You are on page 1of 2

TABLERO PRINCIPAL

Potencia Maxima
Circuito Descripción Instalada F.D. Demanda
(kW) (kW)
C-1.1 TABLERO "TG - 1" 39.56 0.79 31.15
C-1.3 TABLERO "TG - 2" 26.68 0.81 21.55
POTENCIA INSTALADA (kW) 66.24
MAXIMA DEMANDA (kW) 52.71
FACTOR DE DIVERSIDAD 0.70
MAXIMA DEMANDA DIVERSIFICADA (kW) 36.89

TABLERO GENERAL Nº 01
Potencia Maxima
Circuito Descripción Instalada F.D. Demanda
(kW) (kW)
C-1.1 TABLERO "STD - P1" 1.30 0.82 1.06
C-1.2 TABLERO "STD - P2" 1.30 0.82 1.06
C-1.3 TABLERO "STD - P3" 1.30 0.82 1.06
C-1.4 TABLERO "STD - P4" 1.30 0.82 1.06
C-1.5 TABLERO "STD - P5" 1.30 0.82 1.06
C-1.6 TABLERO "STD - P6" 1.30 0.82 1.06
C-1.7 TABLERO "STD - P7" 1.30 0.82 1.06
C-1.8 TABLERO "STD - P8" 1.30 0.82 1.06
C-1.9 TABLERO "STD - P9" 1.30 0.82 1.06
C-1.10 TABLERO "STD - P10" 1.30 0.82 1.06
C-1.11 TABLERO "STD - P11" 1.30 0.82 1.06
C-1.12 TABLERO "STD - P12" 1.30 0.82 1.06
C-1.13 TABLERO "STD - P13" 1.30 0.82 1.06
C-1.14 TABLERO "STD - P14" 1.30 0.82 1.06
C-1.15 TABLERO "STD - SSHH - P1" 0.29 0.83 0.24
C-1.16 TABLERO "STD - SC - P1" 3.10 0.63 1.96
C-1.17 TABLERO "STD - SC - P2" 2.80 0.65 1.81
C-1.18 TABLERO "STD - BIBLIOTECA - P1" 1.30 0.82 1.06
C-1.19 TABLERO "STG - P1" 13.93 0.81 11.22
POTENCIA INSTALADA (kW) 39.56
MAXIMA DEMANDA (kW) 31.15
FACTOR DE DIVERSIDAD 0.70
MAXIMA DEMANDA DIVERSIFICADA (kW) 21.81

TABLERO GENERAL Nº 02
Potencia Maxima
Circuito Descripción Instalada F.D. Demanda
(kW) (kW)
C-1.1 TABLERO "STD - S1" 1.30 0.82 1.06
C-1.2 TABLERO "STD - S2" 1.30 0.82 1.06
C-1.3 TABLERO "STD - S3" 1.30 0.82 1.06
C-1.4 TABLERO "STD - S4" 1.30 0.82 1.06
C-1.5 TABLERO "STD - S5" 1.30 0.82 1.06
C-1.6 TABLERO "STD - S6" 1.30 0.82 1.06
C-1.7 TABLERO "STD - S7" 1.30 0.82 1.06
C-1.8 TABLERO "STD - S8" 1.30 0.82 1.06
C-1.9 TABLERO "STD - S9" 1.30 0.82 1.06
C-1.10 TABLERO "STD - S10" 1.30 0.82 1.06
C-1.11 TABLERO "STD - S11" 1.30 0.82 1.06
C-1.12 TABLERO "STD - S12" 1.30 0.82 1.06
C-1.13 TABLERO "STD - S13" 1.30 0.82 1.06
C-1.14 TABLERO "STD - S14" 1.30 0.82 1.06
C-1.15 TABLERO "STD - S15" 1.30 0.82 1.06
C-1.16 TABLERO "STD - S16" 1.30 0.82 1.06
C-1.17 TABLERO "STD - SSHH - S1" 0.29 0.83 0.24
C-1.18 TABLERO "STD - SSHH - S2" 0.29 0.83 0.24
C-1.19 TABLERO "STD - TE - S" 1.49 0.75 1.12
C-1.20 TABLERO "STD - CAF" 1.30 0.82 1.06
C-1.21 TABLERO "STD - ALM 1.30 0.82 1.06
C-1.22 TABLERO "STD - CASETA" 0.72 0.80 0.57
C-1.23 TABLERO "STD - ALM EXT" 0.56 0.50 0.28
POTENCIA INSTALADA (kW) 26.68
MAXIMA DEMANDA (kW) 21.55
FACTOR DE DIVERSIDAD 0.70
MAXIMA DEMANDA DIVERSIFICADA (kW) 15.09