Measurements

 of  individual  chiller  systems  compared  to  


District  Cooling  solu8ons    
 

Johannes  Jungbauer  
European  Affairs  Officer  
Johannes.jungbauer@euroheat.org      
   
Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
Before  we  start…  

Reduce  

Recycle  

Replace    

Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
Introduc8on  

Why  did  we  conduct  study?  


 
A  growing  demand  for  air-­‐condi:oning    
 
A  central  requirement:  Energy  Efficiency  
 
Energy  Efficiency  raises  two  ques:ons:  
•  Measure  and  control  the  efficiency  of  exis:ng  systems  
•  Develop  ever  more  energy  efficient  systems  
 
A  common  issue:  
•How  to  measure  effec8ve  energy  efficiency  of  a  chilled  water  produc8on  system  ?  
•Lack  of  informa8on  

Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
Exis8ng  Indicators…  

Nominal  COP  /  EER  :  performance  energy  indicators  as  defined  by    


Available  

     manufacturers  based  on  nominal  working  condi:ons  


 

 
ESEER  /  SEER  :      Nomina:ve  performance  energy  indicators  taking  
     into  account  par:al  loading  rates  (seasonal)  

to  be  compared  with  real  measures  


Measured  COP  /  EER  :    Cooling  energy  produced  along  the  year,  compared  
     to  all  energy  used  in  produc:on  system  

Problem  is…  lack  of  measures  !  

Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
Yearly  efficiency  of  cooling  system  

Chiller  +  addi:onal  
equipments  

Chiller  

COP  

EER  

SEER  

Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
Instrumenta8on  and  measures  on  a  series  of  
chilled  water  produc8on  systems  
•    12  chilled  water  plants    
• 7  in  Paris  (France),  4  in  Helsinki  (Finland),  1  in  Gothenburg  (Sweden)  
• Performance  measurements  carried  out  over  a  long  period  of    8me  (minimum  
one  year)  
• e.g.  Hospitals,  Banks,  Museum,  Commercial  buildings  

•    Range  of  cooling  power  


• 100  to  1500  kW    

•    Measurements  equipments  (per  instrumented  plant)  


• Data  acquisitors  
• Flow  meters  
• Waa  meters  
• Temperature  sensors  

Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
Methods  used  for  measuring  
Condensor
power

Electrical Evaporator
power power

• Measurement of all electrical consumption of each machine

• Measurement of all thermic power exchanged

• Recording of values every 10 minutes

Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
Some  measurements…  
Results A Results B
4 4

EER and Nb of chillers


40%
EER and nb of chillers

40%
3 3

Loading rate
Loading rate
30% 30%

2 2
20% 20%

1 10% 1 10%

0 0% 0 0%

July

Nov.
June
Janu-08

Janu-09
Aug.
July

May
March

March
Nov.

Oct.

Dec.
Apr.
Feb.

Feb.
Sept.
June
Janu-08

Janu-09
Aug.
May
March

March
Oct.

Dec.
Apr.
Feb.

Sept.

Feb.
EER Nb of chillers Loading rate Nb of chillers EER Loading rate

Results C Results D
EER and Average nb of

4 4

EER and nb of chillers


40% 40%
3
Loading rate
3

Loading rate
30% 30%
chillers

2 20% 2
20%
1 10% 1 10%
0 0% 0 0%
nov.

June
Janu-09

May
March
aug-08

April
oct.
sept.

dec.

Feb.

Nov.

June
Janu-09

May
March
Aug-08

April
Oct.

Dec.

Feb.
Sept.
EER Nb of chillers Loading rate EER Average nb of chillers Loading rate

Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
Synthe8c  results    

EER

Strong  disparity  between  measurements  carried  out  and  chillers  nominal  


performances  

All  indicators  tell  the  truth…  but  not  the  same  truth  

Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
Distribu8on  of  electrical  energy  consump8on  

Other
9%

Condensor
Chillers
pumps
51%
8%

Evaporator
primary pumps
19%

Cooling towers
13%

Chillers  :  only  51%  of  the  total  energy  consump8on  

Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
2  
Energy  to  other  systems  mul:plied  by  PEF  
of  replaced  energy  (The  result  is  replaced  
primary  energy)  

1  
Every  different    
energy  mul:plied  by          PEF  (heat)            PEF  (elect.)            PEF  (fuel)  
 
its  own  PEF    
  3  
Electricity   Heat   Elect.   Fuel   Cooling  energy  sold  to  
PEF  (elect.)   the  customers  
Cold   Energy  out  that  replaces  
Primary  
PEF  (cold)   energy  
energy  supply  in  other  
Heat   systems  
to  DC  
PEF  (heat)   system   District  cooling    
Fuel   PEF  (fuel)                                            system  
 

1   -­‐   2  
Primary  energy  in  to    
the  DC  system   -­‐   Replaced  primary  energy  
in  other  systems  
PEF  =     =    
Cooling  energy  sold  to  the  
3   customers  
Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
District  Cooling  results  
  1  

0,9  

0,8  

0,7  
PEF  value  

0,6  

0,5  

0,4  

0,3  

0,2  

0,1  

0  
Helsinki   Gothenburg   Barcelona   Vienna   Copenhagen  
District  Cooling    

Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
Considering  a  standard  primary  energy  factor  of  
2.5  for  electricity  the  EER  of  individual  systems  is  
converted  into  PEF  
 
 

1  
PEF  =     X   2.5  
EER  

Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
District  Cooling  compared  to  individual  chiller  systems  

3,5  

3  

2,5  
PEF  value  

2  

1,5  

1  

0,5  

0  
Helsinki  

Barcelona  

Helsinki  D  
Vienna  

Paris  D  
Copenhagen  

Paris  A  
Gothenburg  

Helsinki  A  
Paris  B  

Helsinki  B  

Paris  C  

Helsinki  C  
District  Cooling     Individual  chiller  

Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  
Conclusions  
•  Real  Energy  Efficiency  calcula:on:  requires  measurements  
carried  out  over  a  long  period  of  :me  (min  1  year)  
•  Lack  of  measurement  instruments  on  most  of  the  
installa:ons  
•Large  impact  of  opera:ng  paYerns  on  effec:ve  
performances  
•  Chillers  represent  only  50  %  of  the  global  consump:on  
•District  Cooling  Installa:ons  are  more  efficient  than  
individual  solu:ons  
•Lack  of  informa:on  has  sever  consequences  

Energy efficiency requires instrumentation,


measurements and accurate operations
Measurements  of  individual  chiller  systems  compared  to  District  Cooling  solu8ons  -­‐  eceee  Summer  Study  2011  