KD41 PRESSURE TRANSDUCER

INSTALLATION INSTRUCTIONS

m WARNING! READ m Symptoms of fluid hammer and surge’s


damaging effects:
Mounting
The KD41 transducer requires no spe-

BEFORE INSTALLATION • Pressure transducer exhibits an out-


put at zero pressure (large zero offset).
cial mounting hardware and can be
mounted in any orientation with negli-
gible position error. Although the units
1. GENERAL: • Pressure transducer output remains can with- stand considerable vibration
A failure resulting in injury or dam- constant regardless of pressure without dam- age or significant output
age may be caused by e ­ xcessive • In severe cases, there will be no effects, it is always good practice to
overpressure, excessive vibration output. mount the transducer where there is
or pressure pulsation, excessive minimum vibration. For units with NPT
 REEZING:
F
instrument temperature, corrosion type pressure fittings apply sealing tape
Prohibit freezing of media in pressure
of the pressure containing parts, or or an equivalent sealant to the threads
port. Unit should be drained (mount
other misuse. Consult Ashcroft Inc., before installing. When installing or
in vertical position with electrical ter-
Stratford, Connecticut, USA before removing the unit apply a wrenchto the
mination upward) to prevent possible
installing if there are any questions hex wrench flats, located above the
overpressure damage from frozen
or concerns. pressure fitting. DO NOT tighten by
media.
2. OVERPRESSURE: using a pipe wrench on the housing.
3. STATIC ELECTRICAL CHARGES:
Pressure spikes in excess of the rated A 22mm wrench can be used on the
Any electrical device may be sus-
overpressure capability of the trans- wrench flats of the hex (as per DIN 894
ceptible to damage when exposed
ducer may cause irreversible electrical or similar) with a tightening torque of
to static electrical charges. To avoid
and/or mechanical damage to the ~25Nm (20 ft. lbs.). For KD41 transduc-
damage to the transducer observe the
pressure measuring and containing er with detachable electrical connectors
­following:
elements. a 6-point deep socket can also be used
• Ground the body of the transducer
Fluid hammer and surges can destroy to install the unit.
BEFORE making any electrical
any pressure transducer and must
connections. Electro-Magnetic Interference
always be avoided. A pressure snub-
• When disconnecting, remove the The circuitry of the KD41 transducer
ber should be installed to eliminate
ground LAST! is designed to minimize the effect of
the damaging hammer effects. Fluid
electromagnetic and radio frequency
hammer occurs when a liquid flow Note: The shield and drain wire in the interference. To minimize susceptibility
is suddenly stopped, as with quick cable (if supplied) is not connected to tonoise, avoid running the termination
closing solenoid valves. Surges occur the transducer body, and is not a suit-
when flow is suddenly begun, as when wiring in a conduit which contains high
able ground.
a pump is turned on at full power or a current AC power cables. Where possi-
valve is quickly opened. DESCRIPTION ble avoid running the termination wiring
Liquid surges are particularly damag- The Ashcroft Model KD41 pressure near inductive equipment.
ing to pressure transducers if the pipe transducer is a high performance Field Adjustments
is originally empty. To avoid damaging instrument intended for use in applica- The KD41 transducer is precisely cali-
surges, fluid lines should remain full (if tions where the process media is com- brated and temperature compensated
possible), pumps should be brought patible with 304 SS/PH17-4 or all 316L at the factory to ensure long and stable
up to power slowly, and valves SS (Range dependent). performance. There are no field accessi-
opened slowly. To avoid damage from MECHANICAL INSTALLATION ble adjustments on the KD41 transducer
both fluid hammer and surges, a surge Environmental ELECTRICAL INSTALLATION
chamber should be installed. The KD41 transducer can be stored Please refer to the reverse of this page for
within a temperature limit of -40°C to power supply requirements and for appro-
125°C (-40°F to 257°F) and operated priate wiring protocol based on the partic-
within a temperature limits of -40°C to ular output signal and electrical termina-
105°C (-40°F to 221°F). IP67 (ingress tion features of the unit being installed.
protection) rating applies for most
configurations depending on electrical
connection, install accordingly.

©Ashcroft Inc. 2019, 250 East Main Street, Stratford, CT 06614 USA, Tel: 203-378-8281, Fax 203-385-0402 www.ashcroft.com
All sales subject to standard terms and conditions of sale. All rights reserved. kd41_transducer_i&m_RevA_Ltr_04-05-19
KD41 PRESSURE TRANSDUCER
INSTALLATION INSTRUCTIONS

KD41 ELECTRICAL INSTALLATION


Typical Wiring Diagrams

KD41 POWER SUPPLY REQUIREMENTS

Output Signal Min. Supply Max. Supply

J1939 &CANopen 9Vdc 32Vdc

KD41 ELECTRICAL TERMINATIONS AND WIRING


Connections

Plug M12x1 Cable port

4 3

1 2

Power Power
1: UB+ Red: UB+
2. Can-High Black: UB-
3: UB- White: CAN-High
4: CAN-Low Green: CAN-Low

The electrical connection must be made in


accordance with the respective connection
diagram unless otherwise agreed upon.

©Ashcroft Inc. 2019, 250 East Main Street, Stratford, CT 06614 USA, Tel: 203-378-8281, Fax 203-385-0402 www.ashcroft.com