SSP Se Se3 Eq TF DL 0013 0i (Ac) Reply
SSP Se Se3 Eq TF DL 0013 0i (Ac) Reply
SSP-SE-SE3-EQ-TF-DL-0013-0I
SSP-SE-SE3-EQ-TF-DL-0015-0C
Reply: Modified
CTT or CCT ????
See comment on
sheet 11 and 17
Referencing
Reply: Modified
Reply: Modified
Referencing and make sheet 11
compatible with sheet 9 and 20
CT15
CT13
CT14
Reply: Modified
Indicate connection.
Indicate cross-reference with document:
SSP-SE-SE3-EQ-TF-DL-0014-0H
Reply: Modified
21 23 25 27 29 31
Indicate connection.
Indicate cross-reference with document:
SSP-SE-SE3-EQ-TF-DL-0014-0H
Reply: Modified
See comment on
sheet 2
Indicate connection!
Make sheet 16 compatible with sheet 9 and 20 See comment on sheet 20
???
Reply: Modified
See comment on
sheet 11 and 17
Reply: Modified
Y1
(CT8)
Y2
(CT9)
Y2 FOR WTI
(CT15)
Reply: Modified
CCT1, CCT2 and CCT3 not located on the diagram.
Represent and locate!
See comment on sheet 11
Reply: Modified
General comment:
Create a column indicating the sheet where the terminal is located.
Apply this comment to all terminals: X0 to X13 (Sheets 18 to 20)
Follow the example below:
X0: 28
See comment on
sheet 11 and 17
Make sheet 20
compatible
with sheet 9,
11 and 16
See comment
on sheet 16
Indicate connection
Make sheet 20
compatible
with sheet 9,
11 and 16