Note Unit shall be supplied by a power source which complies with the requirements of
a limited-energy circuit in accordance with IEC/EN/UL/CSA 61010-1 or a Limited
You can find detailed specifications for the product, the device description file Power Source (LPS) in accordance with IEC/EN/UL/CSA 60950-1 or IEC/EN/UL/
(IODD) with a description of the IO-Link parameters and the declaration of con CSA 62368-1 or a Class 2 circuit in accordance with NEC or CEC.
formity at: è www.festo.com/sp.
3 Function and application
1.1 Overview The sensor converts pneumatic pressure values (relative pressure) into electrical
signals, which can be used for control or regulating functions. Measurements are
1 carried out using a piezoresistive sensor element with a following electronic evalu
2 ation unit. Interfacing to the higher-level system is provided by 1 or 2 switching
outputs, an optional analogue output and an optional IO-Link interface.
The switching outputs can be configured for monitoring of a threshold value,
a pressure range or a differential pressure. The outputs can be set as PNP or NPN
3 and normally open (NO) or normally closed (NC). Via the IO-Link interface, process
values can be read out and parameters changed and transmitted to additional
devices.
Fig. 2
Window comparator for monitoring of a pressure range _|¯|_ 4.1 Mechanical and pneumatic
Function NO (normally open) NC (normally closed)
Switching function: Out Out Note
– 2 Switching points HY HY HY HY An unfavourable mounting position can impair the function of the product.
(SP.Lo, SP.Hi) 1 1
Mount the sensor so that no condensate from the compressed air lines can
TEACH mode1): gather in the device.
0 p 0 p
– 2 teach-in points (TP1, TP2) Install the sensor so that it cannot be heated above the maximum permissible
TP1=SP.Lo TP2=SP.Hi TP1=SP.Lo TP2=SP.Hi
– TP1 = SP.Lo, TP2 = SP.Hi operating temperature (plan for convection possibilities).
1) SP.Lo = smaller pressure/vacuum value, SP.Hi = larger pressure/vacuum value, dependent on the
Teach sequence
SPAN-...-G18M/R18M/N18M Mounting bracket
Fig. 6
– Seal connecting thread.
31 -0.4 X
31 -0.4
1
31 -0.4
X=31*n+3.5*(n-1)
1 Reference value is determined 2
2 Measured value deviates by [d.SP] from the reference value
3 Monitoring area
Fig. 7 1 Panel frame
2 Clamping element
The parameters [SP.Lo], [SP.Hi], [t.obS] and [d.SP] can be configured by the user.
Fig. 11 Fig. 12
The greater [t.obS] is set, the more constant the pressure signal must be to establish
the reference value PRef.
4.2 Electrical
Function NO (normally open) NC (normally closed)
Switching function: Out Out Warning
d.SP d.SP
– 2 switching points (SP.Lo,
1 1 Use only power sources which guarantee reliable electrical isolation of the oper
SP.Hi) for setting the valid
work range ating voltage in accordance with IEC/EN 60204-1. Consider also the general
– 1 switching point (d.SP) requirements for PELV circuits in accordance with IEC/EN 60204-1.
0 p 0 p
for determination of
SP.Lo PRef SP.Hi SP.Lo PRef SP.Hi
the monitoring area Connect sensor.
TEACH mode1):
– Consider the maximum permissible line length: 30 m (20 m for IO-Link).
– 2 teach-in points (TP1, TP2) Pin Colour1) Allocation Plug L1
– TP1 = SP.Lo, TP2 = SP.Hi
1 Brown (BN) Operating voltage +24 V DC 1 2 3 4
1) SP.Lo = smaller pressure value, SP.Hi = larger pressure value, independent of the Teach sequence
2 Black (BK) Switching output OutA or IO-Link
Fig. 8 (C/Q line)
3 White (WH) Switching output OutB or
analogue output (pressure
4 Installation
signal InA)
4 Blue (BU) 0V
Note
1) Colours apply for connecting cables NEBS-L1... or electrical adapter SASC-P4... with NEBU-M8...
Installation and commissioning are to be carried out only by qualified personnel Fig. 13
in accordance with the operating instructions.
Circuit diagrams
Remove all transport packaging. The material used in the packaging has been
specifically chosen for its recyclability. SPAN-...-PNLK-PNVBA SPAN-...-PN-PN
Fig. 14 Fig. 15
5 Commissioning [OFF] [Z.AdJ] [OFF] = zero point synchronisation (zero adjust)
deactivated
5.1 LCD display
[ON] = offset correction for measured value indicator,
switching points and analogue output possible
1 1 [Unit] [Sub.d] Settings of the lower display in RUN mode: selected unit
or switching point of OutA or bar graph
[40] [Eco] / [SEC] Economy mode: period after which the display
2 background lighting is switched off
[PNP] [bin] / [Out] Shift of the switching outputs (binary) between PNP and
NPN
3 [bin] [Pin3] / [Out] Shift between switching output (binary) and analogue
output (lnA) at Pin3
[OFF] [Code] Activation and determination of the security code
[OFF] [MASt] Activation of the IO-Link master function for replication of
parameters
5 4
Fig. 18
Note
The process is the same for configuring the switching outputs for OutA and
OutB. In the following, the process is described using the switching output OutA.
Menu structure è Fig. 21.
Master-Sensor Device-Sensor
Requirement: The sensor is ready for operation (RUN mode).
Fig. 20
Set threshold value comparator _I¯, window comparator _I¯I_, auto difference
monitoring d_I¯I_ 1. Select special menu [Spec] at the master sensor via device settings.
1. Press the Edit button briefly. 2. Press the Edit button briefly until [MASt] appears.
è [Edit] appears. [OutA] flashes. 3. With A or B key, select [ON].
2. Press the Edit button briefly. 4. Press the Edit button
è [Fctn] flashes. è [REPL] / [RedY] appears.
3. With A or B key, select _I¯ or _I¯I_ or d_I¯I_. 5. Press A- or B-key.
4. Press the Edit button briefly. è [REPL] / [RUN] appears briefly.
è The set value is saved. è The parameters are transmitted to the device sensor.
è The next adjustable parameter is shown. è [REPL] / [RedY] appears.
5. Set parameters with A- or B-key. If an error occurs, an error message appears (è Fig. 22).
6. Repeat points 4 and 5 until all parameters are set.
6. Repeat point 5 if an additional sensor should be parameterised.
7. Press the Edit button.
7. Press the Edit button briefly.
è Switch to the RUN mode.
è Switch to the RUN mode.
– Switching functions è Chapter 3.2
SP SP.Lo SP.Lo 0…60…100 % FS1) In.Hi 10…100 % FS Unit bar, kPa, MPa, PSI, MMHG, inHG, iH20, kGF
t.obS 5…200…9999 ms Eco di.ON, 5, 10, 20, 40, 80, 160, 320, 640 s
MASt OFF, ON
Note
7 Maintenance and care
There is no Timeout in the TEACH mode. The sensor changes to the RUN mode 1. Switch off the energy sources (operating voltage, compressed air).
only after the entire teach process is ended. 2. Clean sensor with non-abrasive cleaning agents.
No display No operating voltage or Apply permissible operating Protection against polarity reversal All connections against each other
impermissible operating voltage voltage Mechanical system
Electrical connections swapped Connect the device in accordance Mounting position Any, avoid condensation gathering in the sensor
with the circuit diagram Housing material PA reinforced
Device defective Replace device Keyboard material TPE-O
Display or Short circuit or overload at the Eliminate short circuit or overload Threaded connections material Brass (nickel-plated)
switching output output
Display
does not react in Incorrect switching point taught Repeat teaching procedure
accordance with Displayable units bar, kPa, MPa, psi, mmHg, inchHg, inchH2O,
(e.g. at 0 bar)
the settings kgf/cm2
Device defective Replace device
Immissions / emissions
Parameter incorrect Reset to factory settings
Storage temperature [°C] –20 … +80
[Er01] / [FAIL] 1) Device defective Replace device
Max. permissible relative air [%RH] 85
[Er02] / [ASIC] 1) Device defective Replace device humidity
[Er10] / [OVER] Measuring range exceeded Comply with the measuring range Degree of protection (in IP40
[Er20] / [tEMP] 2) Temperature error Check operating conditions accordance with EN 60529)
Replace device Protection class (in accordance with DIN III
[Er21] / [SHRt] 2) Short circuit at OutA Eliminate short circuit VDE 0106-1)
[Er22] / [SHRt] 2) Short circuit at OutB Eliminate short circuit Resistance to shocks (in accordance with 30 g acceleration with 11 ms duration
EN 60068-2) (half-sine)
[Err] / [BUSY] OutA is switched active Check device settings
Vibration resistance (in accordance with 10 … 60 Hz: 0.35 mm / 60 … 150 HZ: 5 g
[Err] / [ID] Device ID error, When replicating, use sensors with
EN 60068-2)
replication function failed the same type (same device ID)
[Err] / [COMM] IO-Link communication error Check line OutA 1) After this time, the electrical outputs take a defined, stable condition
Check settings of the device sensor Fig. 23
1) Display flashes red
2) Display illuminated red
SPAN- -B2 -B11 -V025 -V05 -V1 -P025 -P05
Fig. 22
Pressure measuring [bar] -1 0
range [MPa] -0.1 0
10 Accessories Start value
Accessories: è www.festo.com/catalogue Pressure measuring [bar] 1 10 -0.25 -0.5 -1 0.25 0.5
11 Technical data range [MPa] 0.1 1 -0.025 -0.05 -0.1 0.025 0.05
End value
SPAN- Overload range [bar] -1
General Start value [MPa] -0.1
Approval certificate c UL us – Listed (OL) Overload range [bar] 5 15 1 2 5 1 2
RCM End value [MPa] 0.5 1.5 0.1 0.2 0.5 0.1 0.2
Switching function Threshold value comparator Pressure differential max. 1.6 MPa
Window comparator Ambient temperature max. 50 °C /122 °F
Auto difference monitoring Pollution degree 3
Switch-on/switch-off time [ms] typ.: 2, max.: 4 with FILT = OFF Max. permissible relative humidity 85 %
Max. output current [mA] 100 Only for indoor use.
Capacitive load maximum DC [nF] 100 Altitude up to 2000 m. Altitude up to 2000 m or above 2000 m if specified by the manufacturer.
Voltage drop [V] Max. 2
Fig. 26
Pull-down resistor integrated (PNP)
Pull-up resistor not integrated (NPN)
Inductive protective circuit Present IO-Link1)
Analogue output Protocol version Device V1.1
Output characteristic curve [V] 0 … 10 Profiles Smart sensor profile
initial value … end value [V] 1…5 Function classes Binary data channel (BDC)
[mA] 4 … 20 Process data variable (PDV)
Max. load resistance of current [Ω] 500 Identification
output Diagnostics
Teach channel
Min. load resistance of voltage [kΩ] 20
output Communication mode COM2 (38.4 kBaud)
Output, additional data Port class A
Short circuit protection Yes Process data width IN 2 byte
Overload protection Present Process data content IN 2 bit BDC (pressure monitoring)
Electronics 14 bit PDV (pressure reading)
Max. current consumption [mA] 230 IODD, IO-Link device description è www.festo.com/sp