2 Safety

Pressure sensor SPAN Intended use


The pressure sensor SPAN is intended for monitoring pressure of compressed air
and inert gases in the piping.

General safety information


 Only use the product in its original status, without any unauthorised modifications.
 Only use the product if it is in an excellent technical status.
 The product is intended for use in industrial environments. Measures may need
Festo SE & Co. KG to be implemented in residential areas for radio interference suppression.
 Take into consideration the ambient conditions at the location of use.
Ruiter Straße 82  Operate the product only with compressed air of the specified air quality class
73734 Esslingen (è Technical data).
Germany  Observe the specifications on the rating plate.
+49 711 347-0  Comply with all applicable national and international regulations.
www.festo.com
Disposal
Operating instructions 8035566  Observe the local specifications for environmentally friendly disposal.
2017-11a
[8035568] Range of applications and certifications
In connection with the UL marking on the product, the information of this section is
also applicable for compliance with the certification conditions of Underwriters
Laboratories Inc. (UL) for the U.S.A. and Canada.
Translation of the original instructions
UL approval information
Product category code QUYX (USA)
Pressure sensor SPAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . English QUYX7 (Canada)
File number E322346
For all available product documentation è www.festo.com/pk
Considered standards UL 61010­1
C22.2 No. 61010­1
UL mark
1 Product description
The operating instructions describe the entire function range. The function range is
limited, depending on the product variant. Fig. 3

Note Unit shall be supplied by a power source which complies with the requirements of
a limited-energy circuit in accordance with IEC/EN/UL/CSA 61010-1 or a Limited
You can find detailed specifications for the product, the device description file Power Source (LPS) in accordance with IEC/EN/UL/CSA 60950-1 or IEC/EN/UL/
(IODD) with a description of the IO-Link parameters and the declaration of con­ CSA 62368-1 or a Class 2 circuit in accordance with NEC or CEC.
formity at: è www.festo.com/sp.
3 Function and application
1.1 Overview The sensor converts pneumatic pressure values (relative pressure) into electrical
signals, which can be used for control or regulating functions. Measurements are
1 carried out using a piezoresistive sensor element with a following electronic evalu­
2 ation unit. Interfacing to the higher-level system is provided by 1 or 2 switching
outputs, an optional analogue output and an optional IO-Link interface.
The switching outputs can be configured for monitoring of a threshold value,
a pressure range or a differential pressure. The outputs can be set as PNP or NPN
3 and normally open (NO) or normally closed (NC). Via the IO-Link interface, process
values can be read out and parameters changed and transmitted to additional
devices.

3.1 Operating statuses


6 5 4

Operating status Function


1 Display 4 B-key
RUN mode – Basic status after the operating voltage is switched on
2 Electrical connection 5 Edit button – Display of the current measured value
3 Pneumatic connection 6 A-key SHOW mode – Display of the current settings
Fig. 1 Representation of other variants can deviate from this EDIT mode – Setting or modification of parameters
TEACH mode – Acceptance of the current measured value to determine switching
1.2 Characteristics points

Characteristic Value Description Fig. 4


Type SPAN Pressure sensor
Pressure -B2, -B11, -P025, -P05, -P1, -P2, è Technical data 3.2 Switching functions
measuring range -P6, -P10, -P12, -P16, -V025,
Threshold value comparator for monitoring of a pressure threshold _|¯
-V05, -V1
Supply port R Relative pressure Function NO (normally open) NC (normally closed)
Pneumatic port -G18, -R18, N18, -M5, Thread Gx, Rx, NPTx, M5 Switching function: Out Out
-Q4, Push-in connector 4 mm – 1 switching point (SP) HY HY
1 1
Thread type None
M Male thread TEACH mode:
F Female thread – 2 teach-in points (TP1, TP2) 0 p 0 p
– SP = ½ (TP1+TP2)
Electrical -PNLK Switching output PNP / NPN / IO-Link TP1
SP
TP2 TP1 SP TP2
output 1 -PN PNP / NPN
Electrical -PNVBA PNP / NPN / 0…10 V / 1…5 V / 4…20 mA Fig. 5
output 2 -PN PNP / NPN
Electrical -L1 Plug connector, design L1
connection
Certificate Without
+T With inspection report

Fig. 2
Window comparator for monitoring of a pressure range _|¯|_ 4.1 Mechanical and pneumatic
Function NO (normally open) NC (normally closed)
Switching function: Out Out Note
– 2 Switching points HY HY HY HY An unfavourable mounting position can impair the function of the product.
(SP.Lo, SP.Hi) 1 1
 Mount the sensor so that no condensate from the compressed air lines can
TEACH mode1): gather in the device.
0 p 0 p
– 2 teach-in points (TP1, TP2)  Install the sensor so that it cannot be heated above the maximum permissible
TP1=SP.Lo TP2=SP.Hi TP1=SP.Lo TP2=SP.Hi
– TP1 = SP.Lo, TP2 = SP.Hi operating temperature (plan for convection possibilities).
1) SP.Lo = smaller pressure/vacuum value, SP.Hi = larger pressure/vacuum value, dependent on the
Teach sequence
SPAN-...-G18M/R18M/N18M Mounting bracket
Fig. 6
– Seal connecting thread.

Auto difference monitoring d_|¯|_


This funciton permits monitoring of a pressure value for constancy.
13 mm
If the applied pressure is constant in the range between [SP.Lo] and [SP.Hi], the refer­ @ 3,3 mm
ence pressure PRef is automatically determined. The result is a switching operation at
max. 10 Nm
the output. The signal change signals the start of pressure monitoring.
If the pressure remains in the monitoring range [d.SP] around PRef, the pressure is
stable. When the monitoring range is left (e.g. caused by a leakage in the system), max. 0,5 Nm
the output switches back.
1 2

Fig. 9 Example with G18M Fig. 10 Example with SAMH-PU-A-. Fastening


3 SAMH-PN-W correspondingly

Front panel use SAMH-PN-F


– Size of the front panel cut-out in mm è Fig. 11.
– Fasten panel frame to the sensor.
– Guide sensor from the front into the cut-out on the front panel.
– Attach the clamping element and press until it catches.
s=max. 5 mm

31 -0.4 X

31 -0.4
1
31 -0.4

X=31*n+3.5*(n-1)
1 Reference value is determined 2
2 Measured value deviates by [d.SP] from the reference value
3 Monitoring area
Fig. 7 1 Panel frame
2 Clamping element
The parameters [SP.Lo], [SP.Hi], [t.obS] and [d.SP] can be configured by the user.
Fig. 11 Fig. 12
The greater [t.obS] is set, the more constant the pressure signal must be to establish
the reference value PRef.
4.2 Electrical
Function NO (normally open) NC (normally closed)
Switching function: Out Out Warning
d.SP d.SP
– 2 switching points (SP.Lo,
1 1 Use only power sources which guarantee reliable electrical isolation of the oper­
SP.Hi) for setting the valid
work range ating voltage in accordance with IEC/EN 60204-1. Consider also the general
– 1 switching point (d.SP) requirements for PELV circuits in accordance with IEC/EN 60204-1.
0 p 0 p
for determination of
SP.Lo PRef SP.Hi SP.Lo PRef SP.Hi
the monitoring area  Connect sensor.
TEACH mode1):
– Consider the maximum permissible line length: 30 m (20 m for IO-Link).
– 2 teach-in points (TP1, TP2) Pin Colour1) Allocation Plug L1
– TP1 = SP.Lo, TP2 = SP.Hi
1 Brown (BN) Operating voltage +24 V DC 1 2 3 4
1) SP.Lo = smaller pressure value, SP.Hi = larger pressure value, independent of the Teach sequence
2 Black (BK) Switching output OutA or IO-Link
Fig. 8 (C/Q line)
3 White (WH) Switching output OutB or
analogue output (pressure
4 Installation
signal InA)
4 Blue (BU) 0V
Note
1) Colours apply for connecting cables NEBS-L1... or electrical adapter SASC-P4... with NEBU-M8...
Installation and commissioning are to be carried out only by qualified personnel Fig. 13
in accordance with the operating instructions.
Circuit diagrams
 Remove all transport packaging. The material used in the packaging has been
specifically chosen for its recyclability. SPAN-...-PNLK-PNVBA SPAN-...-PN-PN

Fig. 14 Fig. 15
5 Commissioning [OFF] [Z.AdJ] [OFF] = zero point synchronisation (zero adjust)
deactivated
5.1 LCD display
[ON] = offset correction for measured value indicator,
switching points and analogue output possible
1 1 [Unit] [Sub.d] Settings of the lower display in RUN mode: selected unit
or switching point of OutA or bar graph
[40] [Eco] / [SEC] Economy mode: period after which the display
2 background lighting is switched off
[PNP] [bin] / [Out] Shift of the switching outputs (binary) between PNP and
NPN
3 [bin] [Pin3] / [Out] Shift between switching output (binary) and analogue
output (lnA) at Pin3
[OFF] [Code] Activation and determination of the security code
[OFF] [MASt] Activation of the IO-Link master function for replication of
parameters
5 4
Fig. 18

1 Output display 3 Status information


2 Main display (e.g. measured 4 Lower display (e.g. unit) 5.2 Switch on sensor (RUN mode)
value) 5 Signal indicator  Switch on the operating voltage.
è Current measured value is displayed. The sensor is in the basic status
Fig. 16
(RUN mode).
The basic status can be reached from other modes by:
Example for Meaning
– pressing edit button for 3 seconds
LCD display
– expiration of a monitoring time (Timeout)
Output display
[OutA] Switching output OutA selected (flashes with active IO-Link)
5.3 Displaying parameters (SHOW mode)
[OutA] Switching output OutA set
Requirement: The sensor is ready for operation (RUN mode).
[OutB] Switching output OutB selected
Switching output OutA
[OutB] Switching output OutB set
 Press A-key.
Status information / signal indicator
è The first parameter set is displayed. [Fctn] flashes.
[Lock] Security code activated ( è Chap. 5.4)
The subsequent parameters can be displayed by repeatedly pressing the A key
[Spec] Special menu selected ( è Chap. 5.6)
(è Fig. 19).
[InA] Pressure signal InA or analogue signal is selected
è At the end, the min. and max. values are displayed. This can be reset with
IIIIIIII Graphic bar graph in the lower display [Sub.d]
the Edit key.
Fig. 17
Switching output OutB or analogue output for pressure signal InA
Example for LCD display Meaning  Press B-key.
Main display Lower display è The first parameter set is displayed. [Fctn] with OutB or [Out] with InA
Measured value indicator and unit in the RUN mode
flashes.
[– 0.53] [bar] Measured value indicator (here: negative value) and unit The subsequent parameters can be displayed by repeatedly pressing the B-key
Menu for the switching outputs (OutA and OutB) (è Fig. 19).
[Edit] [bin] Edit menu for the switching outputs (binary) Measured value indicator (RUN mode)
[Fctn] Threshold value comparator OutA or OutB InA1)
[Fctn] Window comparator (Switching output) (Analogue
output)
d [Fctn] Auto difference monitoring
[1.80] [SP] Value of switching point (only for threshold value
comparator) _|¯ _|¯|_ d_|¯|_ Out
[2.45] [SP.Lo] Value of lower switching point Fctn Fctn Fctn
[6.45] [SP.Hi] Value of upper switching point
[0.50] [HY] Value of hysteresis
SP SP.Lo SP.Lo In.Hi
[18] [t.obS] / [MSEC] Time interval for determination of a mean value, which is
used to determine the pressure change and establish the
reference value.
HY SP.Hi SP.Hi In.Lo
[0.25] [d.SP] Threshold value of the differential pressure with auto
difference monitoring
[NO] [LOGC] Switching characteristics: HY t.obS
[NO] = normally open, [NC] = normally closed
[bLUE] [COLR] Display colour:
[bLUE] = Blue, colour change function deactivated d.SP
[R.ON] = Red, if switching output set
[R.OFF] = Red, if switching output not set
Note: Independent of the settings [COLR], the red colour LOGC LOGC LOGC
change appears with some malfunctions.
Extreme values (only SHOW mode)
[1.64] [MIN] Minimum measured pressure since switch-on or the last COLR COLR COLR
reset
[8.50] [MAX] Maximum measured pressure since switch-on or the last
reset MIN MIN MIN Reset
Menu of the pressure signal (InA)
[Edit] [ANLG] Edit menu for the analogue output MAX MAX MAX Reset
[1 _ 5] [Out] / [V] Output function of the analogue output
[93] [In.Hi] / [%] Scaling of the analogue output in percent of the final
value of the pressure measuring range Measured value indicator (RUN mode)
[3] [In.Lo] / [%] Scaling of the analogue output in percent of the initial
value of the pressure measuring range MIN, MAX: Parameter is displayed only for switching output OutA,
Menu for device settings (Spec) without Timeout
[Edit] [MENU] Edit menu for additional settings Edit button
[16] [Filt] / [MSEC] Value of the filter time constant for the pressure A or B key
measurement signal
1) Only SPAN-...-PNLK-PNVBA; via B-key
[bar] [Unit] Unit for the pressure indicator
Fig. 19
5.4 Enter the security code (EDIT mode) 5.8 Replicating parameters (EDIT mode)
Requirement: The sensor is ready for operation (RUN mode). Requirement:
1. Press the Edit button. – The pre-configured sensor (master sensor) is ready for operation (RUN mode).
è The EDIT mode is active. If the security code is activated, the parameter – Master sensor and device sensor have the same design regarding the paramet­
entry option is blocked: [Lock] flashes. ers (same device ID).
2. Enter security code set with A or B key. – The master sensor is connected with the device sensor (è Fig. 20).
3. Press the Edit button briefly. – Parameterisation of the device sensor must not be blocked via IO-Link®.
è [OutA] flashes. The parameter entry option is unblocked. – The device sensor is in an unswitched status (switching output PNP, display
OutA off ).

5.5 Configuring switching output (EDIT mode) Power supply

Note
The process is the same for configuring the switching outputs for OutA and
OutB. In the following, the process is described using the switching output OutA.
Menu structure è Fig. 21.
Master-Sensor Device-Sensor
Requirement: The sensor is ready for operation (RUN mode).
Fig. 20
Set threshold value comparator _I¯, window comparator _I¯I_, auto difference
monitoring d_I¯I_ 1. Select special menu [Spec] at the master sensor via device settings.
1. Press the Edit button briefly. 2. Press the Edit button briefly until [MASt] appears.
è [Edit] appears. [OutA] flashes. 3. With A or B key, select [ON].
2. Press the Edit button briefly. 4. Press the Edit button
è [Fctn] flashes. è [REPL] / [RedY] appears.
3. With A or B key, select _I¯ or _I¯I_ or d_I¯I_. 5. Press A- or B-key.
4. Press the Edit button briefly. è [REPL] / [RUN] appears briefly.
è The set value is saved. è The parameters are transmitted to the device sensor.
è The next adjustable parameter is shown. è [REPL] / [RedY] appears.
5. Set parameters with A- or B-key. If an error occurs, an error message appears (è Fig. 22).
6. Repeat points 4 and 5 until all parameters are set.
6. Repeat point 5 if an additional sensor should be parameterised.
7. Press the Edit button.
7. Press the Edit button briefly.
è Switch to the RUN mode.
è Switch to the RUN mode.
– Switching functions è Chapter 3.2

5.6 Change device settings (EDIT mode)


Requirement: The sensor is ready for operation (RUN mode).
1. Press the Edit button briefly.
è [Edit] appears. [OutA] flashes.
2. With A or B key, select special menu [Spec].
è [Spec] flashes.
3. Press the Edit button briefly.
è [Filt] flashes.
4. Set parameters with A- or B-key.
5. Press the Edit button briefly.
è The set value is saved
è The next adjustable parameter is displayed.
6. Repeat points 4 and 5 until all parameters are set.

5.7 Set analogue output (EDIT mode)


Requirement: The sensor is ready for operation (RUN mode).
1. Press the Edit button briefly.
è [Edit] appears. [OutA] flashes.
2. Select [InA] with the A-key or B-key.
è [Edit] appears. [InA] flashes.
3. Press the Edit button briefly.
è [Out] flashes.
4. Set parameters with A- or B-key.
5. Press the Edit button briefly.
è The set value is saved.
è The next adjustable parameter is shown.
6. Repeat points 4 and 5 until all parameters are set.
7. Press the Edit button.
è Switch to the RUN mode.
5.9 Menu structure

Measured value indicator (RUN mode)


2)

OutA OutB InA Spec


Edit Edit Edit Edit
bin bin ANLG MENU

_|¯ _|¯|_ d_|¯|_ Out 0…10 V Filt OFF, 2, 4, 8, ... 1024 ms


Fctn Fctn Fctn 1…5 V
4…20 mA

SP SP.Lo SP.Lo 0…60…100 % FS1) In.Hi 10…100 % FS Unit bar, kPa, MPa, PSI, MMHG, inHG, iH20, kGF

SP.Hi SP.Hi 0…70…100 % FS1) In.Lo 0…90 % FS Z.AdJ OFF, ON3)

HY HY 0…0.5…90 % FS1) Sub.d Unit, SP, SP.Lo, SP.Hi, d.SP, || || || ||

t.obS 5…200…9999 ms Eco di.ON, 5, 10, 20, 40, 80, 160, 320, 640 s

d.SP 0.5…2 …50 % FS1) Out PNP, NPN


bin

LOGC NO, NC Out bin, ANLG2)


Pin3

COLR bLUE, R.OFF, R.ON Lock Code OFF, 1…9999

MASt OFF, ON

Measured value indicator (RUN mode)


= Edit button
= A- or B-key 1) The values refer to the respective measuring range. The display takes place in the selected unit.
2) Not applicable with PN-PN variant
bold = factory setting 3) Not valid with -B2 and -B11 variant (factory setting ON)
Fig. 21

5.10 Zero point synchronisation (zero adjust) 6 Operation


Requirement:
– The sensor is ready for operation (RUN mode).
Caution
– [Z.AdJ] [ON] is set (è Chap. 5.6).
– The measured value lies in the range 0 bar ± 3 % FS. Property damage due to high temperatures.
Extreme pneumatic conditions (high cycle rate with large pressure amplitude)
 Press the A- and B-key and Edit button simultaneously. can heat the product above 80° C.
è [OK] appears. The zero point synchronisation was successful.  Select the operating conditions (in particular the ambient temperature, pres­
è [FAIL] appears. The zero point synchronisation was not successful. Check sure amplitude, cycle rate, current consumption) such that the product does
requirements. not heat up above the maximum permitted operating temperature.

Note Restoring factory settings (restore)


If [Z.AdJ] [OFF] is set for a later time, the device takes over the factory setting
calibration values. Note
By resetting to factory settings, the current settings are lost.
5.11 Teach switching points (TEACH mode)
1. Switch off the operating voltage.
2. Keep the A- and B-keys pressed down simultaneously.
Note
3. Switch on the operating voltage.
The process for teaching the switching outputs for OutA (A-key) and OutB (B-key) is 4. Additionally press the Edit button.
the same. In the following, the process is described using the switching output OutA. è [Rsto] [PARM] appears. All parameters are reset to the factory settings
(è Fig. 21).

Note
7 Maintenance and care
There is no Timeout in the TEACH mode. The sensor changes to the RUN mode 1. Switch off the energy sources (operating voltage, compressed air).
only after the entire teach process is ended. 2. Clean sensor with non-abrasive cleaning agents.

Requirement: The sensor is ready for operation (RUN mode). 8 Disassembly


If the security code is activated, the parameter entry option is blocked: [Lock] 1. Switch off the energy sources (operating voltage, compressed air).
flashes. 2. Separate connections from the sensor.
 Enter the security code (è Chap. 5.4). 3. Loosen the mountings.

1. Establish switching function in the EDIT mode (è Chap. 5.5).


2. Create pressure value 1.
3. Press the A-key and Edit button.
è The current pressure value will then be adopted as the first teach point (TP1).
è [t-IN] flashes.
4. Create pressure value 2.
5. Press the A-key and Edit button.
è The current pressure value is adopted as the second teach point (TP2).
è Switch to the RUN mode.
9 Fault clearance No-load supply current [mA] Max. 30
Malfunction Possible cause Remedy Ready-state delay [ms] typ. 801)

No display No operating voltage or  Apply permissible operating Protection against polarity reversal All connections against each other
impermissible operating voltage voltage Mechanical system
Electrical connections swapped  Connect the device in accordance Mounting position Any, avoid condensation gathering in the sensor
with the circuit diagram Housing material PA reinforced
Device defective  Replace device Keyboard material TPE-O
Display or Short circuit or overload at the  Eliminate short circuit or overload Threaded connections material Brass (nickel-plated)
switching output output
Display
does not react in Incorrect switching point taught  Repeat teaching procedure
accordance with Displayable units bar, kPa, MPa, psi, mmHg, inchHg, inchH2O,
(e.g. at 0 bar)
the settings kgf/cm2
Device defective  Replace device
Immissions / emissions
Parameter incorrect  Reset to factory settings
Storage temperature [°C] –20 … +80
[Er01] / [FAIL] 1) Device defective  Replace device
Max. permissible relative air [%RH] 85
[Er02] / [ASIC] 1) Device defective  Replace device humidity
[Er10] / [OVER] Measuring range exceeded  Comply with the measuring range Degree of protection (in IP40
[Er20] / [tEMP] 2) Temperature error  Check operating conditions accordance with EN 60529)
 Replace device Protection class (in accordance with DIN III
[Er21] / [SHRt] 2) Short circuit at OutA  Eliminate short circuit VDE 0106-1)
[Er22] / [SHRt] 2) Short circuit at OutB  Eliminate short circuit Resistance to shocks (in accordance with 30 g acceleration with 11 ms duration
EN 60068-2) (half-sine)
[Err] / [BUSY] OutA is switched active  Check device settings
Vibration resistance (in accordance with 10 … 60 Hz: 0.35 mm / 60 … 150 HZ: 5 g
[Err] / [ID] Device ID error,  When replicating, use sensors with
EN 60068-2)
replication function failed the same type (same device ID)
[Err] / [COMM] IO-Link communication error  Check line OutA 1) After this time, the electrical outputs take a defined, stable condition
 Check settings of the device sensor Fig. 23
1) Display flashes red
2) Display illuminated red
SPAN- -B2 -B11 -V025 -V05 -V1 -P025 -P05
Fig. 22
Pressure measuring [bar] -1 0
range [MPa] -0.1 0
10 Accessories Start value
Accessories: è www.festo.com/catalogue Pressure measuring [bar] 1 10 -0.25 -0.5 -1 0.25 0.5
11 Technical data range [MPa] 0.1 1 -0.025 -0.05 -0.1 0.025 0.05
End value
SPAN- Overload range [bar] -1
General Start value [MPa] -0.1
Approval certificate c UL us – Listed (OL) Overload range [bar] 5 15 1 2 5 1 2
RCM End value [MPa] 0.5 1.5 0.1 0.2 0.5 0.1 0.2

CE marking (è declaration of conformity) In accordance with EU EMC directive Fig. 24


Note on materials RoHS compliant
Input signal / measuring element SPAN- -P1 -P2 -P6 -P10 -P12 -P16
Operating medium Compressed air in accordance with
Pressure measuring [bar] 0
ISO 8573-1:2010 [7:4:4]; inert gases, operation
range [MPa] 0
with lubricated medium possible
Start value
Temperature of medium [°C] 0 … +50
Pressure measuring [bar] 1 2 6 10 12 16
Ambient temperature [°C] 0 … +50 range [MPa] 0.1 0.2 0.6 1 1.2 1.6
Output, general End value
Accuracy Overload range [bar] -1
– P16 [% FS] ±2 at room temperature Start value [MPa] -0.1
– B2, B11, V1, P1, P2, P6, P10, [% FS] ±1.5 at room temperature Overload range [bar] 5 6 15 20
P025, P05, V025, V05, P12 End value [MPa] 0.5 0.6 1.5 2.0
– B2, B11, V1, P1, P2, P6, P10 [% FS] ±3 in the entire temperature range Fig. 25
– P025, P05, V025, V05, P12, [% FS] ±4 in the entire temperature range
P16
UL - Electrical and environmental ratings
Repeat accuracy [% FS] ±0.3 with Filt = OFF
Temperature coefficient [% FS/K] Typically 0.05 Input voltage max. 30 V DC, Class 2

Switching output Input current max. 0.23 A

Switching output 2x PNP or 2x NPN switchable Power max. 6.9 W

Switching function Threshold value comparator Pressure differential max. 1.6 MPa
Window comparator Ambient temperature max. 50 °C /122 °F
Auto difference monitoring Pollution degree 3
Switch-on/switch-off time [ms] typ.: 2, max.: 4 with FILT = OFF Max. permissible relative humidity 85 %
Max. output current [mA] 100 Only for indoor use.
Capacitive load maximum DC [nF] 100 Altitude up to 2000 m. Altitude up to 2000 m or above 2000 m if specified by the manufacturer.
Voltage drop [V] Max. 2
Fig. 26
Pull-down resistor integrated (PNP)
Pull-up resistor not integrated (NPN)
Inductive protective circuit Present IO-Link1)
Analogue output Protocol version Device V1.1
Output characteristic curve [V] 0 … 10 Profiles Smart sensor profile
initial value … end value [V] 1…5 Function classes Binary data channel (BDC)
[mA] 4 … 20 Process data variable (PDV)
Max. load resistance of current [Ω] 500 Identification
output Diagnostics
Teach channel
Min. load resistance of voltage [kΩ] 20
output Communication mode COM2 (38.4 kBaud)
Output, additional data Port class A
Short circuit protection Yes Process data width IN 2 byte
Overload protection Present Process data content IN 2 bit BDC (pressure monitoring)
Electronics 14 bit PDV (pressure reading)
Max. current consumption [mA] 230 IODD, IO-Link device description è www.festo.com/sp

Nominal operating voltage DC [V] 24 1) Only SPAN-...-PNLK-PNVBA


Operating voltage range DC [V] 15 … 30 Fig. 27