Professional Documents
Culture Documents
Euserc Manual 2022
Euserc Manual 2022
Requirements Committee
euserc.org
INDEX
GLOSSARY
ORGANIZATION 1
GENERAL 1
EUSERC STRUCTURE 6
CONSTITUTION 17-18
BYLAWS 19-26
SHEET SECTION
1 OF 1 TABLE OF CONTENTS
100
ORGANIZATION
PREFACE
The EUSERC (Electric Utility Service Equipment Requirements Committee) is composed of, and the
membership open to, electric utilities located in the United States of America. Associate membership is
open to organizations associated with utility service and metering activities. The utilities participating as
members and associate members are listed in Section 100.
PURPOSE
The purpose of the EUSERC is to promote uniform electric service requirements among the member
utilities, publish existing utility service requirements for electric service equipment, and provide direction
for the development of future metering technology. The EUSERC associate members provide liaison
between the member utilities, state and federal agencies, manufacturers, contractors, and electrical
testing laboratories.
GOALS
The goal of this organization is to support the development of metering and service equipment that is
safe and cost effective to the serving agencies and their customers, and to establish manufacturing and
installation requirements for metering and service equipment that are acceptable to all member utilities.
GENERAL
These requirements and installation guides are based on, and replace, the requirements previously
published by the WUESSC and the PUESRCC. They are intended for the use of serving agencies, metering
and service equipment manufacturers, consulting engineers and architects. The EUSERC requirements
book contains information concerning electric service and metering facilities generally provided and
installed by the customer. Each serving agency will provide specific information pertaining to metering
and service requirement for the territory it serves. Consultation with the appropriate utility prior to new or
reconstruction is advised. Individual member utility acceptability of EUSERC requirement drawings is listed
on the EUSERC web site --- euserc.org
One of the major reasons for EUSERC meetings is to review requests for a new requirement; and to
consider revisions of existing requirements.
All requests, whether generated internally or submitted by a manufacturer or other party, are forwarded
to the Materials Committee Chairperson. The Chairperson will review the request for proper formatting
and completeness. The request will be forwarded to the Executive Board for review and assignment to
the appropriate Sub-Committee.
All requests must be submitted to the Materials Committee Chairperson through EUSERC Form A-1. The
form is included in the 200 Section of this EUSERC manual or may be obtained from a member
representative or downloaded from the website forms.euserc.org
This form is for utility use only and is intended to inform both the Material Committee Chairman and the
manufacturer that a specific component does not meet EUSERC requirements. The situation may be
resolved on an informal basis or referred to an investigative committee.
PURPOSE
To establish a uniform procedure for processing requests for revision of the EUSERC Manual in a timely
manner.
To assign responsibility for the completion of all tasks necessary to process a proposal in a timely
manner.
A. Submitter of Request
1. Submit requests to EUSERC Materials Committee Chairperson. To help the Materials Committee
Chairperson quickly process a proposed revision, the Submitter shall complete the "Request for
Revision or Development of EUSERC Requirement" form (See Section 200, page A-1), and:
a. If the request is for revised text, it shall include both existing and new text by striking
through existing words and highlighting new text.
1. Reviews the request for completeness and proper format. If the request is not in the proper format,
the submitter shall be contacted within 30 days of receipt of request and advised of the
DESCRIPTION necessary to bring the proposal into conformance with EUSERC requirements for
submitting requests. If the Submitter fails to make the required DESCRIPTIONs and resubmit the
proposal within 30 days, the Materials Committee Chairperson shall send the Submitter a letter
stating the reasons for rejection.
2. Submits accepted Project(s) to the Executive Board at the next Executive Board Meeting.
C. Executive Board
D. Sub-Committee
1. Sub-committee shall notify submitter of the committee assignment and applicable project
number(s). Sub-committee shall coordinate development of the assigned project with the
submitter.
2. Review new Project(s) at the sub-committee meeting following project assignment to determine
initial recommendations from one of the categories below:
a. Acceptance
e. Rejection
3. Work on Project(s) with and may solicit comments from manufacturers, industry, or other member
representatives. An Ad Hoc Committee may be established with NEMA, UL, manufacturer's
representatives, or other interested parties with regards to the Project(s).
NOTE: Chairperson shall report progress of all active projects to the Executive Board at each
regularly scheduled meeting. The Board may provide direction or reassignment for
projects that are not, in the Board’s judgment, progressing satisfactorily.
4. Send copies of Project(s) in their first vote form to members approximately 30 days prior to the
scheduled general meeting for presentation and first vote.
5. Discuss Project(s) at the next general meeting following the first vote notification; then presents
Project recommendations to the Committee for first vote at the next general meeting. (If editorial
DESCRIPTION only, Projects will proceed to the Forms Committee for publication.)
6. Send copies of Project(s) that have passed first vote to manufacturers and others on the current
Section 300/400/500 mailing list. Provides notification of the intended date for second vote for
the Project(s).
NOTE: Thirty-five days from the date of the notification cover letter, including mail delivery
time, is recommended as a general time limit for comment submittals. Any comments
received before the second vote meeting that have not been addressed by the sub-
committee, will be presented to the Committee.
7. Review manufacturers’ comments on Projects which have passed first vote and modify Project(s)
as necessary.
8. Send copies of Project(s) in their second vote form to the members approximately 30 days prior
to the scheduled general meeting for presentation and second vote.
9. Discuss Project(s) at the next general meeting following the second vote notification, then presents
project recommendations to the Committee for second vote at the next general meeting.
10. Send Project(s) which have passed second vote to the Forms Committee Chairperson for
publication in the EUSERC manual.
11. New or revised requirements shall become effective upon publication in the new EUSERC Manual,
but not sooner than six months after the date of final committee approval.
E. Committee
1. Final Project disposition by the Committee shall be reported to the submitter of the Project by the
sub-committee chairman assigned responsibility for that project.
2. Projects rejected by the Committee shall be returned with written substantiation to the submitter
with a copy of the appeals procedure.
PRESIDING STANDING
OFFICERS COMMITTEES
SUBCOMMITTEE
CHAIRPERSONS
SECTION 100 & SECTION 300 SECTION 400 SECTION 500 SECTION G
200 LOW VOLTAGE MAXIMUM ALTERNATIVE INSTALLATION
GENERAL METERING & VOLTAGE GENERATION GUIDES
REQUIREMENTS SERVICING METERING &
EQUIPMENT SERVICING
EQUIPMENT
Southern California Edison (OC Region) San Diego Gas & Electric
1241 S. Grand Ave. Bldg. A 8326 Century Park Ct.
Santa Ana, CA 92750 San Diego, CA 92123
Phone: (626) 388-5307 Phone: (619) 203-1034
Email: fabricio.marroquin@sce.com Email: ijuarez@sdge.com
WEBSITE ADMINISTRATOR
Craig Greer
MEMBER AT LARGE
Jeffrey Duncan
MATERIALS CHAIRPERSON
Pacificorp
1407 W. North Temple
Salt Lake City, UT 84116
Phone: (951) 288-8596
Email: paul.kristensen@pacificorp.com
FORMS CHAIRPERSON
SECTION G
INSTALLATION GUIDES
Scott Anderson
Silicon Valley Power
1500 Warburton Ave.
Santa Clara, CA 95050
Phone: (408) 615-6610
Email: sanderson@SantaClaraCA.gov
1. ALAMEDA, CITY OF
Alameda, California
2. ANAHEIM, CITY OF
Anaheim, California
7. BANNING, CITY OF
Banning, California
54. S. M. U. D.
Sacramento, California
3. CALIFORNIA ISO
Folsom, California
B. Alumni members, that work for a Manufacturer, Company or Organization that may be considered
a “conflict of interest” are prohibited from attending the business portion of the meetings.
D. Alumni members are eligible to receive EUSERC hotel rates and discounts if booked in advance.
ARTICLE I
Name
This organization shall be named Electric Utility Service Equipment Requirements Committee and hereafter
be referred as “EUSERC” or “Committee”.
ARTICLE II
Purpose
A. To develop and promote safe uniform electric meter service equipment requirements among member
utilities.
B. To publish electric meter service equipment requirements acceptable to the member utilities.
ARTICLE III
Membership
A. Electric Utility Members must be employees of an Electric Utility. To maintain EUSERC membership,
Electric Utility Members will agree to uphold the EUSERC Constitution, Bylaws, Organization and Will:
1. Attend minimum of one (1) committee meeting in a twenty-four (24) month, calendar period.
4. Pay a yearly $200.00 membership fee per utility to cover costs associated with maintenance of
the EUSERC website and manual.
Electric Utilities that do not participate in one (1) of the above four (4) items will be considered for EUSERC
suspension. Suspended members will be excluded from all EUSERC functions and mailings.
B. Associate Members shall not be affiliated with an Electric Utility, or a specific Equipment
Manufacturer. Perspective Associate Members shall submit statements to the Executive Board
indicating, knowledge of the work of the Committee, intent to participate actively in the work of the
Committee, and state what benefits they bring to EUSERC.
Examples of Associate Membership are NEMA, ANSI, IEEE, etc. To maintain EUSERC membership,
Associate Members will agree to uphold the EUSERC Constitution, Bylaws and Will:
1. Attend minimum of one (1) committee meeting in a twenty-four (24) month, calendar period.
Associate Members that do not participate in one (1) of the above two items will be considered for
EUSERC suspension. Suspended members will be excluded from all EUSERC functions and mailings.
ARTICLE I
RESPONSIBILITY
EUSERC membership as defined in the Constitution, ARTICLE III, will be inclusive except; whereas other
criteria may warrant recognition and is acceptable by two-thirds (2/3) vote of the Executive Board and
enacted by majority vote of Electric Utility Members in attendance.
6. Review and vote on DESCRIPTIONs in the Constitution, Bylaws, policies, and procedures.
B. Associate Members shall participate in discussions in Sub Committee and General Committee
discussions and participate during open forum discussions via Subcommittee, General Committee, and
open forums.
ARTICLE II
SUSPENSION
Any Electric Utility or Associate Member that violates Articles II or III of the Constitution or uses EUSERC
for self- promotion or financial gain shall be cause for immediate review by the Executive Board for
suspension.
A. Suspension shall:
2. Be notified in writing by the EUSERC Vice Chairperson at the direction of the Executive Board.
3. Be for a minimum of twelve (12) consecutive months from the date of the Executive vote for
suspension.
1. Suspended members shall petition EUSERC in writing for reinstatement of membership status.
3. Reinstated members are required to attend a minimum of one (1) meeting within one (1)
calendar year of being reinstated.
4. Reinstated members shall receive EUSERC books, materials, and mailings upon reinstatement.
ARTICLE III
GOVERNMENT
To conduct business, a quorum of EUSERC members is required to be present. Ten Percent (10%) of
Electric Utility Members constitute a quorum. Except as noted otherwise, EUSERC shall be governed by a
simple majority vote of the Electric Utility Members in attendance with each Electric Utility casting one (1)
vote.
Elections shall be held the first day of the last regular meeting of the year. The new officers will be installed
as the last order of business on the last day of the last regular meeting of the year. Special elections shall
be called by the Executive Board to replace any elective officer, or a member of the Executive Board as
deemed necessary.
Elected Officers (Executive Board) shall preside and administer EUSERC business. A simple majority of
members shall elect the Executive Board in attendance during the election ballot vote. Officers shall hold
office two (2) years from the month of their election. The Chairperson shall be limited to two (2)
consecutive terms. The Executive Board shall consist of four (4) Presiding Officers, and three (3) Standing
Committee Chairs.
A. Chairperson
a. Create agenda.
B. Vice Chairperson
2. Assist the Chairperson during regularly scheduled meetings and preside over Executive and
General Meetings in the absence of the Chairperson.
a. Vendor Review
1) Approve prospective vendors upon request.
b. Members
1) Update member list as requested by member utilities.
2) Assign usernames and passwords.
c. Post news
C. Recording Secretary
1. Record and maintain minutes of the Executive Board and Committee meetings.
4. Act in capacity of Chairperson during the absence of the Chairperson and Vice Chairperson.
D. Treasurer
1. Collect and deposit any funds, dues, assessments, or contributions as directed by the Committee.
3. Provide quarterly statement to the Executive Board for general distribution at the quarterly
general meeting.
4. Pay all invoices and incurred bills as directed by the Executive Board.
5. Purchase materials as authorized by the Executive Board or 2/3 aye (yes) vote of the attending
members.
a. Assign Project Numbers to requests that are approved and assign them to the appropriate
Subcommittee.
b. Notify requestor of request that is denied within thirty (30) days of Executive Board action.
c. Work with manufacturer to resolve the discrepancy. Keep the person that submitted the report
abreast of corrective measures or outcome of manufacturers' discussions.
d. Report all events and what (if any) corrective actions were taken at the next EUSERC meeting.
G. Member-At-Large
1. Coordinate and maintain the following mailing and contact lists for:
a. Membership
b. Manual Distribution
f. Utility Representatives
2. Act as Sergeant at Arms and assist the Chairperson when needed to maintain decorum.
2. Determine and set forth the policies for EUSERC with a majority vote of the members in
attendance.
3. Continuously monitor the effectiveness of the Organization, Constitution and Bylaws and
recommend revisions as needed.
4. Determine the membership status of all members and review and act upon requests for
membership.
8. Provide educational programs as requested by the General Membership and directed by the
Presiding Officers.
9. Schedule quarterly meetings and assist the Chairperson with the meeting agenda.
11. Insure adherence and compliance to the Constitution, Bylaws and the best interests of the
Organization.
12. Require a simple majority of Presiding Officers and Standing Committee Chairpersons to
conduct EUSERC Executive Board business.
13. The Executive Board shall be governed by a simple majority vote of the Presiding Officers and
Standing Committee Chairpersons.
14. Review and approve all EUSERC expenditures and provide direction to the Treasurer.
15. Authorize appointment of officers and Standing Committee Chairpersons to interim vacancies,
not to exceed six (6) months.
ARTICLE IV
FINANCIAL
EUSERC shall remain a not-for-profit organization. All monies received or collected shall be used for the
enhancement and good of the EUSERC. A financial report shall be submitted for approval at each Executive
Board and General meeting.
ARTICLE V
AMENDMENTS
A. The Bylaws may be amended by a simple majority vote of a quorum present at two (2) consecutive
regular meetings.
B. The Constitution may be amended by a simple majority vote of a quorum present at two (2)
consecutive regular meetings.
ARTICLE VI
COMMITTEE DISSOLUTION
A. The activities of the EUSERC may be suspended or dissolved upon the recommendation of the
Executive Board and a two-thirds (2/3) majority vote of the active membership. This action shall be
determined by submission of a letter ballot.
B. All unexpended funds remaining in the treasury shall be donated to a charity specified by the Executive
Board at the time of dissolution. No funds shall be vested to the benefit of any individual member or
group of members.
C. Nothing in the foregoing shall prevent prior assignment of funds to a successor organization(s). The
Executive Board shall specify such assignment.
DATE: _________________________
PROJECT NO.: __________________
REF. DWG.:_____________________
___________________________________________________
(Organization/Company)
___________________________________________________
(Address)
___________________________________________________
(Telephone/Employer/Fax Number)
___________________________________________________
(Best Time of Day to be Contacted)
REQUEST: ________________________________________________
_________________________________________________________
REASON: _________________________________________________
_________________________________________________________
NOTES: Attach both old and new texts for drawings. See General Use Guide,
Section 100, pages 1-5 and Section 200, A-2 to A-4 for proper format. Attach
additional pages as needed.
EUSERC ACTION TAKEN
REJECTED: _______________________________________________
(Date)
DATE: __________________________
MANUFACTURER: __________________________________________________
DESCRIPTION OF EQUIPMENT: _______________________________________
MFG NO.: __________________ PLANT CODE: ____________________
MFG DATE: _____________ _____ CONTRACTOR: _____________________
PHONE NO.: _________________
LOCATION OF EQUIPMENT: _____________________________________________
REPORT: ____________________________________________________________
____________________________________________________________________
____________________________________________________________________
REPORTED BY: _______________________________________________________
UTILITY: ____________________________________________________________
PHONE NO.: _________________
EUSERC ACTION: _____________________________________________________
E-MAIL ADDRESS: _____________________________________________________
FEEDBACK SHEET
EUSERC/UTILITY/MANUFACTURER
DATE: _______________________
ORIGINATOR TO SUBMIT COMPLETED SHEET TO APPROPRIATE ORGANIZATION
TO: FROM:
_____EUSERC _____EUSERC
_____UTILITY _____UTILITY
_____MANUFACTURER _____MANUFACTURER
________________________________________ ____________________
(Name – Print or Type) (Phone Number)
________________________________________ ____________________
(Title – Print or Type) (Fax Number)
________________________________________ ____________________
(Address) (E-Mail Address)
________________________________________
(City, State, Zip)
Maximum of two representatives per utility/company. Fee is $200 per utility payable to
“EUSERC.” Acceptability pages must be received within 90 days of receiving acceptance letter.
Link can be added to the website by co-sponsoring an EUSERC event. See EUSERC calendar
quarterly events for details.
The Acceptability Tables list EUSERC drawings and their acceptability to EUSERC
member utilities. These Tables represent the most up-to-date polling information that
EUSERC has regarding member acceptance of published requirements.
The Acceptability Tables are listed on the EUSERC website --- https://euserc.org
DESCRIPTIONs to the acceptability pages can be made by completing the form on the
next page and sending the form to the Section 200 committee chairperson.
Place an X in the appropriate box for each drawing: A = Acceptable C = Consult U = Unacceptable N/A = Not Applicable
SYMBOLS MEANING
4 4 clip socket
5 5 clip socket with the 5th clip at either 6 or 9 o'clock position
5A 5 clip socket with the 5th clip at the 9 o’clock position
5B 5 clip socket with the 5th clip at the 6 o'clock position
5C 5th clip at 9 o'clock position for 100-amp sockets 5th clip at 6 o'clock
position for 200-amp sockets
6 6 clip socket with clips at 3 and 9 o'clock positions
7 7 clip socket
8 8 clip socket
13 13 clip socket
15 15 clip socket
P Potential transformers used
E 8 clip socket for less than 400 amps; otherwise 13 clip socket
F 8 clip socket for less than 500 amps; otherwise 13 clip socket
G 8 clip socket for less than 800 amps; otherwise 13 clip socket
* Consult the utility
N/A Not Applicable
AMERICAN ELECTRIC
POWER SERVICE
ANCHORAGE MUM
4 NA NA NA NA 5A 4 4 NA 7 7 NA 7 NA
POWER & LIGHT
ARIZONA PUBLIC
4 NA NA NA NA 5A 4 NA NA 7 7 NA 7 NA NA
SERVICE
ELECTRICAL DISTRICT
4 NA NA NA NA 5 4 NA NA 7 7 NA 7 NA N/A
#3
ELECTRICAL DISTRICT
#4 & #5
FLATHEAD ELECTRIC
COOP.
IMPERIAL IRRIGATION
NA NA NA NA NA N 4A NA NA 7 7 NA 7 NA
DISTRICT
INTERMOUNTAIN RURAL
4 NA NA NA NA 5 4 NA NA 7 7 5 7 5
ELEC. ASSC.
MODESTO IRRIGATION
4 NA NA NA NA 5A 4 NA NA 7 7 * 7 5A
DISTRICT
NAVOPACHE ELECTRIC
4 NA NA NA NA 5A 4 NA NA 7 7 NA 7 NA NA
COOP
PACIFICORP 4 NA NA NA NA 5A 4 4 NA 7 7 5 7 5
PORTLAND GENERAL
4 NA 4 NA NA 5A 4 4 NA 7 7 5A 7 5A
ELECTRIC
SALT RIVER PROJECT 4 N/A N/A N/A N/A 5 4 N/A N/A 7 7 N/A 7 N/A
TUCSON ELECTRIC
4 N/A N/A N/A N/A 5A 4 4 N/A 7 7 5A 7 N/A
POWER
TURLOCK IRRIGATION
4 N/A N/A N/A N/A 5 4 N/A N/A 7 7 N/A 7 N/A
DISTRICT
UKIAH, CITY OF N/A N/A N/A N/A N/A 5A 4 N/A N/A 7 7 N/A 7 N/A
UNISOURCE ENERGY
SERVICES
ALAMEDA, CA, CITY OF 5 N/A N/A N/A N/A 8 6 N/A N/A N/A 13 13 8 13 8
ANCHORAGE MUM
POWER & LIGHT N/A N/A N/A N/A N/A N/A 6 N/A N/A N/A 13 13 N/A 13 N/A
ARIZONA PUBLIC
SERVICE N/A N/A N/A N/A N/A 8 8 N/A N/A N/A 13 13 N/A 13 N/A
AZUSA, CA. CITY OF N/A N/A 5A N/A N/A N/A N/A N/A N/A N/A 13 13 8 13 8
BURBANK, CA, CITY OF N/A N/A 4 N/A N/A N/A 6 N/A N/A N/A 13 13 8 13P 8P
COLTON, CA, CITY OF 5 N/A 5 N/A N/A N/A 6 N/A N/A 8 13 13 N/A 13 N/A
ELLENSBURG, CITY OF ‐
ENERGY SERVICES
FLATHEAD ELECTRIC
COOP.
GLENDALE, CA, CITY OF N/A N/A N/A N/A N/A N/A 5 N/A N/A N/A 15 N/A 8 15P 8P
GRANT COUNTY, PUD N/A N/A N/A N/A N/A N/A 5A 7 N/A N/A 7 13 N/A 13 N/A
INTERMOUNTAIN RURAL
ELEC. ASSC. N/A N/A N/A N/A N/A N/A 8 N/A N/A N/A 13 13 N/A 13P N/A
LODI, CA, CIT Y OF N/A N/A N/A N/A N/A N/A 6 N/A N/A N/A 15 15 15 15 15
LOMPOC, CA, CITY OF N/A N/A N/A N/A N/A N/A 6 N/A N/A N/A 13 13 8 13 8
LOS ANGELES, DWP N/A N/A N/A N/A N/A N/A 6 N/A N/A 8 13 13 8 13 8
MESA, AZ, CITY OF N/A N/A N/A N/A N/A N/A 5A N/A N/A N/A 13 N/A 8 13 8P
NEVEDA POW ER
COMPANY N/A N/A N/A N/A N/A N/A 5 N/A N/A N/A 13 13 N/A 13 N/A
NORTHW ESTERN
ENERGY, LLC
PACIFIC GAS &
ELECTRIC CO 8 N/A 8 N/A 8 N/A 6 N/A N/A 8 15 15 8 15 8
PACIFICORP N/A N/A N/A N/A N/A N/A 6 * N/A N/A 13 13 N/A 13 N/A
PUGET SOUND ENERGY N/A N/A N/A N/A N/A N/A 6 N/A N/A N/A 13 13 N/A 13 N/A
REDDING, CA, CIT Y OF N/A N/A N/A N/A N/A N/A 6 N/A N/A 13 13 13 N/A 13 8
RIV ERSIDE, CA, CIT Y OF N/A N/A N/A N/A N/A N/A 6 N/A N/A N/A 13 13 8 13 8
SACRAMENTO
MUNICIPA L UT ILIT Y N/A N/A N/A N/A N/A 8 6 N/A N/A N/A 13 13 N/A 13 N/A
SALT RIVER PROJECT N/A N/A N/A N/A N/A N/A 6 N/A N/A N/A 13 13 N/A 13 N/A
SILICON VALLEY
POW ER N/A N/A N/A N/A N/A N/A 8 N/A N/A N/A 13 13 N/A 13P 8P
SNOHOMISH COUNTY
PUD#1 N/A N/A N/A N/A N/A 8 6 6 N/A 5 13 13 8 13 8
SOUTHERN CALIFORNIA
EDISON N/A N/A N/A N/A 5 N/A 5 N/A N/A N/A 15 15 15 15 15
SPRINGFIELD UT ILIT Y
BOARD N/A N/A N/A N/A N/A N/A 8 * * N/A 13 13 8 13 8
SULPUR SPRINGS
VALLEY ELEC. 5A 5A 5A 5A 5A 8 6 8P 8P N/A 13 13 8 13P 8P
TACOMA POW ER N/A N/A N/A N/A N/A 8 6 N/A N/A N/A 13 13 N/A 13 8
TRUCKEE‐DONNER PUD 5A N/A N/A N/A N/A 8 6 N/A N/A N/A 13 13 N/A 13 N/A
TUCSON ELECTRIC
POW ER N/A N/A N/A N/A N/A N/A 6 6 N/A N/A 13 8 * 13 *
UKIA H, CIT Y OF N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 13 13 N/A 13 N/A
UNISOURCE ENERGY
SERVICES
Manufacturers’ drawings are required in some cases prior to fabrication or installation of the services
and metering equipment. Specific instances are:
1. All single self-contained metering equipment, 0-600 volts
2. All multiple self-contained metering equipment, 0-600 volts
3. All instrument transformer rated metering equipment, 0-600 volts
4. All standard switchboard service sections, 0-600 volts
5. Standard switchboard service sections rated 400 amps and above
6. Standard switchboard service sections rated 1000 amps and above
7. Specially engineered switchboards
8. High voltage switchboards
See the following page for individual EUSERC member requirements. CODES:
X: Required
ELECTRICAL DISTRICT #3 X X X X X X X
ELECTRICAL DISTRICT #4
& #5
FLATHEAD ELECTRIC
X X X X X X
COOP.
IMPERIAL IRRIGATION
X X X X X X X X
DISTRICT
INTERMOUNTAIN RURAL
X X X X X
ELEC. ASSC.
MODESTO IRRIGATION
X X X X X X X
DISTRICT
NAVOPACHE ELECTRIC
X X X X X X X
COOP
NEVADA POWER
X X X X X X
COMPANY
NORTHWESTERN ENERGY,
LLC
PACIFIC GAS & ELECTRIC
X X X X X X X
CO
PACIFICORP X X X X X X
PORTLAND GENERAL
X X X X
ELECTRIC
SACRAMENTO MUNICIPAL
X X X X X X X
UTILITY
TACOMA POWER X X X X X X
TRUCKEE‐DONNER PUD X X X X X X X
TUCSON ELECTRIC
X X X X X X
POWER
TURLOCK IRRIGATION
X X X X X
DISTRICT
UKIAH, CITY OF X X X X X X X
UNISOURCE ENERGY
SERVICES
SECTION SHEET
300 I. SCOPE 1
DRAWINGS
301 RESIDENTIAL COMBINATION METER PANEL, 225 AMPS MAXIMUM
303 METER PANEL FOR BOLT-ON METER – UNDERGROUND SERVICE 201 - 400
AMPERES
310 BLANK
DRAWINGS
DRAWINGS
328 BLANK
329 BLANK
– 800A)
334 BLANK
335 BLANK
337 BLANK
DRAWINGS
340 BLANK
341 BLANK
346 BLANK
350 BLANK
352 BLANK
A. This section contains minimum manufacturing requirements for utility metering and service
equipment rated 0-600V.
B. The following general notes apply to all drawings in this section where applicable. Each drawing
may also contain additional notes which should be considered unique to that drawing unless
reference is made to another specific drawing or section.
C. Refer to Section 200 for specific utility requirements and utility acceptability of these
requirements.
D. Refer to the installation guide section for typical application and installation requirements.
These Requirements are based on practices that are necessary to supply uniform satisfactory and safe
service. Interpretations or clarifications of intent of these Requirements are subject to EUSERC
approval. Installations shall also conform to the provisions of applicable codes and ordinances of local
inspection authorities and the servicing agency.
A. Grounding, General
1. Lugs for terminating the customer’s ground wire (or other grounding conductors) shall be
located outside of the sealable section and shall be designed to readily permit the customer's
neutral system to be isolated, when necessary, from the serving agency.
2. Ground buss, when provided, shall be located at the rear of underground terminating
enclosures (i.e., pull boxes and pull sections).
B. Meter Sequence
The metering arrangement, approved as the standard and required by all the serving agencies,
provides for the line current to enter the meter first and then the disconnecting means and
overload protective devices (meter-switch-fuse sequence). For multiple meter installations, refer
to local codes.
Customer locking for meter enclosures shall provide for independent access by the serving agency.
D. Meter Heights
Meters shall be located not more than 75 inches and not less than 48 inches above the ground or
standing surface when installed outdoors. When meters are enclosed in a cabinet or indoors in a meter
room, the minimum height may be reduced to 36 inches. The meter height shall be measured to the
meter axis. Exception: Utilities in snow areas may require increased height.
1. See Section 200 for tabulation of meter socket requirements of member utilities.
2. The socket and enclosure shall be designed in accordance with the latest revision of AEIC-
EEI-NEMA Standards for Watthour Meter Sockets, Publication ANSI C12.7, and Underwriters
Laboratories Standard for Meter Sockets UL414. Socket rim to jaw clearance shall be no less
than ANSI C12.7 (0.500”) or more than (0.690”).
Exception: The 0.690” dimension does not apply to transformer rated sockets and ground and
neutral clips on self-contained sockets.
a. For residential service applications, meter sockets shall have a maximum ampacity rating
not less than the ampacity rating of the associated service disconnect. The maximum
ampacity rating is 125% of the continuous-duty rating.
b. For commercial and industrial service applications, meter sockets shall have a continuous-
duty rating of 100 amperes for service disconnects rated up to 125 amperes (maximum)
and a continuous-duty rating of 200 amperes for service disconnects rated up to 250
amperes (maximum)
5. When self-contained meter sockets are installed in switchboards, they are to be wired by the
switchboard manufacturer. Consult the Utility for use of lever bypass meter sockets.
6. Sockets for instrument transformer installations shall be furnished and installed by the
customer. The serving agency will furnish and install the normal secondary wiring from the
instrument transformers to the meter socket.
7. Potential taps, including the neutral potential tap, shall be located behind a sealed panel. The
customer's grounding electrode connection shall not be located within the meter socket or
socket area of a combination CT / meter enclosure.
8. Ring-type sockets shall be furnished with sealing rings. Consult the Utility for usage of ring
less sockets.
a. Hinged panels shall be fabricated and installed by the manufacturer for back
connection. (See Drawings 332 and 333)
Note: Screws used to mount cast meter sockets to hinged panels shall provide a 1/8”
minimum clearance between the screw head and the back of the meter socket ring.
b. Non-hinged panels shall be fabricated and installed by the manufacturer for front
connection. (See Drawings 313, 314 & 339)
Note: Meter sockets shall be attached with machine screws so that they may be entered or
replaced. Sheet metal and self-tapping screws are not acceptable.
Note: Screws used to mount cast meter sockets to hinged panels shall provide a 1/8”
minimum clearance between the screw head and the back of the meter socket ring.
b. Non-hinged panels shall be fabricated and installed by the manufacturer for front
connection. (See Drawings 313, 314 & 339)
Note: Meter sockets shall be attached with machine screws so that they may be entered or
replaced. Sheet metal and self-tapping screws are not acceptable.
11. All self-contained meter sockets shall be rigidly attached to the backwall of the socket
enclosure or to a stationary support connected to the enclosure. For ring- type meter panels,
the meter sockets shall be attached to the meter panel to assure alignment of the socket ring
to the socket jaws and prevent removal of the panel with the meter in place. Sheet metal or
self-tapping screws are not acceptable.
1. Sockets equipped with test-bypass disconnect facilities are required for some installations and
prohibited on others. For use in any locality, consult the serving agency.
1. The hinged meter panels shown on Drawings 332 & 333 are designed to accommodate only
transformer-rated socket meters. Self-contained sockets shall not be mounted on hinged
panels.
2. The nonhinged meter panels shall not be used in front of a current transformer section. For
a specially engineered switchboard, the nonhinged panel as shown on Drawing 336 will
accommodate a socket-type meter when used with current transformers.
3. Not more than two meters shall be mounted on any removable meter panel.
4. Additional space may be required for recording or graphic demand meters (see Drawing 333).
5. Hinged meter and filler panels shall be equipped with stops to prevent inward swinging
beyond the front surface of the switchboards.
7. All pull and termination section cover panels shall be removable, sealable, provided with two
lifting handles, and limited to a maximum size of nine square feet in area.
H. Lifting Handles
1. When lifting handles are required on panels and covers, each handle shall be sized for full
hand grasping, securely attached, and have strength to withstand handling stresses of a
minimum of 75 pounds.
Note: Chest type handles with a folding bale grasp are not acceptable.
I. Sealing
1. All cover panels, removable access panels, and hinged panels for compartments containing
unmetered conductors shall be sealable. When a raceway or conduit for meter secondary
wiring is necessary, the raceway or conduit shall be sealable. No removable panel or cover
requiring sealing shall be located behind other panels, covers or doors (except raintight
enclosure doors).
Note: Carriage bolts may be used to secure cover panels in place of sealing provisions when
the bolts are installed at the factory and do not require field removal and installation to
complete assembly of the switchboard sections.
2. Sealable latches, stud, and wingnuts, or sealing screws shall be provided as the means of
sealing removable or hinged access covers.
3. Hinged cover panels shall be sealed on the side opposite the hinges.
4. Removable cover panels shall be sealed with stud and wing-nut assemblies on opposite sides
of the cover. Alternate sealing methods may be used if the removable covers are self-
supporting with the captive screws and sealing provisions removed.
a. Stud and wing-nut assemblies shall consist of a ¼ inch X 20 (minimum) stud and an
associated wingnut, each drilled .0635 inches (minimum) for sealing purposes. The stud
shall be securely attached to not loosen or screw out when being fastened.
b. Sealing screws shall be drilled .0635 inches (minimum) for sealing purposes.
c. Latching devices shall be designed to permit positive locking and be made of a durable
corrosion resistant material.
Test-bypass block compartment cover panels shall have a caution sign on the front reading:
K. Unmetered Conductors
Customer unmetered service wires and metered load wires are not to be run in the same conduit,
raceway or wiring gutter. Metered and unmetered wires shall be separated by suitable barriers.
Metered wires from the customer's distribution section (branch circuits) shall not pass-through
sealable sections. For exceptions, see Apartment Metering.
L. Buss Bars
1. Ampacity
a. The dimensions in these requirements are based on the use of rectangular bus bar.
Ampacities of buss bar conductors shall be based on UL-891. Standard for Dead-Front
Switchboard, including ampacities based on thermal limits provided for therein. Maximum
widths and number of bus bars shall conform to EUSERC requirements.
2. Plating
a. Buss bars and other hardware attached to the outer walls of the enclosure shall be secured
with devices that may not be loosened from the outside. Screws or bolts requiring special
tools for installation or removal are not acceptable.
M. Service Disconnects
a. For each meter, the customer shall furnish and install a circuit breaker, fused switch, or
other approved disconnecting means with over-current protection referred in these
requirements as a meter disconnect.
b. The meter disconnect shall control all the energy registered by its related meter.
c. Where permitted by the serving agency, the meter disconnect may consist of six
separate devices.
(1) A lockout device which is incorporated as an integral part of each meter disconnect.
(2) A lockable cover for each meter disconnect where the lock prevents the operation
of the disconnect and prevents removal of the cover
(3) A lockable cover for multiple meter disconnects where the lock prevents the
operation of any of the disconnects, prevents removal of the cover, and all
disconnects are supplied from a single instrument transformer compartment.
(5) For fused disconnects, the fuse access cover shall be lockable when the disconnect
is in the off (open) position.
(7) All locking provisions for disconnects rated 400 amperes and above shall accept a
lock shank of not less than 5/16 inch.
a. A main service disconnect device is installed on the supply (line) side of a group of meter
sockets and may be a circuit breaker, fused disconnect, or other approved disconnecting
means.
b. A service disconnect shall be installed on the supply (line) side of more than six- meter
sockets.
c. A service disconnect may be permitted on the supply side of two to six-meter sockets.
Consult the serving agency for specific requirements.
d. A service disconnect is not permitted on the supply (line) side of a single meter socket.
(Old Sequence).
e. The cover on a line side disconnect shall be sealable, (see Drawing 315 Note 5).
Manufacturers shall provide information and safety labels in utility compartments as follows:
1. Caution labels for switchboard pull sections shall be provided on the safety barrier and cover
of each pull section where energized buss is less than 4 inches from removable access cover
panels. See Drawing 347 for additional requirements.
2. Torque labels shall be provided in each utility compartment where nut and bolt assemblies
using cone-type (Belleville) washers are used for utility terminations, test-bypass block circuit
closing nuts, or for securing current transformers or current transformer buss removable links.
Labels shall be readily visible and shall not be installed on any removable or hinged cover
panel.
Self-contained meters are designed to carry rated current and be energized at line potential. They
do not require auxiliary instrument transformers to step down line current or voltage.
A. Residential, General
Four Types of self-contained meters are commonly used for this application.
Class 100 or 200 socket-type meters are commonly used; and test-bypass disconnect facilities
are required for this application. Some utilities allow Class 320 or Class 400- amp meters for
specialized installations (Go to euserc.org for specific utility requirements).
C. Multiple, Switchboard
1. The socket and socket enclosure shall be designed in accordance with the latest revision of
AEIC-EEI-NEMA Standards for Watthour Meter Sockets, Publication ANSI C12.7, and with
Standard for Meter Sockets UL414.
2. The bussing or cables to each individual meter socket are to be installed so they can be visibly
traced.
3. Multiple Meter enclosures that are not factory bussed shall have non-removable, solid metal
barriers to isolate the metered conductors from the unmetered conductors.
4. The service termination enclosure, socket enclosures, raceways and sections for test-bypass
or manual circuit closing facilities shall have separate, removable and sealable access panels
(or plates). Meter socket enclosures shall have a separate sealable cover containing no more
than two-meter positions.
1. The rules for spacing of socket meters in multiple residential meter installations shall be as
follows:
a. Metered and unmetered conductors shall be separated so that all the load is being
metered (Line and Load conductors not cabled together).
b. Factory "harness-style" wiring (or equivalent) shall be used between the line wire and
line terminals of each meter socket, between the load terminals of each meter socket,
and the line side of the corresponding circuit breaker.
c. Connecting wires between meter socket load terminals and circuit breaker line terminals
shall be separately cabled for each position in the row.
d. When the installation is completed, all panels must be removable for inspection of
wiring.
e. Panel design shall permit convenient replacement of any individual meter socket.
A. General Requirements
1. Instrument transformer compartments are generally required when the connected load
exceeds 200 amperes. See Section 200 for exceptions and utility acceptability of these
requirements and Section 400 when the voltage between conductors exceeds 600 volts.
2. Meter, instrument transformers and test switches will normally be furnished and installed by
the serving agency. Any required conduits or raceways shall be furnished and installed by the
switchboard manufacturer or contractor.
(See Section 200 for specific utility requirements).
1. For both standard and specially engineered switchboard service sections, all service or supply
conductors shall enter the service section through one end and leave through the opposite
end of the instrument transformer compartment. This stipulation applies to either overhead
or underground service or if two or more service sections are connected. The direction of
feed shall be vertical through the instrument transformer compartment, (See Drawing 345).
2. When more than one switchboard service section is installed, each service section shall be
completely barriered from other service sections, pull sections, or service switches or
disconnects. Barriers may have an opening to allow passage of un- metered conductors
between sections. Barriers shall be constructed from 16-gauge (minimum) steel in accordance
with (B)(3) below.
Note: A portion of the barrier between sealed utility metering sections and the pull section
may be 1/8” minimum glastic or equivalent due to potential electrical clearance issues.
4. When two or more switchboard service sections are supplied from one set of service
conductors, the supply conductors are to be arranged so they are readily accessible without
disturbing the instrument transformers and associated secondary wiring.
5. Additional service connections may be made in the main service termination and pull section
where more than one metering installation is necessary or where more than one rate schedule
is desired. Additional service connections shall not be made in the instrument transformer
compartment. Consult serving agency for approval.
1. The general arrangement of a standard switchboard section is shown on Drawings 325 and
326.
2. A standard switchboard service section has a hinged meter panel located in front of the
instrument transformer compartment. Drawing 333 shows spacings for various combinations
of multiple meters.
3. Hinged meter panels must have handles and open a minimum of 90 degrees with meters and
test switches mounted to permit safe and ready access to the instrument transformers. When
hinged panels are recessed, the section shall have additional width to meet this requirement.
A recessed panel requires utility approval as a specially engineered section, (See Drawing
354).
4. Hinged meter panels must be sealable and easily removable with the hinges readily
interchangeable from the right or left side on the job site.
5. The hinged meter panels on Drawings 332 and 333 are designed for transformer- rated,
socket-type meters.
6. Meter panels and filler panels shall be equipped with stops to prevent inward swinging beyond
the front surface of the switchboard.
7. Not more than two meters shall be mounted on any removable meter panel.
8. For hinged socket meter panels, see Drawings 332 and 333.
9. For underground service application Of Standard Switchboard Service Sections, see Drawing
345.
1. Switchboards which do not conform to standard design criteria are considered specially
engineered and include installations:
b. Where the service breaker ampacity rating exceeds that of the standard service section.
1. Switchboards which do not conform to standard design criteria are considered specially
engineered and include installations:
b. Where the service breaker ampacity rating exceeds that of the standard service section.
3. The general arrangement of Specially Engineered Switchboard Service Sections should follow,
as nearly as practicable, the Standard Switchboard Service Sections and the following general
requirements shall be observed:
b. If a hinged meter panel is located behind a door, a clear space of at least 11 inches
between the meter panel and the door is required and shall be designed to open 90
degrees with meters and test switches in place. If needed, additional section width shall
be provided to meet this requirement.
c. A clear space behind a meter panel shall be provided for the secondary wiring and phase
shifting device. For minimum dimensions between the hinged meter panel and the
nearest buss, see Drawings 319-324.
d. For nonhinged meter panels, a clear space of four inches minimum to any barrier or
obstruction shall be provided.
e. The nonhinged meter panels shall not be used in front of a current transformer section.
For a specially engineered switchboard, nonhinged panels will accommodate socket-type
instrument transformer-rated meters.
g. Additional panel space is required for recording or graphic demand meters, (see Drawing
333).
h. Not more than two meters shall be mounted on any removable meter panel.
j. The busses and current transformer mountings shall be designed so that each of the
current transformers may be withdrawn from its mounting position directly through the
access panel without disturbing any other current transformer. When multi-leaf busses
are used, the busses shall be oriented so that they appear "edgewise" when viewed from
the access panel.
F. Instrument-Transformer Compartments
2. Covers for instrument transformer compartments shall be made of code gauge metal. If
nonhinged panels are used as covers, they shall be provided with lifting handles and be
attached with sealable studs and wingnuts or by other approved means.
3. Copper or aluminum buss bars shall be used on both the line and load sides of all current
transformers. When aluminum bus is used, the bus bars shall be plated, (See Bus Bar Plating,
Drawing 300).
4. When the serving agency requests links and supports for through-type current transformer(s),
the bus and removable links must be of a compatible material.
5. Instrument transformers supplied by the serving agency for metering shall not be utilized for
any other purpose.
6. The ends of the current transformer buss stubs shall be located so the current transformers
can be installed without removing adjacent panels.
8. Except for factory-installed cross-bussing and conductors, either bus or cable, used to supply
the instrument-transformer compartment, no other conductors or devices shall be installed in
the instrument-transformer compartment or in the sealed area above the instrument-
transformer compartment.
A. Switchboards Excluded
This paragraph of the Requirements applies to all meter and service equipment when not
installed on switchboards.
1. General
a. Service termination facilities shall be specifically designed to receive the serving agency’s
underground service lateral conductors as a single cable entry. Enclosures designed for
either overhead or underground cable entry are acceptable provided they meet
requirements for both types of cable entry.
b. Service cable termination lugs or connectors shall be suitable for use with both aluminum
and copper conductors. The serving agency should be consulted for specific lug or
connector requirements.
c. Socket enclosures designed for single sockets rated up to, and including 200 amperes,
shall have service terminating lugs independently mounted from the socket jaw support.
d. Test for meter sockets shall be in accordance with the current Standard for Meter Sockets
UL414.
e. Service terminating space in enclosures rated greater than 200 amperes with multiple
meter sockets shall accommodate either compression-type or screw- type mechanical
landing lugs. All bussing or cable conductors beyond the terminating lugs shall be
provided by the manufacturer or the customer’s contractor. Bus stubs or bussing in the
service terminating space used for terminating the utility service lateral shall have
mounting bolts spaced in accordance with NEMA Standards. For termination buss detail,
(see Drawing 343.)
g. Wireways in the service termination space designed for terminating the utility service
lateral shall be clearly identified for such use. Service termination shall be made in the
service termination enclosure or in a specially designed space a meter panel which has a
separate removable and sealable access plate.
h. The layout or design of the service termination enclosure that requires bending the utility
service conductors should provide space to permit a minimum cable bending radius equal
to four times the overall diameter of the cable measured from the inner surface of the
cable (from Minimum Bending Radius for Thermo- Plastic Insulated Cables, IPCEA S-61-
402 and NEMA WC 5-1961 Standards).
NOTE: The overall termination enclosure size is not predicated solely on the cable bending
radius. Adequate working space and electrical clearances are also considered in
establishing enclosure dimensions in these requirements.
i. The service termination enclosure, socket enclosure and test-bypass disconnect block
section shall be sealable and isolated or barriered from other integral enclosure sections
which are accessible to the customer to effectively prevent unauthorized connections to
unmetered conductors or terminals.
j. The manufacturer’s rating label, or other markings used in lieu of a label, shall show
among other things:
(1) The socket or socket enclosure is designed for overhead service entry, underground
service entry, or both.
(2) The terminating lugs are designed for both aluminum and copper conductors.
a. The socket and enclosure shall be specifically designed to receive service cables from an
underground supply system. Separate service terminating lugs supported independent of
the socket and connected by buss bars are required for single family residential meter
socket enclosures, (See Drawing 301).
c. A separate removable cover, independent of the meter panel, is required in front of the
pull section, (See Drawing 301).
d. Knockouts in cable wireways shall be positioned to minimize service lateral cable bending.
e. The service cable entry and the meter socket section shall be sealable and isolated or
barriered from other integral enclosure sections which are accessible to the customer to
effectively prevent the attachment of unauthorized connections to unmetered conductors
or terminals.
f. The load wires from the distribution section (branch circuits) shall not pass through any
sealable section.
B. Switchboards
a. For underground services, the serving agency will terminate its service conductor on lug
landings at the current transformer bus stubs only when the service is a single-meter
installation, and the switchboard is rated 400 amperes or less.
NOTE: Some utilities require the service conductors to be terminated in the pull section
for switchboards rated less than 400 amperes.
(i) The serving agency will terminate its service conductors on lug landings the pull
section when the service is for multiple metering or the switchboard is rated 401
amperes or larger, (see Figure 1 on Drawing 345).
(b) On switchboards rated 800 amperes or with multiple meters, bus bars shall
extend from the service terminating lug landings into the current transformer
compartment or the meter sockets.
For overhead services, the customer shall furnish lugs and connect the cable to line and load
sides of the bus stubs in the current transformer compartment, (see Drawing 348).
7 Require only one set of utility termination for combination UG/OH residential meter 10/08
panel rated up to 225 Amperes
Latest Revision Revised Information Edited Information Removed
4 Add requirement for securing screw on the Pull Section cover 10/08
4 Add requirement for securing screw on the Pull Section cover 10/08
5 Add requirement for securing screw on the Pull Section cover 10/08
5 Add requirement for securing screw on the Pull Section cover 10/08
2 Add requirement for securing screw on the Pull Section cover 10/08
2 Add requirement for securing screw on the Pull Section cover 10/08
2 Add requirement for securing screw on the Pull Section cover 10/08
02/97
02/97
7 Removed Dimensions 6-3/16” & 6 9/16” and Revised Note 1 – Project#030202 12/04
7 Removed Dimensions 6-3/16” & 6 9/16” and Revised Note 1 – Project#030202 12/04
1 New Drawing Moved from Drawing 327 and Revised for Clarity 11/94
400 I. SCOPE 1
II. SWITCHGEAR WITH FUSED VOLTAGE
TRANSFORMERS 1
A. GENERAL 1
B. BUS BARS AND CONDUCTORS 3
C. TERMINATIONS 4
D. INSTRUMENT TRANSFORMER MOUNTING
BASE AND BUS LINKS 4
III. METERING COMPARTMENT (15,000 VOLTS MAX) 5
A. VOLTAGE TRANSFORMER DISCONNECT
REQUIREMENTS 5
B. ALTERNATE METER PANEL LOCATIONS 6
IV. INSTRUMENT TRANSFORMER MOUNTING 6
V. FUSE SPECIFICATION 6
VI. METERING COMPARTMENT (15001 TO 27000
VOLT SERVICE) 6
DRAWINGS
SECTION
This section of the requirements applies only to revenue metering compartments of indoor and
outdoor metal-clad switchgear for 601 through 27,000-volt installations. (See Drawings 401 and 404
for enclosure requirements.) Front access medium voltage switchgear is acceptable.
A. General
1. Drawing Approval
The manufacturer shall submit copies of the design drawings to the serving agency as
required for high-voltage metering equipment prior to fabrication. Such drawings shall
indicate the customer's name, the job address, the contact address, and the telephone
number of the manufacturer's representative.
Compartments of the metering enclosure shall be permanently labeled with machine engraved
laminated phenolic (or equal) tags. Tags shall have quarter-inch white letters and numbers
on red colored material that is readily visible and mechanically attached to the face of the
following designated compartments.
Bare bus 7 inches above and below the current transformers shall be provided to permit
application of serving agency safety grounds. A grounding knob may be provided on the line
and load side of the bus at each current transformer location.
Meter panel and hinges are to be designed to adequately support a 25-pound load applied at
the unsupported end with 1/8-inch maximum sag when open. Bond meter door to switchgear
enclosure with a #4 AWG flexible braided bond wire, (See Drawings 408 and 409 for meter
panel layout).
5. Lifting Handles
When lifting handles are required on panels and covers, each handle shall be sized for full
hand grasping, securely attached, and have strength to withstand handling stresses of 75
pounds minimum (See Drawings 401, 408, 409 and 418).
Note: Chest type handles with a folding bale grasp are not acceptable.
6. B.I.L. Rating
B.I.L. (Basic Impulse Level) for the metering enclosure shall not be less than the customer's
associated switchgear. Reference shall be made to ANSI Standards for the minimum
acceptable.
B.I.L. ratings for high voltage switchboards built to the listed nominal voltages shown in the
applicable tables "Voltages and Insulation Levels for AC Switch Gear Assemblies" and as
tabulated for Metal Enclosed Interrupter Switchgear. The metering cubicle shall be labeled
with the B.I.L. rating.
4.76 60
8.25 75
15.0 95
27.0 125
Working clearances (*) at the customer's job site may determine if the manufacturer is to
furnish either a single or double full height hinged rear door access. Provisions for a three-
point locking mechanism with hardware for attachment of the utility-furnished padlock are
required.
All external doors shall, when open, be equipped with a device to hold the door at 90 degrees
or more.
Enclosure sketches on the following drawings show equipment with weatherproof doors. The
meter panel shall be hinged on the side opposite that of the outer door on weatherproof
units to permit 90-degree openings with the meters and test facilities in place. The
weatherproof doors may be omitted if the equipment is located indoors. If the outer door is
omitted, the meter panel must be lockable. The front weatherproof door shall be a single door
equipped with a latch-type handle to accommodate the serving agency's padlock.
9. CT and VT Installation
Current transformers, voltage transformers, meters, testing facilities, and all normal
secondary wiring from the transformers to the meters will be furnished and installed by the
serving agency.
(*) (Consult with utility for working clearance. Working clearances are governed by utility,
code and customer requirements. Clearances can vary.)
When the main switch or circuit breaker enclosure is adjacent to and on the source side of
the metering enclosure, connections from the load side of the main switch or circuit breaker
to the line side of the current transformers shall be made using bus bars.
When full BIL insulation cables or buses pass through compartment walls, full voltage and a
BIL insulation system shall be provided.
For service ampacities up to 800 amperes, one landing position (*) shall be provided on each
phase and neutral bus for every 400 amperes, or portion thereof, of service ampacity. All
bolts shall be secured in place and provided with nuts and pressure maintaining spring
washers. All parts must be plated to prevent corrosion. Consult the serving agency for
termination requirements when the ampacity exceeds 800 amperes.
Note: When Belleville (cone) washers are used, the manufacturer shall provide a label with
the required torque setting. This label shall be in a readily visible location within the
compartment that the washers are being utilized.
(*) Two 1/2-inch steel bolts on 1-3/4-inch vertical centers extending 1 inch minimum to 1-
1/2 inches maximum from the mounting surface. Terminating bolts must be secured in place.
“Secured in place” shall mean that the stud will not turn, back out, or loosen in any manner
when tightening or loosening terminal nuts (including cross-threaded situations).
When an insulated neutral is required, it shall have full voltage rated insulation from the
metering cubicle. Consult the serving agency to determine if an insulated neutral is required.
Voltage transformer and current transformer mounting bases are to be provided by the
manufacturer, (See Drawing 407).
1. Voltage Transformers
Locate the front or leading set of voltage transformer mounting holes 9 inches from the
voltage transformer compartment door.
The current transformer bus units shall be drilled and spaced to accept the current
transformers of the proper rating and class, (See Drawing 407, 2 of 2) and permit installation
and removal of individual transformers without disturbing adjacent transformers. Center bus
shall include a removable link dimensioned the same as the current transformer bars on the
metered phases.
Lugs for voltage transformer phase and neutral connections shall be provided in the voltage
transformer compartment.
4. Fuse Specification
Voltage transformer fuses shall be furnished and installed by the serving agency. The
manufacturer shall provide mounting clips for indoor current limiting fuses with mounting clip
separation and fuse ferrule diameter appropriate for the voltage rating of the equipment.
Fuses shall be accessible through V.T. interlocked compartment door.
1. Key Interlocking is required between the voltage transformer disconnect and the voltage
transformer compartment door so that, for personal safety, the voltage transformer
compartment cannot be entered until all the following conditions are met:
b. When the voltage transformer disconnect is fully open, the disconnect blades must
ground automatically.
2. The interlock system must prevent closing of the disconnect without first closing and locking
the voltage transformer compartment.
3. The local utility will be provided with two keys for the interlock system.
4. Primary contacts for the voltage disconnect shall be of the blade and jaw design or equivalent
to assure continued adequate contact. Wiping contact or pressure contact is not acceptable.
5. Operating handle or lever of the voltage transformer disconnect switch shall be pad lockable
in the closed position.
6. The voltage transformer compartment door shall provide unobstructed access to the voltage
transformer and fuses.
2. All external and internal doors providing access to the CT bus including the outer door, meter
panel door, and hinged barrier shall be equipped with a device to hold them open at 90
degrees or more.
V. FUSE SPECIFICATION
Voltage transformer fuses shall be furnished and installed by the serving agency. The manufacturer
shall provide mounting clips for indoor current limiting fuses with mounting clip separation and fuse
ferrule diameter dimensions as shown on Drawings 401 and 404.
A. Vertical busing in the pull section and C.T. compartment shall be spaced 18 inches on the
centerline between phases and the center phase shall be on the enclosure centerline.
B. Current and voltage transformers will be outdoor type. Provide the transformer mounting bases
and busing configuration (in the C.T. compartment) to accommodate this style of transformer.
Consult utility for manufacturer catalog number and obtain the C.T. drawing.
5 DELETED DIMENSION "F", ADDED NOTE TO DIMENSION "G", PROJECT #040203 12/04
5 DELETED DIMENSION "F", ADDED NOTE TO DIMENSION "G", PROJECT #040203 12/04
5 DELETED DIMENSION "F", ADDED NOTE TO DIMENSION "G", PROJECT #040203 12/04
1. The panel shall be single, full-height door constructed of 12-gauge (Minimum) steel and furnished with
a meter ring, meter socket, sealing ring and a slotted opening with a removable plate for installation of
a test switch. The plate shall be attached to the rear of the panel with screws that do protrude through
the face of the panel. The edges of the plate and the slotted opening shall be smooth to prevent damage
to the meter wiring. See Drawing 409 for meter socket, test switch cutout and removable plate details.
2. The panel shall be equipped with hinges. The hinges shall permit the panel to open to 90 degrees and
shall be easily interchangeable, right or left, on the meter socket panel. Removable pin type hinges
shall be removable from the top.
3. The panel shall have a handle attached on the side opposite the hinges.
5. The panel shall be bonded to the switchboard enclosure with a flexible, brained wire installed across
the hinges.
6. A clear barrier shall be provided to isolate the current-transformer compartment from the meter panel.
The barrier shall be hinged with a door stop and must close with the serving utility’s current
transformers installed without the barrier contacting the transformers.
7. One inch, non-metallic, V.T. and C.T. conduit shall be located on the hinged side of the meter panel at
a maximum of 75 inches above the standing surface. The conduits shall be continuous conduits with
no junction boxes or condulets.
8. The alternate meter panel arrangement is shown as a weatherproof enclosure with an exterior door.
SECTION SHEET
500 1. PURPOSE 1
2. APPLICABILITY 1
3. EXCEPTIONS 1
4. DEFINITIONS 1
5. STANDARDS 3
7. METERING REQUIREMENTS 4
8. A/C DISCONNECTS 4
DRAWINGS
These electric service requirements include information and criteria for use by utilities, employees and
customers regarding the interconnection and parallel operation of all distributed generation sources
within a utility’s distribution system. The requirements presented herein are to ensure the safety of
both the utility and customer personnel and property.
2. Applicability
3. Exceptions
Exceptions to Section 500 may be granted following engineering review and approval by the serving
utility and provided that appropriate labeling criteria are met.
4. Definitions
On Site Generation System is a facility or energy system used to generate electricity that:
a) Uses renewable energy to generate electricity.
b) Isolated from the distribution system at the customer’s premises when the Utility grid is de-
energized.
c) Operates in parallel with the utility’s distribution facilities
d) Intended primarily to offset part or all the customer’s requirements for electricity
Disconnect Switch: A visibly open (with the door open, the air gap must be visible at the trailing
edge of the moveable disconnect blades when the switch is in the open position) disconnect device
that the customer is required to install and maintain in accordance with the requirements set forth
herein. It will completely isolate the customer's generating facility from the electric utility’s distribution
grid.
Distributed Generation: Any type of customer owned electric generator, static inverter, or
generating facility that has the capability of being operated in parallel with an electric utility’s
distribution system.
Distribution System: The infrastructure constructed, maintained, and operated by a utility to deliver
electric service to retail customers at primary and secondary distribution voltages.
Generating Facility: All or part of the customer's electrical generator(s) or inverter(s) together with
all protective, safety, and associated equipment necessary to produce electric power at the customer's
facility.
Interactive Static Inverter: A power electronic device that converts DC power to AC by means of
electronic switching. For purposes of this document, only those static inverters designed to
automatically separate from the utility’s distribution system upon loss of voltage from the utility and
prior to reclosing voltage from the utility side will be acceptable for interconnection of customer owned
equipment.
Meter:
1. NET Meter-- A meter designed to measure the power or energy delivered or received from
the customer.
3. Revenue Meter-- A meter designed to measure only the power or energy delivered to the
customer.
Parallel System: A generating facility that is electrically interconnected to a bus common with the
electric utility’s distribution system either on a momentary or continuous basis
All customer equipment shall conform to the nationally recognized standards and recommended
practices. These include, but are not limited to the following:
(a) NFPA 70E, 2018 130.5(C) –National Fire Protection Association Electrical Safety Code
(b) NFPA 70, 2020 - National Fire Protection Association Nation Electrical Code (NEC)
(c) IEEE 1547-2018 Standard for Interconnecting Distributed Resources with Electric Power
Systems
(d) IEEE 1547.1—Standard for Conformance Test Procedures for Equipment Interconnecting
Distributed Resources with Electric Power Systems
(f) IEEE 519-Recommended Practices and Requirements for Harmonic Control in Electrical
Power Systems
(h) UL 1741-SA Inverters, Converters, Controllers, and Interconnection System Equipment for
Use with Distributed Energy Resources
DESCRIPTIONs or modifications to the approved design shall not be made without prior approval.
If DESCRIPTIONs or modifications are desired, the customer must submit the revised plans
including the DESCRIPTIONs or modifications for utility approval.
(a) General
The customer shall provide and install all necessary metering sockets and cabinets as required in
locations approved by the utility. The utility will furnish and install the revenue meter (or revenue
net meter) at the point of delivery to the customer's facility.
Informational Note: For systems participating in the various incentive programs, the utility may
require a performance meter.
Additional equipment shall be selected from an approved materials list provided by the serving
utility.
The performance meter socket shall be wired so the output from the customer’s inverter will be
properly measured by the meter. The performance meter and utility disconnect will be installed
in a location readily accessible by the serving utility during normal business hours. Under no
circumstances shall any metering enclosure be used as a conduit or raceway for any conductors
other than those phase conductors being metered and the associated grounded conductor
(neutral) and grounding conductor (equipment ground).
The performance/production meter shall be located within sight and 10 feet of the revenue meter.
All related metering enclosures and equipment shall be grounded in compliance with the NEC and
any applicable local codes.
8. A/C Disconnects
(a) General
When required by the serving utility, the customer shall provide and install a disconnect switch
to isolate all ungrounded conductors from their alternative generating facility to the utility’s
distribution system. The switch shall be a gang- operated, load-break device with a visible airgap
in the open position. It shall be rated for the current and voltage requirements of the customer’s
generating facility and shall be lockable in the open position.
The utility AC disconnect, and all required AC disconnects shall be within sight and 10 feet of the
customer's service entrance section. AC disconnects shall be accessible and operable to serving
utility always.
(c) Labeling
1.) Labels shall be permanent and suitable for the environment and shall be either engraved
phenolic or comply with ANSI Z535.4. Lettering shall be minimum 3/8” high and in all
capitals. Consult serving utility for specific requirements.
a. Circuit breaker shall be labeled as required by the NEC edition adopted by the
authority having jurisdiction.
WARNING
NEC 690.17(E)
c. Label AC disconnects:
PHOTOVOLTAIC
AC DISCONNECT
AC DISCONNECT
3.) Where the Performance meter is not grouped with the utility meter provide a label with
the following information:
SECTION SHEET
G 1. GENERAL REQUIREMENTS 1
2. LISTING 1
4. METER SEQUENCE 1
6. ESTABLISHMENT OF SERVICE 2
7. TYPE OF SERVICE 2
22. GROUNDING 7
DRAWINGS
G6 BLANK
a. These guidelines are based on typical utility practices that are deemed necessary to supply uniform
satisfactory and safe service. Interpretations or clarifications of intent of these Requirements are
subject to individual utility approval. Installations shall also conform to the provisions of applicable
codes and ordinances of local inspection authorities.
b. All meter and service equipment installations shall comply with the service requirements of the
serving utility, and with rules and regulations of the inspection authorities having jurisdiction.
2. LISTING
All meter sockets, boxes and enclosures shall be listed by a qualified electrical testing laboratory
acceptable to the jurisdiction having the authority.
All safety socket boxes with factory installed test-bypass disconnect facilities shall be listed by a
qualified testing laboratory and shall have a continuous-duty rating not less than the service
equipment ampacity.
4. METER SEQUENCE
a. Hot Sequence
This metering arrangement provides for the line current to enter the meter and then the
disconnecting means and overload protection devices (Meter-switch-fuse sequence).
For multiple meter installations, refer to local codes.
b. Cold Sequence
This metering arrangement provided for the line current to enter the disconnecting means and
then the meter (Switch-meter sequence).
Transformer compartments are normally required if either the rated capacity of the service switch
exceeds 200 amperes or the capacity of the conductors supplying a breaker or group of breakers
exceeds 200 amperes. Refer to Section 200 for individual utility requirements.
Electric service will not be established until the service entrance facilities are satisfactorily completed
by the customer. In those areas where local ordinances require permits and final inspection, the
serving utility will not establish service until the installation has passed inspection.
7. TYPE OF SERVICE
Since the type of service available may vary with the locality, it is important that the customer consult
the local office of the serving utility for this information before proceeding with the purchase of
equipment or installation of wiring.
a. The customer shall furnish, install and maintain the service entrance conductors and service
equipment beyond the point of attachment to the overhead service drop or underground service
conductors. All conductors between the overhead service outlet, underground splice box, or pull
section and meter enclosure shall be suitably enclosed and protected and shall not be concealed
except with express consent of the serving utility.
b. The type and size of the service entrance conductors shall conform to the ordinance and codes of
the local inspection authority. Where there is no ordinance requirement, they shall conform to
current standards of the National Electrical Code. In no case shall the service entrance conductors
be smaller than No. 8 AWG.
c. In the Requirements, the capacity of the service switch has been used as the basis for determining
the size of other related equipment. In those cases where a main service switch is not used, the
rating of the service equipment shall be considered as the service switch capacity.
d. In general, a building will be supplied through only one set of service conductors of the same
voltage classification.
All service or supply conductors shall enter the service sections through one end and leave through
the opposite end of the metering transformer compartment. This stipulation applies to either overhead
or underground service, or if two or more adjoining service sections are connected.
For overhead services, the customer shall furnish lugs and connect the cable to line and load sides of
the bus stubs in the current transformer compartment.
a. For underground services, the serving utility will terminate its service conductors on lug landings
at the current transformer bus stubs only when the service is a single-meter installation, and the
switchboard is rated 400 amperes or less.
b. The serving utility will terminate its service conductors on lug landings in the pull section, as shown
in Figure 1 on Drawing 345, when the service is multiple metering, or the switchboard is rated 400
amperes and above.
c. On switchboards rated 401-800 amperes, the customer shall install conductors from the service
termination lug landings to the line side of the current transformer compartment.
NOTE:
1) Some utilities require the service to be terminated in the pull section for switchboards rated
under 400 amperes.
2) When a neutral tap is required for metering, provide a dedicated termination point separate
from the service neutral termination.
If landing lugs are provided in the pull section, bus bars (or cable) shall extend from these
landing lugs to the CT bus stubs.
Bus bars (or cable) shall extend from the landing lugs in the pull section to the CT bus stubs.
Bus bars shall extend from the service-terminating stubs in the pull section to the CT bus stubs.
a. Electric meter installations shall be accessible to authorized representatives of the serving utility
for reading, testing and inspection always.
Note: Outdoor meter locations are preferred. Some of the serving agencies prohibit the installation
of meters inside any building. Consult the serving utility.
b. When adequate exterior wall space is not available, the architect or builder may provide a meter
room accessible from outside the building in which the required number of meter sockets may be
properly installed. Consult the serving utility.
1) Dwellings or Apartments
Meter sockets shall be installed on or enclosed in exterior walls and shall be located so the
meters will be accessible for reading or testing without entering the building. Future building
or other structural DESCRIPTIONs shall not render the meters inaccessible.
Meter sockets may be installed as required for dwellings or apartments or installed inside the
building provided, they are in a public area or meter room. Consult the serving utility.
3) Multi-Story Buildings
b) When the plan of a meter socket location has been established for a building, any
additional meter sockets shall conform to that plan.
4) In any doorway
7) In any place where moisture, fumes or dust may interfere with its operation or
materially damage the meter.
10) In any enclosed show window or one having a bulkhead or raised platform
14) On any balcony or mezzanine floor unless such balcony or mezzanine floor has a
clear stairway of normal tread and rise and with utility approval
15) On or enclosed in any bedroom wall or bedroom closet wall without permission
from the serving agency
16) On or recessed in the external surface of any wall or any building that is built within
three (3) feet of any property line or on the line of any walk, alley or driveway giving
access to commercial or industrial property except when permitted by the serving
utility.
17) In any underground vault or other depressed location unless such location is
approved by the serving agency and is accessible by a stairway of normal tread and
rise. Entrance to the location shall be through a vertical doorway not less than 30
inches wide and 72 inches high.
In multiple occupancy buildings, all meters shall be mounted at a common location or as otherwise
specified by the serving utility. This same general rule applies when one or more meters are added
to existing meters for a multiple occupancy building.
a. Each meter position and each service switch or breaker shall be clearly and permanently identified
by the customer to indicate the location supplied by it. The relation of the socket, breaker, and
dwelling served must be easily discernible. Meters will not be installed until the marking is
complete.
b. Examples of permanent marking are: (1) an identification plate attached by screws, rivets or a
secure adhesive, (2) non-removable, by usual solvents, paint applied with stencil or careful
lettering, or (3) commercially available decals designed for this purpose.
c. Clear identification means a legible street address, apartment or store number. Store name may
be included but it does not constitute a location designation.
Customer locking means for meter enclosures shall provide independent access for the serving
utility.
a. A level standing and working surface shall be provided and maintained in front of each metering
installation. A clear and unobstructed working space shall be provided above this surface.
b. The width of the working space shall be sufficient to permit ready access to the metering
equipment in no case less than 3 feet. The height of the working space shall be equal to the
overall height of the metering installation and in no case less than 7 feet, 1 inch. The working
space shall extend at least 3 feet in front of the surface on which the metering equipment is
mounted and 10 inches from the meter centerline to any side obstruction and 9 inches from the
meter centerline to any obstruction above the meter.
Meters shall be located not more than 75 inches and not less than 48 inches above the ground
or standing surface when installed outdoors. When installed in a cabinet or indoors in a meter
room, the minimum height may be reduced to 36 inches. The meter height shall be measured to
the meter axis.
a. Sockets for self-contained meters shall be furnished, installed and wired by the customer.
b. Sockets for instrument transformer installations shall be furnished and installed by the customer.
Refer to Section 200 for individual utility requirements or exceptions.
a. For self-contained meters, the customer shall terminate the wiring. The socket shall be equipped
with terminals of sufficient size to install the conductors without removing any strands of wire.
See Drawing G-1 for connection diagrams.
b. For instrument transformer-rated meters, the serving utility will furnish and install the normal
secondary wiring from the metering transformers to the meter socket.
Customer’s unmetered service wires and metered load wires are not to be run in the same conduit,
raceway or wiring gutter. Metered and unmetered wires shall be separated by suitable barriers.
Metered wires from the customer’s distribution section (branch circuits) shall not pass-through
sealable sections. For exceptions, see Drawing 300, sheet 4, note K.
22. GROUNDING
Lugs for terminating the user's ground wire (or other grounding conductors) shall be located
outside of the sealable section and shall be designed to readily permit the user's neutral system
to be isolated, when necessary, from the serving utilities neutral.
a. The secondary conduit run between the instrument transformer enclosure and the safety socket
box shall not exceed 15 feet. The minimum size of the secondary conduit shall be 1-1/4 inches.
a. No connections shall be made in the instrument transformer enclosure to supply any other meter
or more than one load circuit.
b. When the neutral conductor is part of the service, it shall pass through the instrument transformer
box, be continuous, and be capable of being bondable to the box.
c. The instrument transformer box may be used as a combination service pull and current
transformer-mounting box for residential underground services when the service conductors
supply only the one customer. The underground service conduit shall enter the center of the lower
end of the instrument transformer box.
a. The serving utility shall be consulted prior to manufacture of the switchgear to determine the type
of metering, size of current and/or voltage transformers, and any special arrangement(s)
necessary for mounting instrument transformers.
b. The rating of the current transformers will not necessarily be the same as the service switch.
c. All compartments containing unmetered conductors shall be sealable. When a raceway or conduit
for meter secondary wiring is necessary, such raceway or conduit shall be sealable.
d. The current transformers supplied by the serving utility for metering shall not be utilized for any
other purpose.
a. In cases where more than one meter is to be installed, there will ordinarily be a separate service
section for each meter installation and its associated service switch.
b. Regarding services with self-contained meters (not using current transformers), it may be
practicable to put two or more meters and switches in the service section.
c. When two or more switchboard service sections are supplied from one set of service conductors,
the supply conductors serving these switchboards shall be terminated ahead and outside of the
metering transformer compartments in a separate sealable enclosure. The supply conductors are
to be arranged so they are readily accessible without disturbing the metering transformers and
associate secondary wiring.
Switchboard design which does not conform to the standard switchboard is considered specially
engineered and includes installations:
b. Where the service breaker ampacity rating exceeds that of the standard service section.
C Cabinet 316-318
Current Transformer
C.T. and Meter 313-314
Meter G-6
Test Blocks 340
Cable Terminations 300/9, 400/3
Class 320 Meter 302
Clearance, Meter 353
Conductors, Unmetered 300/3/5/6/9/10, G-8
C.T. Bus
Compartment 330, 331
Mounting Base 319-324, 328, 329
Cubicle, High Voltage 401, 404
The purpose of this section is to define and make clear the meaning of certain words and phrases
concerning electrical metering and service equipment used in these requirements as understood by this
committee. These definitions apply specifically to these requirements.
ACCESSIBLE - A location in which the utility terminating, and metering equipment is available for reading,
testing and inspecting as required by the serving utility.
ACCESS OPENING - The minimum opening of a pull section or termination enclosure required for utility
work access. This opening is measured from the edge of one flange to the other: not from sidewall to
sidewall.
AUTOMATIC BYPASS - A device within a meter socket that automatically operates upon removal of the
meter from the socket and that allows current to flow from the line side socket clips to the load side socket
clips with the meter removed from the socket.
BACKFEED - The energizing of a utility’s distribution system from a non-utility generation source.
BILLING METERING - Electricity meter, recorders and associated devices used by the utilities to measure
electric energy consumed by the customer as necessary to implement a given rate schedule.
BONDABLE - Capable of the permanent joining of metallic parts to form an electrically conductive path
which will assure electrical continuity and the capacity to conduct safely any current likely to be imposed.
BUS, LAMINATED - More than one bus bar per phase, connected in parallel.
BUS, REMOVABLE LINK - Used in a current transformer compartment to link the line and load bus
together. This removable section of bus is designed to allow the utility to install current transformers.
BUSWAY SERVICE HEAD - Termination facilities required when terminating high voltage service
conductors to bus bars enclosed by a raceway (bus duct).
CAPTIVE SCREWS - Screws used to attach removable metering panel covers on switchboards or
enclosures and designed to stay attached to the panel cover when the cover panel is removed.
CLEARANCE, RADIAL - The clearance required around a termination facility measured from the sides, top,
and bottom of the termination surface area. See: CLEARANCE, BARREL OF PROXIMITY.
COMMITTEE RECOGNIZED - Approval and accepted by a majority vote of a quorum of EUSERC member
utilities.
CONDUCTORS METERED - Conductors transmitting electrical energy which has been previously recorded
by the utility's billing metering.
CONDUCTORS, UN-METERED - Conductors transmitting electrical energy which has not been recorded by
the utility's billing metering.
CONNECTOR, PRESSURE - A device that establishes a connection between two or more conductors or
between one or more conductors and a terminal by means of mechanical pressure and without the use
of solder.
CUSTOMER - Any person, persons, corporation, etc. or their designated representative, for whom the
electrical service and meter installation is provided.
DISCONNECT SWITCH – A visibly open (with the door open, the air gap must be visible at the trailing
edge of the moveable disconnect blades when the switch is in the open position) disconnect device that
the customer is required to install and maintain in accordance with the requirements set forth herein. It
will completely isolate the customer’s generating facility from the electric utility’s distribution grid.
DISTRIBUTION SYSTEM – The infrastructure constructed, maintained, and operated by a utility to deliver
electric service to retail customers at primary and secondary distribution voltages.
ELECTRIC UTILITY - An organization which owns, operates and maintains the distribution and delivery of
electricity to its customers for compensation except where electricity is generated on or distributed by the
producer through private property solely for its own use or the use of its tenants and not for the sale or
transmission to others.
ENCLOSURE - Box-like structure designed to enclose and protect utility service conductors or equipment.
FILLER PANEL - The panel used on a switchboard in conjunction with a meter panel to affect a cover over
the total instrument transformer enclosure opening.
GENERATING FACILITY - All or part of the customer's electrical generator(s) or inverter(s) together with
all protective, safety, and associated equipment necessary to produce electric power at the customer's
facility.
GROUNDING LUG - Lug designed for terminating the customer's grounding wire.
HANDLES, LIFTING - Handles attached to meter and service equipment panels to aid in the panel
removal/replacement and open/close operation. They are to be non-folding grasp type designed to provide
full secure attachment and the ability to withstand stress of a 75-pound load.
INTERACTIVE STATIC INVERTER - A power electronic device that converts DC power to AC by means of
electronic switching. For purposes of this document, only those static inverters designed to automatically
separate from the utility’s distribution system upon loss of voltage from the utility and prior to reclosing
voltage that must be restored from the utility side will be acceptable for interconnection of customer
owned equipment.
INSTALLATION GUIDE - Drawings illustrating typical utility metering and service equipment installations.
Each utility should be consulted regarding their requirements.
LINE WIRES - See CONDUCTORS, UNMETERED. LOAD WIRES - See CONDUCTORS, METERED.
LUG, RANGE-TAKING - Lug designed to accept more than one size cable within a specified range.
METER HEIGHT - Meter height is the distance measured from the center axis of the installed meter and
the standing surface.
METER, BOLT-IN TYPE - Self-contained meter designed to be bolted into the meter enclosure. Not
considered a socket-type meter.
METER MOUNTING DEVICE - Meter enclosure used to mount BOLT-IN type meters.
METER PANEL - Panel used exclusively for mounting meter sockets and associated equipment.
METER PANEL, SPLIT - Switchboard meter panel assembly consisting of two single meter panels.
METER PEDESTAL - Free standing meter enclosure typically used for residential or commercial
applications. Installed by bolting to a concrete slab.
METER POST - Free standing meter enclosure typically used for residential mobile home service. Installed
by burying in the earth.
METER SEQUENCE - The sequential relation between the service switch and the utility's billing meter in a
series arrangement. The term New Sequence means a meter-switch-fuse sequence. Old Sequence means
a switch-fuse-meter sequence.
METER SOCKET - Socket designed to receive socket-type meter and sealing rings.
METER, SOCKET TYPE - Self-contained or instrument transformer type watt-hour meters designed to be
inserted into a compatible socket. The socket, in turn, is connected into the circuit to be measured.
MULTIPLE METERING - Prefabricated service equipment consisting of a service termination section and
two or more-meter sockets.
NET METER - A meter designed to measure the power or energy delivered or received from the
customer.
ON SITE GENERATION SYSTEM - A facility or energy system for the generation of electricity that:
PERFORMANCE / PRODUCTION METER - A meter designed to measure only the energy output from the
customer’s alternate generation source i.e., inverter.
POINT OF INTERCONNECTION (DELIVERY) - The physical location where the electric utility’s service
conductors are connected to the customer’s equipment to allow parallel operation of the customer’s
generating facility with the utility’s electric distribution system (Back feed breaker is defined in the NEC)
PULL SECTION - The compartment in a customer's switchboard where the utility's service conductors are
terminated.
RACEWAY - An enclosed channel designed expressly for holding wire, cables or bus bars. If designated
for line conductors, it must be sealable. The intermixing of line and load conductors in the same raceway
is not permitted.
REVENUE METER - A meter designed to measure only the power or energy delivered to the customer.
SAFETY SOCKET BOX (self-contained metering) - An independent self- contained meter socket box
equipped with test-bypass disconnect facilities.
SAFETY SOCKET BOX (transformer-rated metering) - An independent meter socket box used when
installing transformer-rated and associated metering devices in a location remote from the instrument
transformer compartment.
SEALABLE - Normally, the provision for the installation of the utility's lead and wire seals. Other devices
such as padlocks may be specified for sealing.
SEALING RINGS - Device used to hold socket-type meter in place, in a ring type socket, with provision for
installing the utility's lead, wire, hardware, or similar type seals.
SEALING STUD - A 1/4"-20 (minimum) stud drilled with a .0635" (minimum) drill. Used for sealing
purposes.
SEALING WING-NUT - A 1/4"-20 (minimum) wing nut with one wing (minimum) drilled with a .0635"
(minimum) drill. Used for sealing purposes.
SPLICE CHAMBER - An enclosure used by the utility to pull and splice service conductors (SPLICE BOX).
STUD - A threaded machine-type bolt or screw used for attachment of wire or cable connectors.
STUD, SECURED IN PLACE - A stud attached so that it will not turn, back-out, or loosen in any manner
when tightening or loosening terminal nuts, including cross thread situations.
SWITCHBOARD - A large single panel frame or assembly of panels which are mounted switches, over
current and other protective devices, buses, instruments and meters. Switchboards may be accessible
from the rear or sides as well as the front.
SWITCHBOARD, ENTRANCE SECTION - That panel of switchboard that is exclusively occupied by the
serving agency's unmetered conductors. Said conductors may enter this section from overhead or
underground and may terminate to bus stubs. This section shall be sealable.
SWITCHBOARD, SPECIALLY ENGINEERED - A switchboard design which does not conform to the standard
switchboard design and includes one or more of the following:
(2) the service breaker ampacity rating exceeds that of the standard service section.
TERMINATING FACILITIES - Bolt-type pads, bus stubs, or range-taking lugs provided by the customer for
the sole purpose of attaching the utility's unmetered service conductors to the customer's service
equipment.
TERMINATION PAD - A usually flat conducting part of a device to which a connector is fastened.
TEST BY-PASS DISCONNECT FACILITIES - An assembly used in conjunction with a self- contained meter
socket designed to allow the utility to de-energize the meter socket without discontinuing electric service
to the consumer.
TEST SWITCH - An arrangement of small knife switches connected in the secondary instrument
transformer circuit between the instrument transformers and associated meters and metering devices.
The test switch is used by the utility to isolate the metering from the instrument transformers. Also
referred to as METER TEST SWITCHES.
TEST PERCH - A bracket designed for the mounting of the utility's METER TEST SWITCH.
TRANSFORMER, INSTRUMENT - A transformer that reproduces in its secondary circuit a definite and
known proportion of the current or voltage of its primary circuit, with the phase relation substantially
preserved.
TRANSFORMER, CURRENT - An instrument transformer designed for use in the measurement of electrical
current.
TRANSFORMER, VOLTAGE - An instrument transformer designed for use in the measurement of voltage.
WATT HOUR METER, INSTRUMENT TRANSFORMER RATED - An electricity meter used in conjunction with
instrument transformers to accurately measure and register all the electrical energy consumed in the
circuit in which it is connected. The unit of measurement is the kilowatt per hour.
WATT HOUR METER, SELF CONTAINED - An electricity meter that measures and registers all the electrical
energy consumed in the circuit in which it is connected and does not require additional instrument
transformers. The unit of measurement is the kilowatt per hour.
WIRE STOP - A protrusion in conjunction with a terminal block designed to prevent the conductor from
intruding beyond the terminal.
WORKING SPACE - The area provided and maintained by the customer. This area is necessary for the
utility to install, remove, or maintain their conductors or equipment.