sustava pjene za gašenje Yard Nos.:
požara na palubi 722, 723
5 Distance between monitors, R
The distance from the monitor to the farthest extremity of the protected area forward of that monitor
shall not be more than 75% of monitor throw length in still air R0.
Foam monitor type is UFM-150M, supplier Wilhelmsen, which for inlet pressure of 8 bar and
specified capacity gives throw length of:
R = R0 . 0,75
R = 80 . 0,75
R = 60 m
5.1 Distance from poop front monitors to aft tank deck monitor, P1a
Q
P = M
1a 10 ⋅ B/2
8855
P1a =
10 ⋅ 16,1
P1a = 55m
Q
P = M
2a 10 ⋅ B
8855
P2a =
10 ⋅ 32.2
P2a = 27.5m
5.3 Distance between poop front monitors to aft tank deck monitor according to throwing
length R, P1b
P = R 2 − (B/4)2
1b
P = (60)2 − (8,05) 2
1b
P = 3535,2
1b
P = 59,5m
1b
5.4 Distance between tanks deck monitors acc to throwing lenght R, P2b
P = R 2 − (B/2) 2
2b
P = (60)2 − (16,1) 2
2b
P = 3340,8
2b
P = 57,8m
2b
Title: Fixed deck foam fire fighting Drawing No.: Page: Rev.
system calculaction 816-132 4 1
Proračun sustava pjene za gašenje Yard Nos.:
požara na palubi 722, 723
5.5 Maximal selection of the distance between the monitors shall be smallest of P1a,b and P2a,b
P1max = 55 m
P2max = 27,5 m
P1 = 33 m
P2 = 27,5 m
6 Number of monitors, n
L −P
n= 1 1 +2
P
2
138,55 − 33
n= +2
27.5
n = 5,84
Q ⋅ (100 − M)
W=
100
8923 ⋅ (100 − 3 )
W=
100
W = 8655,3 l/min
Q ⋅ M ⋅ 60
C=
100 ⋅ 1000
8923 ⋅ 3 ⋅ 60
C=
100 ⋅ 1000
C = 16 m3 /h
Q ⋅ 60 ⋅ (100 − M)
Cf =
100 ⋅ 1000
8923 ⋅ 60 ⋅ (100 − 3 )
Cf =
100 ⋅ 1000
Cf = 519,3 m3 /h
Title: Fixed deck foam fire fighting Drawing No.: Page: Rev.
system calculaction 816-132 5 1
Proračun sustava pjene za gašenje Yard Nos.:
požara na palubi 722, 723
Additionally, water capacity for 2 x water jets, Qh = 533 l/min (32 m3/h), is required, because fire
main and foam main are common line.
Cf = Cf + 32 m3/h
Cf = 519,3 m3/h + 32 m3/h
Cf = 551,3 m3/h
Three sea water pumps are foreseen to deliver this amount of sea water, working in parallel.
Sea water pumps are:
Title: Fixed deck foam fire fighting Drawing No.: Page: Rev.
system calculaction 816-132 6 1
Proračun sustava pjene za gašenje Yard Nos.:
požara na palubi 722, 723