GENERATOR CRANKING TEST REPORT 2020

BATTERY OPTIMA RED TOP 34 MODEL


CAPACITY 24V 150AH 12V 50AH X 6 UNITS
CONNECTION PARALLEL & SERIES
GENERATOR MODEL PERKINS 1250KVA CAPACITY
90 SECS CRANKING RULES ( 15secs x 6 times )
CRANK 15 secs and rest 10 secs and contiune for 6 times ( 7th attempt must be able to start the Generator )

CRANK BREAKAWAY CRANKING REMARKS


NUMBER VOLTAGE VOLTAGE
TESTED ON 27TH MAY 2020
STARTING 25.36V 25.36V
STANDARD REQUIREMENT FROM
1ST CRANK 19.68V 22.86V FIRE DEPARTMENT ( MALAYSIA )

2ND CRANK 19.53V 22.91V BREAKAWAY VOLTAGE MIN 14.4V


CRANKING VOLTAGE MIN 21.0V
3RD CRANK 19.53V 22.91V

4TH CRANK 19.53V 22.92V OPTIMA BATTERY MEET BOTH REQUIREMENT

5TH CRANK 19.53V 22.91V

6TH CRANK 19.49V 22.90V

7TH START 19.49V 23.80V

PREPARED BY : FEATURE :
1) SPIRALCELL TECHNOLOGY
YACHT BATTERY DISTRIBUTOR 2) 99.99 % PURE LEAD
3) VIBRATION REISITANCE
4) HIGH OUT PUT 1000CA
5) MAINTENANCE FREE
6) SAFETY ENVIROMENT