No. 004

Standard Power Terminations – STC Projects

LLVD (load Low Voltage disconnection) - All Non-Critical Connections


BLVD (battery low voltage disconnection) – All Critical Connections

Rectifier Sub Rack

Rectifier LLVD Breakers Rectifier BLVD Breakers

2G/ 3G / 4G / 5G MW / ATN / RTN /


(Wireless Equipment’s) Eband dock

4G-BTS 4G-BTS
Technology 5G BTS 3G BTS 2G BTS
( DCDU-01) ( DCDU-02)

Breaker Type 1 X 125 A (1P) 1 X 125 A (1P) 1 X 125 A (1P) 1X100 A (1P) 1X100 A (1P)
63A dual pole
Optional Breaker 63A dual pole 63A dual pole
or 125A fuse
Busbar/Distribution LLVD in Rectifier LLVD in DCDB LLVD in DCDB LLVD in DCDB LLVD in DCDB

Technology MW DCDB ATN 950 RTN 980 RTN 950 Eband


2 X 32A (1P)
Breaker Type 2 X 32A (1P) 2 X 32A (1P) 2 X 32A (1P) 1 X 16 A (1P)
2X 20 A ( 1P)
BLVD in Rectifier BLVD in Rectifier BLVD in Rectifier BLVD in Rectifier
Busbar/Distribution BLVD in Rectifier
/MW DCDB /MW DCDB /MW DCDB /MW DCDB

Note: Both Active and standby cannot be connected with same DCDB.