You are on page 1of 33

MODULE 5: ARMATURE REACTION.

 The current to the load is the current in


the armature conductors and is equal to
the sum of the current from the parallel
paths in the armature.
 The current flow in the armature
 Consider Fig. 5.2, which shows the
conductors of a dynamo has an
armature rotating in the magnetic field
important and undesirable effect upon
and the resulting armature current when
the dynamo’s operation. a load is connected to the generator.
 The current in the armature produces
a flux, and it is the interaction
between this flux and the field flux.
 When there is no load connected to
the generator, the current in the
armature conductor is zero.
 Under these conditions, there is only
one magnetic field in the generator,
and that field is produced by the
main-field poles of the generator.
 When several conductors are placed
 This field is represented by an arrow, together, the flux from each conductor is
which indicates the direction of the combined to produce a resultant flux.
magnetic flux from the north pole to Note the direction of this resultant flux.
the south pole as shown below in Fig.  The flux from the conductors on the left
5.1 side of the armature and the flux from the
conductors on the right side of the
armature and the flux from the
conductors on the right side of the
armature and the flux in the center of the
armature that is downward in direction.
 The flux from the conductors on the left
side of the armature and the flux from the
conductors on the right side of the
armature;
 and the flux from the conductors on the
right side of the armature ;
 and the flux in the center of the armature
 A load is now connected to the generator,
that is downward in direction.
and of course current flow exists.
 This is resultant flux can be represented
 The current to the load is the current in
by an arrow as indicated, noting that the
the armature conductors and is equal to
arrow passes through both top and
the sum of the current from the parallel
bottom brushes.
paths in the armature.
 The flux from the conductors on the left
 Consider Fig. 5.2, which shows the
side of the armature ;
armature rotating in the magnetic field
and the resulting armature current when
a load is connected to the generator.
 and the flux from the conductors on the  With the brushes in their present location
right side of the armature and the flux they will be short-circuiting coils in
from the conductors on the right side of which there is a voltage induced,
the armature  thereby producing sparking at the
 and the flux in the center of the armature brushes, undue brush wear, and other
that is downward in direction. unfavorable conditions.
 This is resultant flux can be represented
by an arrow as indicated, noting that the
arrow passes through both top and EFFECT OF BRUSH SHIFTING
bottom brushes.
 There are now two fluxes inside the  If the brushes are no longer at the points
generator, one produced by the main- of minimum flux, or magnetic neutral, as
field poles of the generator and the other the points of minimum flux are known,
by the current in the armature  It might appear to be a simple solution to
conductors. shift the brushes until they do fall on the
 These two fluxes now combine to form a magnetic neutral, and then brushes will
new resultant flux as shown in Fig. 5.3. once again be at the points of minimum
 This new resultant flux is not in the same flux.
direction as the original main-field flux;  However, the following problem arises.
 But runs from the tip of one of the poles, If the brushes are shifted to the new
across the armature, to the tip of the other magnetic neutral, will the magnetic
poles. neutral remain fixed or will it shift
again?
 It has just been seen that the direction of
the resultant flux depends upon both the
flux from the main-field poles and the
flux produced by the current in the
armature conductors.
 The flux from the main –field poles is
fairly constant and will remain constant
 The armature conductors are now cutting even though the generator is supplying
this new resultant flux that is not in the current to a load.
same direction as the main-field flux  If the load current is small, the armature
which the conductors were originally current will be small and the flux
cutting. produced by the armature conductors
 The brushes, it will be recalled from will be small; hence the shift in the
previous module, are supposed to be resultant flux will be small as compared
located at the points of minimum flux, with the main –field flux.
which of course are at right angles to the  The greater the current delivered by the
direction of the flux, generator, the greater the current in the
 Since the brushes were at right angles to armature conductors, and therefore the
the main field flux, they certainly cannot greater the flux produced by the armature
be a right angles to the new resultant conductors, ending with a greater shift in
flux. the direction of the resultant flux.
 The flux from the main –field poles is
fairly constant and will remain constant
even though the generator is supplying  If the load current is small, the armature
current to a load. current will be small and the flux
 If the load current is small, the armature produced by the armature conductors,
current will be small and the flux and
produced by the armature conductors  Therefore the greater the flux produced
will be small; hence the shift in the by the armature conductors, ending with
resultant flux will be small as compared a greater shift in the direction of the
with the main –field flux. resultant flux.
 The greater the current delivered by the  If the brushes are to be moved to a neutral
generator, the greater the current in the position, the new position will depend
armature conductors, and therefore the upon the load.
greater the flux produced by the armature  With the load on a generator constantly
conductors, ending with a greater shift in varying, it would be impossible to preset
the direction of the resultant flux. the position of the brushes and expect
 The flux from the main –field poles is satisfactory results.
fairly constant and will remain constant  If the load on the generator were
even though the generator is supplying somewhat constant, the position of the
current to a load. magnetic neutral would be stationary to
 If the load current is small, the armature some extent and the brushes could then
current will be small and the flux be shifted to the new magnetic neutral as
produced by the armature conductors in Fig. 5.3.
will be small; hence the shift in the  The brushes must be moved in the
resultant flux will be small as compared direction of rotation of the armature
with the main –field flux. when moving from the original position
 The greater the current delivered by the of the magnetic neutral to the new
generator, the greater the current in the position.
armature conductors, and  It is advisable to analyze the effects of
 Therefore the greater the flux produced shifting the brushes to the new position,
by the armature conductors, ending with that is, with the brushes on the new
a greater shift in the direction of the magnetic neutral.
resultant flux.  It should be apparent that the flux from
 If the load on the generator were the main-field poles is dependent upon
somewhat constant, the position of the the field current, and therefore sifting the
magnetic neutral would be stationary to brushes to the new magnetic neutral
some extent and the brushes could then would have no effect upon the magnitude
be shifted to the new magnetic neutral as or direction of this flux.
in Fig. 5.3.  Hence, the flux from the poles is now the
 If the brushes are shifted to the new same as it was before the brushes were
magnetic neutral, it has been seen that the shifted.
direction of the resultant flux depends  The flux from the armature must now be
upon both the flux from the main-field considered. Referring to Fig. 5.4, it is
poles and the flux produced by the seem by Fleming’s right-hand rule that
current in the armature conductors. the conductors under the north pole carry
 The flux from the main-field poles is current away from the observer and the
fairly constant and will remain constant conductors under the south pole carry
even though the generator is supplying current toward the observer.
current to a load.
 The flux from these conductors is seems to have become worse. Before the
indicated on the diagram, and of course, brushes were shifted, the armature flux
the combined flux from all the was at right angles to the main-field flux
conductors is still in a direction from the and therefore produced only a cross-
top of the brush to the bottom of the magnetizing field,
brush. As indicated before that the brush  Somewhat reduced in magnitude,
were shifted. additionally, there is now a
 Note that the flux from the armature demagnetizing field which tends to
conductors is not at right angles to the reduce the main-field flux, resulting in
flux from the main-field poles. lower generated voltage.
 This demagnetizing component was
obtained only after the brushes were
shifted, and the brushes were shifted
because of the change in direction of the
resultant flux, which was due to the
armature conductors carrying current.
 The application of some means to
prevent the shift of the resultant flux
would eliminate the necessity of shifting
 The effects of the armature flux may be the brushes, and hence no demagnetizing
analyzed by considering the flux to field would be produced.
consist of two components that are at
right angles to each other as shown in
HIGH – RELUCTANCE POLE TIPS
Fig. 5.5. One component is a right angles
to the main field, and because this  Referring to Fig. 5.3, it can be seen that
component crosses the main -field flux. the flux from the current in the armature
 It is known as the cross-magnetizing conductors causes the main-field flux to
component of the armature flux. The shift from the center of the main-field
second component is in the same plane as poles to the tips of the poles.
the main-field flux, with the result that it  Because of this shift in the resultant flux,
tends to reduce the effect of the main- the brushes should be moved to the new
field flux, with the result that it tends to magnetic neutral.
reduce the effect of the main-field flux.  If moving of the brushes is to be avoided,
 This component of the armature flux is then the resultant flux must be brought
known as the demagnetizing component back to its original position, with current
of the armature flux. still flowing in the armature conductors.
 Applying the knowledge that most of the
flux follows the path of least reluctance,
poles are designed where the reluctance
at the ends of the poles is greater than the
reluctance at the center.
 This variation in reluctance is obtained
by chamfering the poles; that is, the pole
is so constructed that the greater the
 It appears momentarily, that shifting the distance from the center of the pole, the
brushes has not improved the situation. It
greater the air gap between the pole and
the armature.
 The greater the air gap, the greater the
reluctance. With no current in the
armature conductors, the flux will be
concentrated at the center of the pole, and
when current flows in the armature
conductors, the flux will tend to shift to
the end of the pole.
HORIZONTAL SLOTS IN MAIN-FIELD
 The air gap will offer an increase in
POLE
reluctance to the flux as it moves from
the center of the pole, thereby tending to
keep the flux in the same original
position. The shape of this pole is shown  The high – reluctance pole-tip
in Fig. 5.6. construction reduced the effects of
armature reaction by not allowing the
flux to shift.
 The shift in the resultant flux was caused
by the armature flux. If the armature flux
could be reduced to a negligible value,
 Then its cross-magnetizing effect upon
the main –field flux would be small and
the brushes would have to be shifted.
 Figure 5.8 shows that the part of the path
 The same effect on the flux can be of the magnetic flux is through the field
obtained by a different design of the poles.
main-field pole. The field pole, it should  By cutting horizontal slots in the poles,
be recalled, is built up of laminated sheet several air gaps are introduced in the path
pole. Cutting each lamination into a of the flux.
shape indicated in Fig. 5.7a, we can  These slots increase the reluctance to the
immediately see that there is only one armature flux while having very little
pole tip available from each lamination, effect on the main-field flux. The
and not two. armature flux is materially reduced, and
 When these laminations are stacked so the brushes need not be shifted.
that the first lamination has the tip on the
right, the second lamination has the tip on
left, etc.
 A field pole is developed that has a low
value of reluctance at the center of the
pole while the tips of the pole have a
higher reluctance.
 The effect of this pole construction,
shown in Fig. 5.7c, is the same as the
chamfered-pole construction.
 The flux is concentrated at the center of COMPENSATING WINDINGS
the pole.
 Another method of reducing the armature  If the armature current increases, the
flux on large machines is by the use of compensating current increases, so
compensating windings. that the armature flux us canceled for
 These windings are placed in the pole all load conditions.
faces of the field pole can run parallel to  The compensating flux, being
the armature conductors. opposite in direction to the armature
 A connection is made from one brushes flux, tends to cancel the armature
to one end of this winding, so that the flux.
current from the armature must first pass  If the armature current increases, the
through this winding before going to the compensating current increases, so
load. that that the armature flux is canceled
for all load condition

COMMUTATION

 At this point, let us review the process of


commutation in greater detail.
 Commutation is the process a coil
undergoes after leaving the magnetic
 The direction of current through the field of one pair of poles and just before
winding is opposite to that of the entering the magnetic field of the next
current in the armature conductors pair of poles.
under that pole.  The brushes are located between the
 The location of the compensating poles at the point of minimum flux so that
winding and of the connection to the the brushes will not short-circuit a coil
winding is shown in Fig. 5.9. while there is a voltage induced in the
 Figure 5.9 indicates that the current coil.
in the armature conductors located  The current in the coil also undergoes a
under the north pole carry current change in direction; that is, the current in
away from the observer; the coil is in one direction before
 Therefore the direction of current commutation, and after commutation the
flowing in that part of the direction of current in the coil is reversed.
compensating winding situated in the
north pole is toward the observer.
 The direction of flux due to the
current in the armature conductors
shown in Fig. 5.9 will be from the top
brush to the bottom brush.
 Since the current in the
compensating winding is opposite in
direction to the current in the  Figure 5.10 above, exhibits the current in
armature conductors, the flux the coils of a two-pole generator having
produced by the current in the a gramme-ring armature, the direction of
compensating winding will be current having been determined by the
opposite in direction to the armature right hand rule.
flux.
 The armature of the generator is rotating;  In Fig. 5.12a current flows through coil
therefore the coils are always changing A from left to right and the magnitude of
their position with respect to the poles. the current is indicated in Fig. 5.13 as
 In a consideration that any conductor point 1. as the armature rotates, the brush
located to the left of the brush carries makes contact with the commutator
current in one direction when segment 1 and just touches the segment
approaching the brush and in the opposite 2,
direction when moving away from the  Creating a partial shot circuit across coil
brush. A as shown in magnitude of the current
 Thus a coil rotates it carries current first in the coil as shown as point 2 of Fig.
in one direction; then this current must 5.13. With further rotation of the coil, as
drop to zero during commutation; and indicated in Fig .5.12 c, it seen that coil
when the coil moves away from the brush A is completely short-circuited, causing
the current in the coil must reverse. the current to reduce to zero at point 3 of
 This process is shown in Fig. 5.11. this Fig. 5.13.
diagram shows the commutator
segments, the coils connected to the
commutator segments, and one of the
brushes.
 Thus a coil rotates it carries current first
in one direction; then this current must
drop to zero during commutation; and
when the coil moves away from the brush
the current in the coil must reverse.  With further rotation of the coil, as
 This process is shown in Fig. 5.11. this indicated in Fig. 5.12 c, it is seen that the
diagram shows the commutator coil A is completely short-circuited,
segments, the coils connected to the causing the current to reduce to zero at
commutator segments, and one of the point 3 of 5.13. as the coil continues past
brushes. the brush, the short circuit is gradually
 The coils to the left of the brush carry removed and currents begins to flow
current to the brush from left to right. through coil A again.
 The coils to the right of the brush also  However, now that the coil is on the other
carries current to the brush, but from side of the brush, the current in the coil
right to left. Let us follow coil A as it will be in the other direction. When the
rotates from left to right and undergoes short is completely removed from the
commutation. coil, the current will again reach to its full
value (Fig. 5.12 d).
EMF OF SELF- INDUCTION current, from zero to a finite value, the
direction of the induced voltage must be
 It is a well known fact that whenever of such as to oppose the applied voltage.
there is current in a conductor, magnetic
field is set up about the conductor. Therefore:
 The greater the current through the
 The net voltage has been reduced and the
conductor, the greater the strength of the
rise in current has also been reduced.
magnetic field about the conductor.
 The same would be true if the current had
 If the current in the conductor changes,
some finite value and were increased to
the magnetic field around the conductor
a larger value.
also changes.
 It should be recalled that a voltage is
 This magnetic field surrounds and links
induced only when there is a change in
the conductor, and whenever there is a
the magnitude of the current.
change in the flux of the magnetic field,
 When the current reaches a steady value
this flux cuts the conductor and induces a
the induced voltage does not exist
voltage in the conductor.
because the flux does not change.
 The direction of this induced voltage is
such that it will oppose any change in the After effect done by EMF of Self Induction
magnitude of the current.
 It is a well known fact that whenever  If the current in a circuit were induced,
there is current in a conductor, magnetic the field about the conductor would
field is set up about the conductor. collapsed to some extent.
 The greater the current through the  This collapsing field cuts the conductor
conductor, the greater the strength of the to produce an induced voltage.
magnetic field about the conductor.  The direction of the induced voltage is to
 If the current in the conductor changes, oppose the change of current,
the magnetic field around the conductor  and since the current is decreasing, the
also changes. induced emf is in the same
 This magnetic field surrounds and links  direction as the applied voltage. This
the conductor, and whenever there is a additional voltage, aiding the
change in the flux of the magnetic field,  applied voltage, tends to slow the
this flux cuts the conductor and induces a decrease in current.
voltage in the conductor.  The coils in the armature of the generator
 The direction of this induced voltage is carry, and when a coil carrying current
such that it will oppose any change in the undergoes commutation, the current in
magnitude of the current. the coil drops to zero rather quickly.
 As the manifestation, assuming a voltage  This reduction in current causes the
is applied to a circuit producing a current magnetic field about the coil tro
flow.  collapse quickly , creating an induced
 The current in the circuit was originally voltage in the coil.
zero and is to be changed to some finite
value. As the current begins to increase
in value, the surrounding flux increases  This emf is in a direction that is the same
in magnitude, thereby cutting the as the applied voltage because the current
conductor and producing an induced emf. is decreasing. How about the applied
 Since the induced voltage is in a voltage in this instance?
direction as to oppose the change in
 It is the voltage that was induced in the  Moved away from the north pole;
coil when the coil cut the flux of the otherwise coils undergoing commutation
main-field pole. would be cutting flux from the north
 If the coil undergoing commutation had pole.
just left the magnetic field of the north  If it is desirable to keep the brush in the
pole, the emf of self – induction would be same position and not move it away from
in the same direction as a coil cutting the the north pole, then it becomes necessary
flux of the north pole. to reduce the flux from the north pole that
 Because of the emf of self- induction is cutting the coil from the commutation.
would be in the same direction as a coil  To do this another pole is placed
cutting the flux of the north pole. between the main-field poles, and the
 Because of this emf of self-induction , the flux from this added pole opposes the
brush short-circuits as coil in which a flux from the north pole to make the net
difference of potential exists, causing a flux to zero.
large circulating current causes sparking  Now that the net flux between the main
at the brushes, undue heating of the poles is zero, there is no need to shift the
brushes and commutator, and brushes because the brushes are located
unnecessary wear of these components. at the points of minimum flux.
Naturally, this effect is undesirable, and  The same reasoning applies to the bottom
the circulating current must be brush of Fig. 5.14.
eliminated.  The bottom brush would have been
shifted toward the north pole, away from
the effects of the south pole.
FUNCTIONS OF THE INTERPOLE  To keep the brush in the same position,
the effects of the south pole must be
 There are two effects resulting from the eliminated. This would be accomplished
current in the armature conductors. by placing a north pole at the point where
 The First Effect was the change in the the flux should be zero.
direction of the magnetic flux, where it
was seen that the brushes were shifted in Explanation of the Second Effect.
the direction of the rotation of the
 Referring to Figure 5.14 above as an
armature.
example, a coil having just left the north
 The Second Effect of the armature
pole and now undergoing commutation
conductors carrying current is the emf of
will have:
self-induction.
 An emf induced in the coil, and the
direction of this voltage will be the same
as the voltage induced when the coil was
under the north pole.
 This emf of self – induction cannot be
eliminated, but if the coil is made to cut
flux so that another voltage is induced in
the coil, and if the new induced voltage is
Explanation of the First Effect. equal and opposite to the emf of self-
induction, the net voltage in the coil will
 Referring to the top brush of Figure 5.14 be zero.
above as to draw an illustration, the brush 
would have to be:
ELABORATION  The strength of the interpole will also be
greater, to produce the required increase
 Since the net voltage induced in the coil
in the flux.
undergoing commutation is now zero, the
brushes will be short-circuiting a coil
with no induced voltage, and no
circulating current will exist between the
coil and the brush.
 This new induced emf must be opposite
to the emf of self-induction, and
therefore the coil just having left the
north pole must cut flux from a south
pole.
 Fortunately, a south pole was required to
eliminate the first effect of the armature
conductors carrying current.
 If the strength of this magnetic south pole
is increased, the necessary voltage will
be induced in the coil and the generator
will perform satisfactorily. Figure 5.14
shows the location of the added south
pole and the added north pole necessary
for the second brush of the generator.
 Added poles are located between the
main-field poles, they are called
Interpoles.
 Figure 5.15 exhibits the manner in which
the interpole flux opposes the armature
flux.

 The interpoles are connected in a similar


manner to the series field of a compound
generator; that is the situation:
 The load current passes through the coils
of the interpoles and produces flux, thus
the greater the current through the
armature conductors, the greater the
distortion of the flux; The greater the emf
of self-induction.
MODULE 6: PARALLEL OPERATION a choice is available, two units are
OF GENERATOR preferable.
 The current a generator can safely
supply is stated on the nameplate of
Parallel Operation of Generators the machine and is known as “ rated”
current.
 One of the electrical considerations  This value of current should not be
in the planning of any building exceeded for fear of possible damage
requiring direct current from local to the generator.
generators is the selection of either  Now of a generator is supplying
one large generator or two smaller power to a load and the demand upon
ones to supply the load. the generator is such that the value of
 In general, while one large generally rated current is to be exceeded, a
be selected. This is because some second generator is required to assist
time in the future, as components the first in supplying the demand.
show signs of wear, maintenance  Just as batteries are connected in
work will be performed on the parallel to supply a load that is too
generator. relatively simple; it is not as simple
 If one large generator is used, this to connect two generators in
work can be done only during odd parallel.
hours when the plant is not on  First some preliminary adjustments
operation. If two generators are used, must be made, and then a set
one generator may have the procedure must be followed. The
necessary repairs made during slack procedure to connect two shunt
periods while the other can furnish generators is different from the
power. procedure to connect cumulative
 In the event of the generator failure it compound generators in parallel;
is still desirable to have tow small
generators rather than one large one.
Failure of the large generator means CONNECTING SHUNT GENERATORS IN
complete plant shut down. But PARALLEL
failure of one small generator means
that the plant still has the use of two
small generators operating in parallel  Figure 6.1 shows two generators and a
is generally the most desirable. load. Let us assume that generator 1 is
These are the factors which may operating and supplying current to the
dictate the selection of large load.
generator.  The polarity of the voltage at the
 These factors may include such items terminals of the generator is indicated in
as initial investment, maintenance, the diagram. Fuses or circuit breakers are
space requirements, and type of plant used to protect the equipment in the event
operation. The requirements of each of an overload or short circuit, and meters
installation will determine the type of are included to determine the generator
plant operation. The requirements of output voltage and generator current.
each installation will determine the Since the second generator is not
type of power plant to be selected. If operating, it is not connected to the load.
 With the polarity of the incoming
machine determined, the next step is the
correct setting of the terminal voltage.
Generator 2 cannot be connected in
parallel with generator 1 without due
 The load on generator 1 now increases to
regard to the value of its terminal
the point where the rated current is
voltage.
exceeded. The second generator must be
 If the terminal voltage of generator 2 is
placed in operation to share the load.
lower than that of generator 1, and then
 The prime mover of the second generator
both machines are connected in parallel,
is started, and the voltage builds up in
generator 1, with the higher terminal
generator 2. Before anything else is done
voltage, will supply power not only to the
after the voltage of generator 2 is built up,
load, but also to the second generator.
the polarity of the incoming generator (2)
 This result requires additional
should be compared with the running
explanation. Figure 6.2a shows the
generator (1). Since both of these
generators are to be connected in parallel, electrical relationship existing in
generator 2 before being connected in
the positive terminals of each generator
parallel with generator 1.
are to be connected and the negative
terminals of each generator are to be  There is no load connected to generator
connected together. 2; thus the terminal voltage Vt2 equals
the generated voltage E2, neglecting the
 If the generators are not properly
connected, as just indicated, the improper small Ia Ra drop in the armature due to
the field current being supplied by the
connections will place both generators in
armature.
series, with only the internal resistance of
each generator limiting the magnitude of  The direction of the armature current
the current. inside the generator is from the - brush
to the + brush.
 In as much as the internal resistance of
the generator is very small, an  he field circuit being connected across
exceedingly large value of current will the terminals of the generator has current
flow which will trip the circuit breaker or flowing through the windings from the +
blow fuses. terminal to the – terminal of the
generator.
 Note: The student working in the
laboratory should check this point very  When the generator 2, with its low value
carefully to avoid unnecessary delay in of terminal voltage, is connected in
the completion of the experiment. parallel with generator 1, conditions are
set up that are indicated in Fig. 6.2b. The
greater voltage from generator 1, Vt1,
will cause current to flow through
generator 2 from the + terminal to the –  If the generated voltage of the incoming
terminal. machine is then increased, the incoming
 The current through the armature of generator be a few volts higher than the
generator 2 is still in the same director, terminal voltage of the incoming
for now, instead of receiving power from generator be a few volts higher than the
the terminals of generator 2 is still in the terminal voltage of the first machine.
same direction.
 The current in the field circuit of
DIVISION OF LOAD-SHUNT
generator 2 is still in the same direction,
GENERATORS
for now, instead of receiving power from
the terminals of generator 2, it is  With two generators connected in
receiving power from the terminals of parallel, adjustments can be made for one
generator 1, and the polarity of the generator to deliver all or any part of the
voltage impressed across the field circuit load.
has not changed.  If the resistance of the field rheostat of a
 Thus, we see that the direction of the field generator is lowered, the resulting
current remains the same. increase in field current will cause the
 The current through the armature of generated voltage to increase.
generator 2 is still in the same direction,  This increase in generated voltage causes
for now, instead of receiving power from the load delivered by the generator to
the terminals of generator 2, it is increase. Naturally, of one generator
receiving power from the terminals of “takes” more load, the other generator “
generator 1, and the polarity of the drops” some load. Hence, by adjusting
voltage impressed across the field circuit the field rheostats of the generators, the
has not changed. Thus we see that the load can be shifted from one generator to
direction of current in the armature of the other or divided in any proportion
generator 2 has reversed while the desired.
direction of the field current remains the  Division of load between generators by
same. rheostat adjustment is rather simple, but
 In the next module, we can refer that normally, when two generators are
when a dynamo takes electrical energy it placed in parallel, adjustments are made
will convert this energy into mechanical so that each generators carries equal
energy, thus making it a motor. load. This adjustments is made at the
 It is now apparent that the voltage of time the generators are placed in parallel
generator w should not be too low before and is usually not readjusted as long as
being connected in parallel with the generators are to remain in parallel.
generator 1.  Will this equal division of load remain as
 it should also be evident that the voltage the total load on both generators is
of generator w should not be too high increased or decreased? To answer the
when compared with the terminal voltage questions let us look at Fig. 6.3, which
of generator 1. shows the external characteristics of the
 In fact, if the two voltages are exactly the generator.
same, the incoming generator will neither
receive nor deliver anyu power but will
remain floating on the line.

ratings are connected in parallel, each
machine will supply a portion of the
load. The portion that each machine will
supply depends upon the characteristics
of the generator. This may be seen from
the characteristics curve of Fig. 6.4. the
characteristic curves for two generators
are shown.

 If both generators are identical, then of


course both have identical characteristics
and the curve applies to both generators.
It should be strongly emphasized that the
terminal voltages of the two generators
connected in parallel are exactly the same
and remain the same as long as the
generators are in parallel. When the
generators are placed in parallel the +
terminals are connected together and –
terminals are connected together, so that  The reference point selected is the
the terminal voltage of one generator full-load rating of the generator. At
must be the same as the terminal voltage the full – load point each generator
of the other. This is true of all generators has the same terminal voltage and
connected in parallel, even though the each generator supplies 100 percent
terminal voltages were not originally the of rated current.
same.  Inasmuch as the two generators two
 With the terminal voltage known, the generators have different current
load delivered by each generator as ratings, 100 percent full of one
determined from the curve is I L2. generator might represent, say, 80 A,
 The total load is now increased both while 100 percent full load of the
generators are identical, then of course second generator might represent
both have so that the generators deliver 60A. But for either generator the
more load. An increase in load causes the terminal voltage is the same when
terminal voltage of the generators to the generator is delivering full load.
decrease.  This point is shown in fig. 6.4, at the
 A reduction in the terminal voltage, say intersection of the two characteristics
to V12 of Fig.6.3, will be obtained when curves. The terminal voltage for this
a current of IL2 is delivered by the point is indicated as Vt FL and the
generator. Since the terminal voltages of current for each machines is 100
both machines are the same and the percent of its full-load rating. When
characteristics of each machine are the the demand upon the generators is
same, each generator will supply a decreased, the terminal voltage will
current of IL2, as indicated by Fig. 6.3, rise, but the terminal voltage of each
the generators will share equally any generator must be the same.
increase or decrease in load.  Should the terminal voltage of the
 When two generators having different generators rise to a value of say, Vt1,
characteristics and different full-load
it can be seen from the characteristics field current increases slightly. All of
curve that generator1 must be these factors tend to increase the
supplying 75 percent of its full load generated voltage of generator 1. An
current while the generator 2 is increase in the generated voltage will
supplying only 60 percent of its full cause the generator to deliver more,
load current. not less, load. Therefore generator1
 These generators will always share will tend to deliver the same amount
the proportionate part of the load. of load instead of reducing the load.
The portion each will share can be  Thus the actions of both generators
determined from Fig. 6.4. combine it maintain the
 Stability of operation is an important proportionate division of load as
factor in the parallel operation of originally set. Any factor which
generators. We have just seen that tends to change the division of loads
shunt generators share the load sets up a reaction to oppose the
proportionately. Should anything change in the division of load.
occur to upset this proportionate  This was accomplished by reducing
division of load, it would be the generated voltage of the machine
desirable for the generators to which was to take on more load and
restore automatically the division by increasing the generated voltage
load. of the machine that was to lose some
 For instance, assume that the speed of the load.
governor of one of the motors  An equilibrium condition is reached,
driving the generators is such that it with one generator taking a small
will not hold the speed constant, and amount of additional load from the
because of this condition the speed of other generator.
generator 2 will increase. The
increase in speed will produce a
larger induced voltage in generator STABILITY OF COMPOUND
2, which will in turn will cause the GENERATORS IN PARALLEL
generator 2 deliver more load.  In direct contrast with shunt generators,
 Of course if generator 2 delivers the parallel operation of overcompound
more of the load, then generator 1 generators present a very unstable
delivers less. This larger load upon condition. Where shunt generators tend
generator2 will cause more current to to oppose any factor upsetting the
flow in the armature of generator 2, division of load, the overcompound
producing a larger Ia Ra drop, a generators tend to aid the upsetting factor
larger drop due to armature reaction. until one generator delivers all the load
An a larger reduction in the field and the second generator takes load.
current, all which tends to oppose the  This phenomenon may be explained with
increase in the induced voltage and the aid of Fig. 6.5. the rising external
thereby not allow the generator to characteristics of two overcompound
deliver more current. generators are indicated in Fig. 6.5.

 In the meantime the load on
generator 1 has decreased with a
corresponding reduction in the Ia R a
drop and armature reaction, and the
 The reduction of the induced voltage of
generator 2 causes generator 2 to drop
some more of the load. This process
continues whereby generator 1 takes
more and more of the load while
generator2 takes less and less of the load.
When generator 2 delivers no current, the
voltage of generator 2 is high compared
with generator 2 delivers no current, the
 The characteristics of the two generators
voltage of generator 2 is high compared
are not the same, and the ratings of the
with generator 2,
two generators are not the same . The
 So that it will cause generator 2 to take
reference point for the diagram is the
power and run as a motor. Thus any
full-load point, where both machines
condition which tends to upset the
deliver rated loads at rated voltage.
proportionate division of load between
 Let us assume that the generators are
cumulative compound generators sets of
connected in parallel and the terminal
events resulting in one generator is a
voltage of the generators is Vt1 from 6.5
function of the induced voltage and not
generator 1 will deliver a load current of
the terminal voltage for any given
I L1 while generator 2 delivers a load
connected load.
current of I L2 now let us assume that for
some reason or the other induced voltage
of generator 1 increases so that generator EQUALIZER CONNECTION
1 tends to take on some additional load.
 Since all or part of the load current must  An equalizer, as can be seen in from Fig.
go through the series field , the increased 6.7, is nothing more than a very low
current will increase the flux produced by resistance conductor connecting together
the series field so that the generated that junction point of the series field and
voltage becomes still larger. the armature of each generator.
 The function of the equalizer is to
 This larger generated voltage causes
eliminate the instability just described in
generator 1 to take still more of the load,
which in turn produces a still reduces the previous section.
voltage. In the meantime the load on  he terminals of each generator joined by
generator 2 has been reduced. the equalizer are equipotential points,
 This reduction in load current reduces that is, they are points having the same
the series-field ampere-turns, which aids potential. Inasmuch as the potential of
the shunt field in producing flux, thereby these two points is the same, the
difference of potential between these
producing the induced voltage.
points zero, and there is no current in the
 Thus any condition which tends to upset
equalizer.
the proportionate division of load
 For this condition to exist, the voltage
between cumulative compound
generators sets of events resulting in one across the armature of each generator
generator is a function of the induced must be the same. As long as the voltage
voltage and not the terminal voltagte for of each generator is the same, each
any given connected load. generator will deliver its proportionate
share of the load. This indicates stable

operation.
 However, when some factor changes this  The equalizer connection also reduces
stable operation, a situation is created the generated voltage of generator 1 so
whereby the induced voltage of one that it will not tend to take con more load.
generator increases because of the  This may be understood by realizing that
additional load and the rising the current through the equalizer
characteristics of the generator. connection comes from the armature of
 Let us assume that the generator 1 of fig. generator 1. this current does not flow
6.7 tends to take more of the load. through the series field of generator 1;
 As the current from generator 1 also therefore it cannot increase the ampere-
increases slightly because of the increase turns, thus increasing the generated
in the field flux produced by the increase voltage.
in the series-field ampere-turns.  Any factor which tends to upset the
 Because of the increase in the induced stable operation of the generators causes
voltages are no longer the same, and the current to flow through the equalizer
difference of potential between the ends connection from the generator; tending to
of the equalizer is no longer zero; a deliver more of the load, but does not
current is therefor established in the flow through the series field of the other
equalizer connection. generator.
 The direct current in the equalizer  The equalizer current therefore reduces
connection is from generator q to the induced voltage of one generator and
generator 2 because of the higher voltage increases the induced voltage of the
across the armature of generator 1. generator, thus maintaining stable
 The current delivered by generator 2 operation between the two generators.
decreases slightly as the current  To have the equalizer connection
delivered by generator 1 increases. maintain stable operation of the
Because of the decrease in current in the generators, it is essential that the
series-field ampere-turns of generator resistance of the equalizer wire be very
decreases, resulting in a somewhat lower small otherwise too large a difference of
induced voltage, and therefore the potential will be required across the
voltage across the armature decreases equalizer before an appreciable amount
slightly. of current will flow.
 This reduction creates a larger difference  The size of wire to use as an equalizer
of potential across the equalizer connection should be the same size as the
connection, which causes an even greater wire used to connect the generators to the
current to flow through the equalizer. load. This large-size wire assures low
 As indicated, the current through the resistance. In addition, all connections
equalizer flows from generator 1 to between generators should be well made
generator 2, and at generator 2 it joins so as to eliminate the possibility of
the current from the armature of contact resistance. Switches should be of
generator 2 and the total current flows good quality and should be inspected
through the series field of generator2. regularly to see that contact pressures are
this additional current, from the correct and contact areas are free of
equalizer, flowing through the series corrosion.
field increases the flux in generator,
which in turn increases the generated
voltage so that the generator 2 will “
pick-up” some of the load it dropped.
cumulative compound generators are
shown in Fig. 6.7. Each generator, by
itself, will operate satisfactorily. But
these generators with the connections
indicated cannot be operated in parallel.
The dotted connections of Fig. 6.7 are
required for parallel operation.
 It can be seen that the low-resistance
series field of one generator is place
directly across the armature of the other
generator.
 The resulting large current and heavy
CONNECTING OVERCOMPOUND load on the prime mover will operate
GENERATORS IN PARALLEL overload devices, removing one or both
units from the line.
 First and foremost either for student and
practitioners must do is to determine
whether the generator is connected as a
cumulatively compound generator or as
a differentially compound generator.
 This may be determined quite readily by
applying a load to the generator.
 If the terminal voltage rises as load is
applied, then the generator is connected
as a differentially compound generator.
To change from a differential connection  Should the student experience the above
to a cumulative connection it is only results in the laboratory, the leads
necessary to reverse the series-field connecting the machines in parallel
connections. should be removed and each generator
 Another method that can be used is to reinvestigated with respect to generator
short temporarily the series-field winding polarity and location of the series field.
after applying load and observing the  It is very possible that the large current in
change in the generator terminal voltage. the series field produced a flux that is
 Shorting the series field causes the greater than the flux of the main field,
generator to operate more as a shunt thereby changing the direction of the
generator than a compound generator. residual flux and causing the generator
 Therefore a drop in the terminal voltage to build up in the opposite direction.
as the result of shorting the series field  The readings of all meters should be
indicates a cumulative compound checked to prevent damage.
connection.  The use of two switches to connect the
 A rise in the terminal voltage indicates generators in parallel is preferable to the
the generator was differentially use of one switch.
connected, the leads to the series field  If one switch were used, the voltage of
should be reversed. the incoming generator would increase to
 The second condition to be investigated a value larger than that of the running
is the electrical position of the series field generator and immediately supply load.
with respect to armature. Two
 This sudden application of load may not
be desirable; hence the use of two
switches so that the load may be
gradually applied.
 The two –pole switch in Fig. 6.8 is closed
first, thus placing both series fields in
parallel.
 The field rheostat of the incoming
machine is adjusted so that both
voltmeters read alike.
 The single-pole switch is then closed.
 The load on the generator can be
increased by decreasing the resistance of
the field rheostat.
MODULE 7: MOTORS  THE LENGTH OF THE
CONDUCTOR IN THE MAGNETIC
FIELD,
 Supposed a conductor is placed in  THE MAGNITUDE OF THE
magnetic field and current is allowed to CURRENT IN THE CONDUCTOR.
flow through the conductor, the
conductor will tend to move.
 A force eventually is exerted on the
conductor because the latter is carrying
the current and it is located in a
magnetic field.
1. A magnetic field must exist, then a conductor
must be located in the magnetic field, and finally
current must flow in the conductor.
Conditions Arises:
Force (conductor)=0; if magnetic field =0.
magnitude (B) = > 0 (greater than than 0 value) ;
if greater (B ) value the greater the Force exerted
on the conductor …. In variable proportion.
2. The length of the conductor determines the
magnitude of the force on the conductor:

 The smaller the conductor, the smaller


the force;
 The longer the conductor, the greater the
force exerted on the conductor.
3. In producing a force it requires the magnitude
of the current of the conductor.

 With no current in the conductor, the


force produced would be zero.
 The greater the current through the
conductor, the greater the force exerted
on the conductor.

DIRECTION OF FORCE
SUMMARY:
THE FORCE EXERTED ON A CONDUCTOR
DEPENDS UPON:  As per illustration Fig.7.2 it shows that a
conductor is carrying current while in
 THE FLUX DENSITY OF THE magnetic field.
MAGNETIC FIELD,  The arrow in the diagram indicates
direction of force on the conductor.
 The direction of the flux from North  Referring 7.3a, the flux due to the poles
Pole to the south pole is from left to right is from north to south. The flux due to
(L - R). conductor carrying current is clockwise
direction.
 The resulting magnetic field will cause
the concentration of flux lines on top of
the conductor and reduction of flux lines
below the conductor as indicated in Fig.
7.3b.
 If it is assumed that these flux lines act as
the elastic bands, then it will be apparent
that the conductor will move in a
downward direction. Either method is
 The direction of current flow is away equally correct for determining the
from the observer, or into the page.The direction force on a conductor.
direction of force on the conductor is
downward.
 Mentioned three directions is at right
angle to each other, and the direction of
force can be found if the other two
directions are known.
 The left hand rule is used in this instance.
 (Recall that the right hand rule was used
when finding current flow in a
generator). The thumb, index finger, and
middle finger are held at right angles to TORQUE
each other.
 As per figure 7.4 shown that the
 The index finger is used to indicate the
conductor could rotate in the magnetic
direction of flux from north pole to the
field unless the current through the
south pole.
conductor would exert a force.
 The middle finger points in the direction
 The conductor would tend to rotate in
of the current, and the thumb points in the
clockwise direction.
direction of force on the conductor.
 This tendency to produce a rotation is
 Should the hand rule for a motor or a
known as TORQUE.
generator be forgotten, it can be recalled
by the following a complete unit that is
used to generate power is known as a
motor-generator set (abbreviated M-G
set) if the motor-generator is associated
with left and right, this will indicate
which hand rule to use: motor-generator,
left-right.
 Another method commonly used to
determine the direction of force is by
analysis of the flux distribution of the
magnetic field.
 The magnitude of torque can be
determined by the product of the force
multiplied by the perpendicular distance
from the force to the center of the
rotation.

 The same current flows through the


conductor Left-Hand Rule, it can be seen
that the conductor under the south pole
will have a force exerted on downward
Or (in SI units) direction.
 `Where: T= torque, newton-meters (N.m)  The same current flows through the
 F= force, newtons (N) conductor under the north pole, but in the
opposite direction,
 r= distance measured perpendicularly
from direction of F to center of rotation,  Therefore, producing a force in an
meters (m). upward direction, both of these forces
will aid each other in producing a torque
and therefore rotation in the same
direction.
 Thus, a conductor forming a part of a
 The position of the coil as described as
motor will produce rotation when current
again in Position 1 in Fig. 7.6.
flows through a conductor and the field is
 The force exerted on the coil is such that
energized.
the coil will rotate from position 1 to
position 2 and then to position 3.
 The torque produced by a single
conductor is normally very small. Since
practical conditions limit the flux density
and the current through the conductor,
the remaining alternative is to increase
the length of wire in the magnetic field.

 As shown in Fig. 7.5, it shows a coil of


one turn.
 The current direction is indicated on the
conductors by an arrow.
 Using the left - hand rule, it can be seen  Note: that the force on the conductor has
that the conductor under the south pole not changed even though the coil has
will have a force exerted in a downward rotated.
direction.  This so because the direction of the flux
has not changed nor has the direction of
current in the conductor.
 Torque has been defined as the product
of the force multiplied by a distance
measured perpendicularly from the axis torque will move the conductor in the
of the force to the center of rotation is same direction at all times.
zero;  The commutator is the device that will
 hence the torque produced is zero. change the direction at the desired point.
 Should the inertia of the moving coil  During the study of the generator the
allow the rotation to position 4, then the action of the commutator was discussed.
torque will again increase in value.  The function of the commutator and
 This time the direction of torque will be brushes was to act as a switch between
counterclockwise, forcing the coil back the coils of the machine and the external
to position 3. and of course forcing it to circuit.
stay at position 3.  For the generator case, the current
 For a motor to produce rotation the reversals in the coils were connected
direction of torque produced by the coil through the commutator and the output
must be changed after if passes position was always in the same direction.
3.  The function of the commutator and
 Should the direction of force exerted on brushes was to act as a switch between
the conductor change after position 3, the coils of the machine and the external
 Then the torque produced with the coil in circuit.
position 4 would be in counterclockwise  For the generator case, the current
direction and continuous rotation would reversals in the coils were connected
be obtained. through the commutator and the output
 Figure 7.7 shows the current direction was always in the same direction.
and the torque produced as the coil  The commutator switches the current to
rotates from position 1 to position 4. the coil to provide the alternating effect
 necessary to produce the desired torque
 Note that the current in the conductor direction.
flows away from the page as long as the  In a generator the switching action
conductor has not reached position 3, occurred when the conductor was a point
of minimum flux; that is the
commutation would occur between the
north and south poles.
 In the motor the action of the commutator
is exactly the same. Unidirectional
current supplied to the motor passes
through the commutator and brushes
before reaching the coils.

 Thereby producing torque in clockwise RE-EMPHASIZING


direction. Past position 3 note the  It was stated the torque is a function of
direction of current. the flux, length of the conductor, and
 Now it is toward of the page, producing current through the conductor.
torque in a clock wise direction.  For any one specific machine the flux and
 Therefore if the direction of current in the current can vary, but all other factors
the conductor can be made to change as are fixed and remain constant.
the conductor passes position 3, then the
 Referring Fig. 7.7, it is observed that the
switching action for a motor should occur
at position 3,
 Which is between the north and south
poles and corresponds to the point of
minimum flux.

COUNTER -EMF

 The name plate of a motor contains a


great deal of information, including the
voltage rating of the motor and the
current drawn by the motor under full
load conditions.
 Values for a typical 5 hp (horsepower)
motor would be 240V and full- load
current of 20.4 A.
 Additional information from the
manufacturer indicates that the total
resistance of the armature circuit is 0.97
Ω.
 Thus, as per ohm’s law, the current in the
motor should be 240 V divided by 0.97,
or 248 A.
 This current is approximately ten times
the full-load current of the motor, which
is 20.4 A.
 Apparently, there must be some factor
other than the ohmic resistance of the
armature that limits the current to the low
value. This factor is the counter-emf
produced by the motor armature.
 A closer look of these pictures should
raise some questions. Say for example,
this motor is designed for operation from
a 240 V supply and the resistance in the
circuit is only 0.97Ω.
 Recalling the discussion from the
generator principles, it was stated that a
voltage would be induced in a conductor
if the conductor cut lines of flux.
 The movement of a conductor through  Hence the voltage induced is opposite to
the magnetic field could be performed the applied voltage and therefore is
manually, or by some external prime referred to as the counter-emf.
mover, or by conductor itself.  The net voltage producing current flow
 When current flows through a through the armature is the difference
conductor, a force is exerted on the between the applied voltage and the
conductor that causes the conductor to counter-emf. The armature current may
move in the magnetic field. be stated as
 Movement of the conductor in the
magnetic field produces generator action,
and a voltage is induced in the conductor
in such direction as to oppose the applied
voltage.
 Fig. 7.8 demonstrates this dual action on
the conductor. Fig. 7.8a, a conductor is
located in magnetic field and current
flows through the conductor will move in
a downward direction.
 The same conductor is now moving in
the same magnetic field as shown in Fig.  In a generator the function of the machine
7.8b. Since this is generator action, the is to create and produce an emf.
right hand rule is used to determine the  The developed emf is therefore greater
direction of current, which can be seen and is equal to the sum of the terminal
from the diagram. voltage plus the armature drop.
 It is opposite to the current in Fig. 7.8a.  The function of the motor is to convert
Inasmuch as the two currents are in electrical energy into mechanical energy.
opposite directions, the two voltages are  In this case a voltage is applied to the
in opposition. motor terminals an this terminal voltage
is equal to the sum of the counter- emf
plus the armature volt drop.
 Worthy to note, that under normal
circumstances the counter –emf
developed by the motor can never be
greater than the terminal voltage.
 This is understandable when it is realized
that the applied voltage cause the
armature to rotate, which in turn
produces the counter-emf.
 If the counter-emf were equal to the
applied voltage, the armature current
would be zero, the armature would cease
to rotate, and the counter-emf would be
reduced to zero.
 Therefore the counter –emf can never be
equal the applied voltage without
reducing its own value.

ELECTRICAL POWER MECHANICAL


POWER

 Not all the electrical power supplied to a


motor is converted into mechanical
power.
 Some of the power is dissipated in the
field windings, and some in the armature
circuit. The remainder is available for
conversion into mechanical power. The
power flow diagram of Fig. 7.9 shows the
power distribution.
 The total power supplied to the motor is
equal to the product of the voltage
impressed across the motor, Vt. And the
current to the motor, IL, a portion of this
power is consumed by the shunt field, Vt,
and the current in the shunt field, I f, the
difference between the power delivered
to the motor and the power consumed in
the shunt field is the power delivered to
the armature.

 The electrical power converted into


mechanical power is equal to the product
of the counter-emf and the armature
current.
 As a reminder that this mechanical power  With a constant voltage applied to the
is not available outside of the motor, only motor, the speed of a motor depends
inside. upon the flux.
 This mechanical power must be used to  This relationship may be seen from the
overcome mechanical losses inside the equation.
machine, including friction of the
bearings and forcing of air through the ARMATURE REACTION
machine for cooling purposes.  The effect of the magnetic field produced
 The remainder of the power is available by the current in the armature was
to do work. previously discussed by previous module
on generators.
 The armature flux distorted the main-
EXAMPLE 7.5 field flux, resulting in shift of the
magnetic neutral.
 The following information was obtained
 The current in the conductor is in
from the name plate of shunt motor: 5
clockwise direction of rotation
hp, 240V d-c; full-load current, 20.4;
 Fig. 7.10 a, The current in the conductor
field resistance, 202 Ω. If the armature
is in clockwise direction of rotation, also
resistance is 0.71 Ω, determine
indicated is the direction of flux due to
1. power delivered to motor;
the main field, φ (field), the flux due to
2. power dissipated in shunt field,
the current in the armature, φ(armature),
3. power dissipated in armature circuit,
and the resultant flux, φ (Resultant).
4. electrical power converted into
mechanical power.  Fig, 7.10 b, but for a motor , the current
direction in the armature must be
indicated if the motor is to run in
clockwise direction.
 It is opposite current direction as that
shown for generator.

SPEED OF MOTOR

SHUNT MOTOR
 The shunt motor is physically the same as torque to meet the new load
shunt generator. The shunt –field coils requirements.
consists of many turns of the fine wire  It is convenient at times to refer to the
and is connected in series with a field horsepower developed by a motor rather
rheostat. The shunt-field circuit is than the torque developed. Horse power
connected across the line in parallel with is the rate of doing the work, or is equal
the armature. to the force multiplied by the distance
 The shunt field is connected across the divided by the time to traverse the
line, the flux in the machine will remain distance; therefore
essentially constant. The torque  hp ∞ [ F x r x 2 π n ] / t
developed by the motor would therefore
Where
be directly dependent upon the armature
current as indicated by the torque  F = force exerted by all conductors, lb
equation, T= Kφ Ia. Increasing the  R2πn = peripheral distance traversed, ft
armature currents would increase the  r = radius of armature, ft.
torque. Decreasing the armature current  n = number of revolutions
would decrease the torque (Fig. 7.11).
 t = time for armature to rotate n times
However, the product of F and r is equal to the
torque, and if n/ t equals revolutions per minute,
then:

 hp ∞ 2 π TS
Where

 T= F x r
 S = n/ t

 To eliminate the proportional sign, 2π TS


must be divided by 33, 000, which
 The armature current depends directly converts foot-pounds per minute to
upon the load connected to the motor. horsepower.
When a load is applied to the motor it will  hp = [ 2 π TS ] / 33,000
tend to slow down. This slight reduction  hp = [ TS ] / 5252
in speed reduces the counter-emf in
accordance with the formula E= K φ S.  A word of caution is now necessary, to
The reduction in E will produce a greater avoid confusion, when introducing the SI
armature current, as can be seen from the unit for the power output of a motor. As
equation noted, the input power to a motor, in
 I a = [ Vt –E ] / Ra English units, the input power is
 The increase in armature current results expressed in watts, but the output power
in an increase in torque to take care of the is also express in watts. Care should be
added load. taken to distinguish between input and
 Thus, it can be seen that a load applied output power.
to the motor results in an increase in
 The formula for output power of a motor increases. The torque will increase in
is : each machine because of the increase in
 P out = T out x rad / s armature current.
 = T out x 2 π r / s  However, the increase in the compound
motor is greater that in the shunt because
Where the total flux increases and does not
 T =output torque, newton – meters remain constant as it does in the shunt
 r = number of revolutions through which motor.
the armature rotates in s seconds.

COMPOUND MOTOR

 The construction of the compound motor


is identical to that of the compound
generator. The current in the armature
must also pass through the series-field
winding.
 The series-field winding may be
connected cumulatively where the flux  The speed of the compound motor is
may also be connected differentially so also affected by the increase in flux.
the series – field flux will oppose the Compare the two speed equations:
shunt –field flux.
 The torque developed by a cumulative Shunt Motor S = ( Vt – I a R a ) / ( K φf )
compound motor will be larger than the
torque developed by a shunt motor if the
flux produced by the shunt field of each  S = E / K φf
machine is the same and the armature
current is the same.
Compound Motor S= ( Vt – I aR a – IsR s )/
[K ( φ f + φ s )
 Since the torque is proportional to the
flux and the armature current, the flux in
the compound motor is greater than in the  S= E / Kφ f
shunt because of the additional flux
produced by the series winding. Compare
the following equations:  It is evident that the speed of the
compound motor is less than that of
Shunt motor the shunt motor, all other factors
T = K2 φf I a being equal.
 Figure 7.13 compares the speeds of
Cumulative compound motor
the shunt motor, and the cumulative
compound motor.
T = K2 (φf + φ s ) I a

 Graphically, the effect of the additional


flux is shown in Fig. 7.12 as the load on
the motor increases, the armature current
SERIES MOTOR

 In a series motor the flux depends upon


the current in the series field, which is the
same current that flows through the
armature. At light loads the armature
current is small; therefore the flux and
torque are small.
 An increase in the load increases both the
armature current and that flux, producing
a much greater increase in the torque.
 The differentially compound motor has The torque equation is
characteristics opposite to those of the
cumulative compound motor as  T= KφIa
compared with the shunt motor.
 The decrease in the flux produces a
reduction in the torque.  Since the current in the series field is the
armature current, the equation may be
written substituting I a for φ .

 T = K’ I²a

 From this equation it can be seen that, as


long as the magnetic material is not
saturated, the torque is proportional to
 Instead of a reduction in the speed of the the square of the armature current.
motor, the speed of the differential  Hence, if the armature current is doubled,
compound motor will be higher than that the torque will increase four times.
of the shunt motor.  Figure 7.15 shows the torque
 In fact, the speed may rise as load is characteristics of the various types of
applied to the motor. Figure 7.14 above motors.
graphically depicted the torque and speed
characteristics of the motors.
 Care should be exercised when starting a
differentially compound motor, the large
inrush current in the series field during
the starting period may produce flux
greater than that produced by the shunt
field. Is will cause the motor to start up in
the wrong direction.
 It is best to short the series field when
starting to prevent such events. At
present there is no commercial use for
this type of motor.
The basic speed equation  Figure 7.17 shows the torque and speed
characteristics of the motors having a
 S = ( Vt - Ia Ra - Ia Rs ) / Kφ
common value at the full-load point.

May be rewritten substituting Ia for φ .

 S = ( Vt – I a R a – I a Rs ) / K Ia

 With no load connection to the motor,


the value of Ia (armature current) is
very small. The numerator of the speed
equation is large, while the denominator
is very small, indicating that the speed of
the motor will be extremely large.
 In fact, the speed of the motor may reach
such a value as to cause the centrifugal
force to destroy the motor.
SPEED REGULATION
 It is for this reason that the series motor
are never used unless they are directly  The speed-change characteristics of
connected to the load, as in trains and various motors may be compared by
cranes. means of the speed regulation.
 As voltage regulation of a generator is an
indication of the per cent change in
MOTORS OF EQUAL RATING voltage from full load to no load, so does
speed regulation of a motor indicate the
variation in speed from full load to no
load, taken as a per cent of the full-load
speed.
 Thus, a motor whose speed changes
very little when the load is removed has
per cent regulation. The series motor has
a high per cent regulation because the
change in speed from full load to no load
is large.
 The formula for speed regulation is
Percent Speed Regulation = ( S NL - S
FL ) / S FL x 100

 In the preceding discussion, it was


convenient to compare the characteristics
of motors beginning with no-load
conditions.
 When comparing motors of equal rating,
the comparison should begin at a point
that is common to all, the full-load point.
MODULE 9: TRANSFORMERS

You might also like