C5
RH
C7
WH
C15 C12
PLATE REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS
APPROVED:
BUILDING OFFICIAL
AND HIGHWAYS
OFFICE OF THE BUILDING OFFICIAL
RECOMMENDING APPROVAL:
CEBU CITY
DATE
DATE
WH ACU WH
C14 RECOMMENDING APPROVAL:
ACU
C11 ACU
C4 REF LAND USE & ZONING
C6
APPROVED:
ACU
C13 HEAD DATE
C10
RECOMMENDING APPROVAL:
HEAD DATE
SERVICE ENTRANCE
RECOMMENDING APPROVAL:
CIRCUIT BREAKER/MAIN SWITCH
SECOND FLOOR
GROUND FLOOR POWER LAYOUT M KILOWATTHOUR METER
S1
S2
S2 RECOMMENDING APPROVAL:
S2 S2 S2
S3
S2
S3 S3
S2 S3
S1
S3
S1
S2
SANITARY
S2
APPROVED:
S2 HEAD DATE
C2
S3S3
C1 RECOMMENDING APPROVAL:
S2
C8
C9
ELECTRICAL
APPROVED:
HEAD DATE
MECHANICAL
APPROVED:
HEAD DATE
FROM THE OFFICE OF: REG. NO: 123456 PROJECT TITLE: OWNER: SHEET CONTENTS SHEET NO:
RECOMMENDING APPROVAL:
LOAD SCHEDULE,230V;60Hz;1"ø;2 WIRE SERVICE ENTRANCE 2-38 THHN IN 2"ø RSCP DATE
HEAD ARCHITECTURAL SECTION
CKT No. FIXTURES DESCRIPTION VOLT WATT AMPS ACB CONDUCTOR CONDUIT
1 19 LIGHTING OUTLET 230V 171 W 0.74 A 15 A 2-2.0mm2THHN 1/2"øPVCP APPROVED:
3
4 1 REFRIGERATOR OUTLET 230V 300 W 1.30 A 20 A 2-3.5mm2THHN 3/4"øPVCP RECOMMENDING APPROVAL:
2
5 1 RANGE HOOD OUTLET 230V 3000 W 13.04 A 30 A 2-5.5mm THHN 3/4"øPVCP 100A
2
6 1(1.5hp) AIRCONDITION UNIT OUTLET 230V 1119 W 4.86 A 30 A 2-5.5mm THHN 3/4"øPVCP
7 1 HEATER OUTLET 230V 3000 W 13.04 A 30 A 2-5.5mm2THHN 3/4"øPVCP 2-38 THHN IN 2"ø PVCP
LAND USE & ZONING
8 12 LIGHTING OUTLET 230V 180 W 0.47 A 15 A 2-2.0mm2THHN 1/2"øPVCP
APPROVED:
9 18 LIGHTING OUTLET 230V 162 W 0.70 A 15 A 2-2.0mm2THHN 1/2"øPVCP
PANEL BOARD/MAIN SWITCH
10 15 CONVINIENCE OUTLET 230V 2700 W 11.74 A 20 A 2-3.5mm2THHN 3/4"øPVCP HEAD DATE
11 1(2hp) AIRCONDITION UNIT OUTLET 230V 1492 W 6.49 A 30 A 2-5.5mm2THHN 3/4"øPVCP 125A
12 1(1.5hp) AIRCONDITION UNIT OUTLET 230V 1119 W 4.86 A 30 A 2-5.5mm2THHN 3/4"øPVCP RECOMMENDING APPROVAL:
LO C1 C2 LO
15A 15A
13 1(1.5hp) AIRCONDITION UNIT OUTLET 230V 1119 W 4.86 A 30 A 2-5.5mm2THHN 3/4"øPVCP
14 1 HEATER OUTLET 230V 3000 W 13.04 A 30 A 2-5.5mm2THHN 3/4"øPVCP CO C3 C4 REF
15 1 HEATER OUTLET 230V 3000 W 13.04 A 30 A 2
2-5.5mm THHN 3/4"øPVCP
20A 20A
LINE AND GRADE
16 SPARE OUTLET 230V RANGE HOOD C5 C6 ACU
30A 30A APPROVED:
HEAD DATE
HEATER C7 C8 LO
30A 15A
RECOMMENDING APPROVAL:
STRUCTURAL
APPROVED:
1. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE. THE RULES, REGULATIONS AND
REQUIREMENTS OF THE LOCAL AUTHORITIES THAT HAVE JURISDICTION OVER THE PROJECT, AND OF THE LOCAL UTILITY COMPANIES FOR ELECTRICAL AND COMMUNICATION.
2. POWER SERVICE TO THE BUILDING SHALL BE 230V, 3ø + GROUND, & 60Hz. RECOMMENDING APPROVAL:
3. UNLESS OTHERWISE INDICATED ALL WIRING METHOD SHALL BE DONE IN THE FOLLOWING MANNER:
A. INTERMEDIATE METAL CONDUIT (IMC) FOR POWER SERVICE ENTRANCE, SUB-FEEDER & ALL EXPOSED WIRING SUBJECT TO MECHANICAL DAMAGE
B. POLYVINYL CHLORIDE (PVC) PIPE FOR CCTV, TELEPHONE SYSTEM & OTHER AUXILIARY SYSTEM
C. ELECTRICAL METALLIC TUBING (EMT) FOR LIGHTING, POWER AND FIRE DETECTION AND ALARM SYSTEM
4. ALL ELECTRICAL MATERIALS/EQUIPMENTS TO BE USED SHALL BE NEW AND OF THE APPROVED TYPE IN ACCORDANCE WITH DRAWINGS & SPECIFICATION, FOR BOTH LOCATION AND PURPOSED.
SANITARY
5. GENERAL USE RECEPTACLE SHAL RATED 15A, 125V/250V, GROUNDINGTYPE WITH PARALLEL SLOTS. SPECIAL PURPOSE OUTLETS SHALL BE OF THE TYPE AND RATING APPROPRIATE FOR THE
APPROVED:
EQUIPMENT TO BE SERVED.
6. SWITCHES FOR LIGHTS SHALL BE RATED 15A, 125V, AC, RATED ONLY. HEAD DATE
7. UNLESS OTHERWISE SPECIFIED IN THE PLANS, THE MINIMUM SIZE OF WIRE AND CONDUIT TO BE USED SHALL BE 3.5mm THHN AND 15mmø CONDUITS,
RESPECTIVELY. ALL WIRES SHALL BE INSULATED FOR 600V EXCEPT AS SPECIFIED IN THE PLAN.
8.WHERE SPARE CIRCUITS ARE INDICATED IN THE SCHEDULE OF PANEL BOARD, THE CONTRACTOR SHALL PROVIDE AN EMPTY CONDUIT STUBBED-OUT INSIDE THE CEILING AND CAPPED. RECOMMENDING APPROVAL:
A. PANELBOARDS, CABINETS & DISCONNECTING SWITCHES 1400mm ABOVE FLOOR FINISH ON CENTER OR AS REQUIRED BY FIELD CONDITION.
B. LIGHT CONTROL SWITCHES 1400mm ABOVE FLOOR FINISH ON CENTER.
C. CONVENIENCE/ TELEPHONE OUTLETS
D. CHIME AND FIRE ALARM BELL
E. OTHERS
300mm ABOVE FLOOR FINSH ON CENTER.
250mm BELOW CEILING @ CENTER.
AS REQUIRED BY EQUIPMENTS SERVED.
ELECTRICAL
10. SIZE AND NUMBER OF WIRES AND CONDUITS FOR ALL AUXILLIARY SYSTEMS SHALL BE VERIFIED FROM THE SUPPLIER PRIOR TO IMMPLEMENTATION.
APPROVED:
11. ALL NON-CURRENT CARRYING METEL PARTS OF ELECTRICAL EQUIPMENT, PANEL BOARD & OTHER DEVICES SHALL BE EFFECTIVELY GROUNDED.
HEAD DATE
12. ALL CIRCUIT BREAKER SHAL BE BOLT ON TYPE WITH 10 KAIC MINIMUM FOR LIGHTING, POWER CIRCUIT & 18 KAIC FOR MOTORS & MAIN CIRCUIT BREAKER,
PLUG-IN CIRCUIT BREAKER ARE NOT ALLOWED.
13. THE ENTIRE ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A COMPETENT LICENSED REGISTERED ELECTRICAL ENGINEER.
RECOMMENDING APPROVAL:
14. WHERE SO REQUIRED, PROVIDE ALL FITINGS/ BOXES FOR ALL SYSTEM ALTHOUGH THEY ARE NOT SHOWN/ MENTIONED ON ALL LAYOUTS.
15. FOR HOMERUNS EXCEEDING 30 METERS, USE THE NEXT HIGHER RATED CONDUCTOR WITH DUE REGARD ON SIZE OF THE CONDUIT RACEWAY SYSTEM.
MECHANICAL
APPROVED:
HEAD DATE
FROM THE OFFICE OF: REG. NO: 123456 PROJECT TITLE: OWNER: SHEET CONTENTS SHEET NO: