Pressure Transmitter (PT) Pressure Differential Transmitter (PDT)

or DP Type PT

• Input:- Pressure • Input:- Pressure


• Output:- 4 to 20 milliampere DC if • Output:- 4 to 20 milliampere DC if
transmitter is HART transmitter is HART
• Use 2-way valve Manifold • Use 3-way or 5-way valve Manifold
• Use Single Impulse tube • Use two Impulse tubes (One for High
• Calibration test equipment- Pressure pressure & Another for Low pressure)
calibrator, 250 Ω load resistance, 24 • Calibration test equipment- Pressure
VDC Power supply, Digital multimeter, calibrator, 250 Ω load resistance, 24
Hart Communicator VDC Power supply, Digital
• Loop test: - Pressure calibrator, Hart multimeter, Hart Communicator
Communicator, Digital Multimeter & • Loop test: - Pressure calibrator, Hart
Loop Folder. Communicator, Digital Multimeter &
Loop Folder.
Pressure Gauge (PG) or Pressure Indicator Pressure Switch High or Low (PSH or
(PI) PSL)

• Input:- Pressure
• Output:- Discrete switching signal
(NO & NC)
• Use 2-way valve Manifold
• Use Single Impulse tube or Line
mounted
• Calibration test equipment- Pressure
• Working principle- Hooke’s Law Calibrator, Digital Multimeter
• Input:- Pressure
• Output:- Pressure display in dial • Loop test: - Pressure Calibrator,
• Use 2-way valve Manifold Digital Multimeter
• Use Single Impulse tube or Line
mounted
• Calibration test equipment- Dead
Weight tester
• Loop test: - No Loop test

Temperature Switch (Contact)


Temperature Gauge (TG) or (TI) Resistance Temperature Detector (RTD)

• Input : Temperature
• Output: Temperature display in dial
• Type: Bi-Metallic
• Calibration Test Equipment: Digital
temperature bath
• Loop test: No loop test

• Input:- Temperature
• Output:- resistance (Ω)
• Use mostly Flanged Thermowell for
installation
• Calibration test equipment- Digital
Temperature Bath, Digital
multimeter,
• Loop test: - Resistance Decade Box,
Digital Multimeter & Loop Folder

If RTD loop is with temperature


transmitter, Hart communicator
will be used in TT.
Thermocouple (T/C) TE

• Input:- Temperature
• Output:- Millivolt (mV) Temperature Transmitter
• Use mostly Flanged Thermowell for • Input:- Millivolt or Resistance
installation • Output:- 4 to 20 Milliampere DC
• Calibration test equipment- Digital • Calibration test equipment-
Temperature Bath, Digital multimeter, Multifunction calibrator-724 or
• Loop test: - Millivolt Simulator, Digital Resistance Decade Box or Millivolt
Multimeter & Loop Folder Simulator, 250 Ω load resistance, 24
VDC Power supply, Digital
If T/C loop is with temperature transmitter, multimeter, Hart Communicator
Loop test: - Multifunction calibrator-724 or
Hart communicator will be used in TT.
Resistance Decade Box or Millivolt
Simulator, Hart Communicator, Digital
Multimeter & Loop Folder.

Temperature Transmitter along with


Temperature Element (RTD or T/C)
Temperature Switch
• Input: Temperature
• Output: Output:- Discrete switching
signal (NO & NC)
• Calibration test equipment- Digital
Temperature Bath, Digital
multimeter,
• Loop test: Jumper & Digital
Multimeter & Loop Folder