You are on page 1of 3

Size & Short Circuit Capacity of D.

G Synchr

D.G Capacity Sub Transient % Reactance


DG's Voltage Rating (KV) Reactance ( Xd")
(KVA) (%Xd")
in PU
1 0.415 1000 0.14 14
2 0.415 1000 0.13 13
3 0.415 2000 0.109 10.9
4 0.415 2000 0.109 10.9
5 0.415 2000 0.109 10.9
6 0.415 1000 0.13 13

Total Capacity of Synchronous Panel


Total Fault level
The equivalent Z at theDG Synch panel by parallel method
Short Circuit Current at DG sync panel is the cumulative of all individual DG short circuit
current
OR
Short Circuit Current at DG Synchronous Panel=(Total Fault level /1.732*E*1000)
apacity of D.G Synchronous Panel
Impedence of the DG( Short Ciruit kVA at DG Short Circuit
Zg) terminal (Psc) Current( Isc ) in KA
(KVxKV/ KVA)x1000 (KVA/%Xd")*100 (Psc/(1.732XEX1000)
0.1722 7142.8571 9.93747341725861
0.1722 7692.3077 10.7018944493554
0.0861 18348.6239 25.5274546498386
0.0861 18348.6239 25.5274546498386
0.0861 18348.6239 25.5274546498386
0.1722 7692.3077 10.7018944493554

9000 KVA
77573.34 KVA
0.0066 Ohm
ividual DG short circuit
97.22 KA

/1.732*E*1000) 107.92 KA
Jignesh.Parmar, jiguparmar@yahoo.com, www.electricalnotes.wordpress.com

Reactance (Zg) in Ohm Equivalent Zg


for Parallel
(% Xd"x kVX KV x 10 / kVA)
0.0241115
0.02238925 0.0116 0
0.0093862625 0.0066 0
0.0093862625 0.0047 0
0.0093862625 0.0047 0
0.02238925 0.0066 0