PUKKA
New Capital City
Technical Specifications
INFRASTRUCTURE
IFC - Rev 01
January 2023
Prepared By:
rmc__raafi
re260500
260513,
260519
260526
260536
261216
261300
262213
262300
262413,
262416
262500
262726
262816
263213
263623
265100
265600
281300
283100
337119
rc
PUKKA.- New Capital City
INDEX
DIVISION 26 - ELECTRICAL
BASIC ELECTRICAL MATERIALS AND METHODS,
MEDIUM-VOLTAGE CABLES
LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
GROUNDING AND BONDING
CABLE TRAYS,
MEDIUM-VOLTAGE TRANSFORMERS
MEDIUM-VOLTAGE SWITCHGEAR
PREFABRICATED TRANSFORMER SUBSTATION
DISTRIBUTION PILLARS AND FEEDING BOXES,
SWITCHBOARDS
PANELBOARDS
LOW VOLTAGE ENCLOSED BUS ASSEMBLIES
WIRING DEVICES
ENCLOSED SWITCHES AND CIRCUIT BREAKERS
DIESEL-ENGINE-DRIVEN GENERATOR SETS
AUTOMATIC TRANSFER SWITCHES
INTERIOR LIGHTING
EXTERIOR LIGHTING
DIVISION 28
IP ACCESS CONTROL SYSTEM
FIRE DETECTION AND ALARM
DIVISION 33 - UTILITIES
UNDERGROUND DUCTS AND UTILITY STRUCTURES
END OF INDEX
Page 1 of 1rmc
ION 260500 - BASIC ELECTRICAL MATERIALS AND METHODS.
PART 1 - GENERAL
1
B
PUKKA.- New Capital City
IFC-Rev.o1 Page 1 of 17 | January 2023
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including Conditions of Contract, apply to
this Section,
SUMMARY,
This Section includes the following:
1. General provisions applicable to Division 26 work and other Sections of the
Specification that refer to this Section.
Supporting devices for electrical components,
Electrical identification,
Covers, brackets and supports.
Electricity-metering components,
Conerete equipment bases.
Electrical demolition,
Cutting and patching for electrical construction.
Touchup painting,
Electrical Work, unless otherwise specified, includes the supply, installation, testing and
commissioning of the complete electrical systems, equipment and materials shown on the
Drawings and/or described in the Bills of Quantities and Specification together with all
associated ancillary work, support work and builder's work in connection.
REGULATIONS AND STANDARDS
Regulations: Carry out electrical work in accordance with the current issue of the local codes
of practice, local power authority regulations and [Requirements for Electrical Installations ~
IEE Wiring Regulations (BS 7671) as published by the Institution of Electrical
Engineers}where not in contradiction with the local codes of practice and regulations, herein
referred to collectively as the Regulations’
Conflict: Should an instance occur in this Specification or on the Drawings in which material
or construction methods called for is less than minimum requirement of the Regulations,
immediately inform the Engineer in writing. Consequent to Engineer's approval, supply the
‘materials and perform the work as though called for to minimum code standards,
Standards: Unless otherwise specified, equipment and materials are to be manufactu
installed in compliance with the relevant recommendations of tht [FUR CORSTIRUSTION]
and approved standards: DORSTRUSTION
rms \
SECTION 261500rmc
IEC: The International Electro-technical Commission
ISO: The Intemational Standardization Organization
CCITT: The International Telephone and Telegraph Consultative Committee
CCIR: The International Radio Consultative Committee
CISPR: The International Special Committee on Radio Interference
‘ETA: Intemational Electrical Testing Association (tests for site acceptance),
IEE: Institution of Electrical Engincers,
8. BS: British Standards,
D. Local standards, where enforced and relevant, are to have precedence over the Standards.
FE, The contractor is committed to comply with all requirements of SCEDC/Global during
execution of work.
14 POWER SUPPLY
‘A. The Local Power Authority will provide incoming power supply and connection at [22KV]
to the location shown on the Drawings.
B, Power Supply: Liaise with the Local Power Authority to confirm:
Characteristics of supply and system earthing.
Location of incoming supply shown on the Drawings.
Space requirements and associated builder's work for the Authority's installations.
Make necessary arrangements at the earliest opportunity to ensure connection as and
when required, and inform the Engineer in the event of any foreseen delay.
KWH-metering: Liaise with the Local Power Authority and provide necessary
instrumentation, enclosures and accessories required by them to effect a complete kWH-
metering installation.
D. Nominal characteristics of power supply and distribution are as follows:
1. Low voltage: 380V, three phase, 4 wire, solidly earthed nutral
2. Frequency: SOHz.
E, Distribution systems ate to be supplied or derived from the voltage system previously
described, as shown on the Drawings, or as otherwise specified
1.5 EQUIPMENT
A. Equipment Spaces and Rooms: Verify that dimensions, structure, ventilating and cooling
arrangements and other provisions in equipment spaces and rooms are suitable for
installation, operation and maintenance of proposed equipment. Note any discrepancies on
the shop and construction drawings
B. Equipment is to be designed for the system voltage and frequency previously described,
unless otherwise specified. Special provisions are to be made IPEE
power supply fequency and voltage variations and or equipmel ete She Oc TON
voltages/frequencies or by direct current sources.
rme