Professional Documents
Culture Documents
Abstract—The conventional virtual synchronous generator under weak grid conditions [3]–[6]. Therefore, it is desirable
(VSG) is typically designed to meet certain operational and con- to eliminate the need for PLLs in these converter interfaces,
trol requirements in the islanded mode. However, once the VSG leading to increasing research interests both in academia and
is switched to grid-connected mode (GCM), the robust operation
cannot be guaranteed under different grid conditions. It can lead industry for the emerging PLL-less grid-forming technology
to poor dynamic performance, especially in strong grids, such as [7].
significant oscillation, long settling time, and large overshoot. To Various kinds of grid-forming control strategies have been
improve the VSG performance in the GCM, this article first developed in the literature, e.g., droop control, power syn-
analyzes in depth the inherent coupling between the active and chronization control, virtual synchronous generator (VSG),
reactive power and its dependence on grid conditions, such as the
short circuit ratio and the grid impedance ratio. Subsequently, synchronverter, matching control, and virtual oscillator control
an adaptive VSG (AVSG) control strategy based on online grid [8]. Among them, the VSG is regarded a promising key
impedance estimation is proposed to ensure robust operation of technology for achieving a 100% inverter-interfaced renew-
the VSG considering both strong and weak grid conditions. This able grid, as it enables these power electronic converters to
technique allows the operator to specify the desired settling time mimic both the steady-state and transient-state characteristics
of the output power and damping ratio. To estimate the grid
impedance in real time without additional hardware and reduce of conventional synchronous generators. The VSG not only
the associated impacts on power quality, an online event-based accurately tracks the power command, but also provides inertia
grid impedance estimation algorithm is embedded in the control and damping to the utility grid [9].
loop of the AVSG. The simulation and experimental results The VSG can operate in the islanded mode (IM) and in the
indicate that, compared with the conventional fixed-parameters- grid-connected mode (GCM). On the one hand, the main task
based controller design method, the AVSG exhibits desired
performance such as no oscillation, specified time duration for of the VSG in the IM is to form the microgrid voltage and
the settling time, and minimal overshoot regardless of the grid frequency. On the other hand, the main task of the VSG in the
conditions. GCM is to inject the active power specified by its reference
Index Terms—Adaptive control, online grid impedance estima- value, while the terminal voltage and frequency are regulated
tion, stability, strong grid, VSG, weak grid. by the utility grid [10]. Conventional grid-following control
strategies cannot provide adequate inertia support for the grid
under these circumstances, which may impose the risk of
I. I NTRODUCTION instability for renewable-energy-rich power systems [11]. The
voltage, frequency, and inertia support in these grid-connected
I N recent years, the deployment of renewable energy farms
has accelerated worldwide due to their declining costs and
environmental issues associated with fossil fuels [1]. Unlike
regions using the grid-forming concept is thus in great need.
Although many research studies have been conducted to
conventional synchronous generator-interfaced hydraulic and improve the VSG control performance, there are still some
thermal power plants, these renewable energy resources are challenges under investigation [9]. Among them, the coupling
mainly connected to the utility grid via highly controllable, between the active and reactive power output that can lead
flexible, and efficient power electronic converters [2]. Despite to degradation of the stability and dynamic performance of
these remarkable advantages, these converters currently in the power system has drawn increasing research attention
service rely mainly on phase-locked loops (PLLs) for grid [12]. Furthermore, severe power coupling results in transient
synchronization to inject a specified power or current com- oscillations and even unstable operation [13]. The decoupling
mand that may induce control interaction-related instability between the active and reactive power is only satisfied in
phenomena or limit the maximum power transfer capability high- or medium-voltage grids where the grid impedance ratio
Xg /Rg is large enough such that the line impedance could be
This work has been supported by the Monash Grid Innovation Hub and regarded as mainly inductive [14], [15]. However, the power
the Australian Renewable Energy Agency (ARENA) under the Advancing
Renewable Program (Grant No.: 2020/ARP007) (Corresponding author: coupling exists in a low-voltage grid due to the small Xg /Rg
Nabil Mohammed). ratio of line impedance, i.e., any change of the active power
The authors are with the Department of Electrical and Computer output will affect the reactive power output and vice versa
Systems Engineering, Monash University, 3800 Victoria, Australia (e-
mail: nabil.mohammed@ieee.org; mohammad.ravanji@monash.edu; wei- [11].
hua.zhou@monash.edu; behrooz.bahrani@monash.edu). Considering the above-mentioned issues related to the cou-
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY 2
pling between the active and reactive power output, such as the estimate the grid impedance [26], [27]. Different estimation
step responses deteriorate (e.g., overshoot, settling time, and algorithms are used for grid impedance estimation using grid-
oscillations) under strong grid conditions, it is important to an- connected inverters, including extended Kalman filter [28],
alyze the negative impacts of the grid impedance on the power recursive least squares [29], system identification [30], power
coupling of grid-forming inverters. However, most of the variations [26], single-frequency injection techniques [31],
control strategies in the literature that address power coupling PRBS [32], and pulse injection [25], [33]. However, the
issues focus on droop-based grid-forming inverters. These literature has not yet proposed the implementation of such
techniques include virtual inductance [16], virtual impedance estimation algorithms into the control loop of the VSG-based
[17], adaptive virtual impedance [18], adaptive droop control inverters, which brings new considerations such as the trade-
[19], and various improved droop control strategies [20]. Few offs between the accuracy, disturbance, and estimation speed.
studies focus on addressing the power coupling issues in This paper initially presents a comprehensive study to reveal
VSG-based grid-forming inverters, especially in the GCM. In the negative impacts of different grid impedance conditions,
[21], the power equations considering a resistive-inductive grid i.e., different SCRs, different Xg /Rg ratios, and different grid
impedance are linearized at a specific operating point. Then, impedance amplitudes, on the step response (oscillation, high
a power decoupling method based on compensating for the overshoot, and long settling time) of VSG-based inverters.
coupling components of the power equations is presented. In Then, an adaptive VSG (AVSG) control strategy is proposed
[13], to assess the power coupling characteristics, a unified to eliminate these negative impacts of the grid impedance on
dynamic power coupling model is presented. In [11], the the power coupling between the active and reactive power
limitation of using only virtual inductance to decouple the loops regardless of the grid conditions. The advantages of the
power flow is investigated. Then, a q-axis voltage-drop-based proposed control are summarized as follows:
power decoupling control is proposed. Furthermore, the effects 1) It relies on the online estimation of the grid equivalent
of adopting the virtual inductance on power decoupling are model, i.e., grid resistance and inductance, in order to
assessed in detail in [22]. In [10], a generalized control is adaptively tune the VSG parameters. Hence, it can stably
presented to meet the operational requirements in both the operate in both weak and strong grids.
GCM and IM. Therefore, in the GCM, the oscillations are sup- 2) To avoid practical complications caused by using net-
pressed, and the settling time of the output power is reduced. work analyzers for impedance estimation purposes, an
In [23], a compensated VSG control scheme is proposed to online event-based active grid impedance estimation
accurately follow the power reference commands in the GCM. (GIE) technique is embedded into the control of the
Compared with the conventional VSG, the compensated VSG AVSG. It only utilizes the available PCC voltage and
results in lower overshoots and shorter settling times in step current measurements to accurately estimate the grid
responses in both strong and weak grids. impedance components.
Despite the above efforts to eliminate the power decoupling 3) It ensures complete decoupling and control of the active
issue in VSG-based grid-forming inverters, several shortcom- and reactive powers with the same desired dynamic
ings remain to be resolved. First, the control design proposed performance, such as no oscillation, specified settling
based on linearization and decoupling, e.g., in [21], is valid time, and minimal overshoot.
and accurate only for a specific linearized operating point.
The rest of this paper is organized as follows. Section II
Second, the proposed control designs, e.g., in [24], assume
provides a comprehensive review of the conventional VSG,
that the grid impedance is purely inductive, which is not the
including the control structure, its performance in the IM and
case in weak and low-voltage grids. In [23], the information of
in the GCM, and a summary of the remaining challenges
the grid inductance is required for tuning the proposed VSG,
related to grid parameters (e.g., SCR and X/R ratios) that hin-
and it is assumed to be known. Again, the grid impedance
der the accurate control of VSG-based inverters in the GCM.
is assumed to be inductive. Hence, the pre-calculated values
Section III describes the proposed AVSG. Section IV presents
for the VSG parameters are neither based on the real value of
the simulation and experimental results. Finally, Section V
the grid inductance nor take into account the grid resistance
draws conclusions.
value. Third, no comprehensive study reveals the performance
of the VSG in the GCM considering operating scenarios with
different values of the short circuit ratio (SCR), different grid II. C ONTROL OF THE C ONVENTIONAL VSG AND ITS
impedance ratios Xg /Rg , and grid impedance variations with C HALLENGES
the same Xg /Rg ratio.
Finally, as reviewed above, the equivalent grid impedance A. Control Structure of the Conventional VSG
seen at the point of common coupling (PCC) affects the op- Fig. 1 shows the topology and control diagram of a con-
eration of the VSG. Therefore, assuming that the information ventional VSG-based grid-forming inverter. The inverter is
about the impedance of the grid impedance is known during interfaced to the grid at the PCC via an LC filter (with
the control design stage is not an accurate assumption since an inductance Lf , an equivalent series resistance Rf , and a
the grid impedance is a parameter varying over time [25]. capacitance Cf ) to the grid or load (not shown in the figure).
One possible and cost-effective solution is to enable the VSG The utility grid is modelled using the Thevenin equivalent
to estimate the grid impedance in real-time. Previous studies circuit that consists of the grid voltage source (Vg ) and the
investigate this feature by enabling grid-following inverters to grid impedance (Zg = Rg + sLg ).
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY 3
vdq, pcc
idq, pcc
idq, pcc vdq, pcc idq, inv is the frequency droop coefficient considering that the VSG is
abc
dq t P Control Dp capable of supplying and absorbing active power, i.e., the VSG
Power calculation
vdc t 1 1 1 Ppcc interfaces large-scale battery storage systems where batteries
Reference generator
Inner idq, inv s s J 0 Pref can be charged and discharged [36]. fmax and fmin are the
voltage & ref maximum and minimum frequency deviations, respectively,
vdq, pcc
current 1
v E ref K iq allowed in the IM. In addition, Pmax is the maximum active
controllers dq, ref s Qpcc power that can be supplied by the VSG.
K pq Qref Based on (2) and (3), J can be calculated as
Q Control
Dp
Fig. 1: Control structure of a conventional VSG-based grid-forming inverter. J = TV SG . (6)
ω0
For the conventional VSG shown in Fig. 1 and by considering
Conventionally, fixed values are assigned to the virtual the circuit and VSG parameters listed in Table I, Dp is
damping Dp and the virtual inertia J at the design stage by calculated as Dp = 1.273×106 W/Hz based on (4) and (5).
considering the operational requirements in the IM. However, Then, for an initial RoCoF as 1 Hz/s (i.e., TV SG = 1 s),
6
in the GCM, although the designed fixed values for the J can be calculated as J = 1 × 1.273×10314.16 = 4052 kg·m2
VSG parameters can still perform reasonably well in weak based on (6).
grids, they could lead to a poor transient response with high Fig. 2 presents the performance of the VSG in the IM. In
overshoot and long-time oscillations in strong grids that have this figure, to verify the desired initial RoCoF requirement
relatively small grid impedances [8]. Therefore, the perfor- in the IM, the VSG system shown in Fig. 1 considering the
mance of the VSGs is highly dependent on the grid conditions, parameters listed in Table I is simulated in MATLAB/Simulink
as will be shown in subsection II-C. where the VSG is connected to a load instead of the grid.
Fig. 2 shows the obtained response to a step-change of the
load active power from 0 to 4 MW at t =0 s, indicating that
B. Control of the Conventional VSG in the IM the initial RoCoF at the PCC is equal to ∆ω π
∆t = 1 = π rad/s
2
In the IM, the VSG is expected to provide frequency support or 0.5 Hz/s that is the same as the designed value shown in
when the load changes. Therefore, the inertia and damping (3). Note that the designed RoCoF is equal to 1 Hz/s for the
parameters of the VSG are designed to meet the rate of change change of the active power from -4 MW to 4 MW.
of frequency (RoCoF) requirements. In Fig. 1, by neglecting It is worth mentioning that the open-loop transfer function
the line losses, the small-signal transfer function from the load of the VSG Gp (s) is given in (7)
variation ∆Pload to the angular frequency variation ∆ω can δ 1
be derived as Gp (s) = = , (7)
∆Pload s(Jω0 s + Dp )
∆ω 1
=− , (1) where δ is the output voltage angle of the VSG operating in
∆Pload Jω0 s + Dp the islanded mode.
where ω0 , Dp , and J are the grid nominal angular frequency, Furthermore, (1) presents the open-loop transfer function
the damping coefficient, and the inertia coefficient of the VSG, ∆ω/∆Pload . It can be seen that ∆ω/∆Pload is a first-order
respectively. Eq. (1) can be rearranged as system that has a real negative pole. Compared to the droop
∆ω 1 1 control with a filter, the pole of ∆ω/∆Pload for the VSG is
=− Jω0
. (2) much closer to the imaginary axis, which contributes to the
∆Pload Dp Dp s +1
slower dynamic response of the VSG upon changes in the
Jω0 output power [10].
Assuming that TVSG = Dp is the time constant of the VSG,
(2) can be rewritten as The Q-V droop coefficient Kpq is calculated as
1 1 (Vmax − Vmin )
∆ω = − ∆Pload . (3) Kpq = , (8)
Dp TVSG s + 1 2Qmax
TVSG is related to the desired initial RoCoF. The RoCoF where Vmax and Vmax are the allowed maximum and minimum
requirement varies in different countries. For example, the voltage deviations, respectively. These parameters are specified
RoCoF requirement in Ireland is 0.5 Hz/s [34]. In Australia, by the grid code [37]. In addition, Qmax is the maximum
the Australian National Electricity Rules cite a minimum reactive power that can be supplied by the VSG. Number
access standard of 1 Hz/s [35], which is used in this paper. 2 in the denominator indicates that the VSG is capable of
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY 4
and
0 3
ROCOF= 0.5 Hz/s Qpcc = [Xg (Vi2 − Vi Vj cosθij ) − Rg Vi Vj sinθij ],
Rg2 + Xg2
( rad/s)
-2 (10)
respectively, where Vi and Vj are the RMS values of the grid
-4
voltages at the PCC and the grid-side (AC bus), respectively.
Additionally, Rg and Xg represent the grid resistance and
-6
inductance, respectively. Please note that δ in (7) represents
-2 -1 0 1 2 3 4 5 the output voltage angle of the VSG operating in the islanded
Time (s) mode while θij in (9) and (10) is the phase angle difference
Fig. 2: VSG performance in the IM: a step response of the ∆ω upon a 4 MW between Vi and Vj when the VSG is operated in GC mode.
load power changes. To study the dynamic performance of the VSG, the small-
signal model of (9) and (10) is established as
TABLE I: Parameters of the study system.
∆Ppcc K11 K12 ∆θij
Quantity Value Unit Description = , (11)
Grid parameters ∆Qpcc K21 K22 ∆Vi
vg 690 V Grid voltage (L-L)
f 50 Hz Nominal frequency where K11 , K22 , K21 , and K22 are related to a specific
Grid parameters (Rg , Xg ) used for the comparison study: Section II-C
Rg , Lg 0.63, 20 mΩ, µH Strong grid with SCR = 15.0, Xg /Rg =10
operating point (θij0 , Vi0 ), shown as
Rg , Lg 2, 19 mΩ, µH Strong grid with SCR=15.0, Xg /Rg =3
3
Rg , Lg 4.5, 14.3 mΩ, µH Strong grid with SCR=15.0, Xg /Rg =1
Rg , Lg 10, 95.8 mΩ, µH Weak grid with SCR=3.0, Xg /Rg =3
K11 = 2 [Rg Vi0 Vj sinθij0 + Xg Vi0 Vj cosθij0 ]
Rg + Xg2
Rg , Lg 22.4, 71.4 mΩ, µH Weak grid with SCR=3.0, Xg /Rg =1
Rg , Lg 25, 239.6 mΩ, µH Weak grid with SCR=1.2, Xg /Rg =3 3
K12 = R2 + X 2 [Rg (2Vi0 − Vj cosθij0 ) + Xg Vj sinθij0 ]
Rg , Lg 56, 178.6 mΩ, µH Weak grid with SCR=1.2, Xg /Rg =1
Grid parameters (Rg , Xg ) used for the simulation study: Section IV-A g g
Rg , Lg 1.68, 37.5 mΩ, µH Strong grid with SCR=8.0, Xg /Rg =7.0
Rg , Lg 2.3, 37.1 mΩ, µH Strong grid with SCR=8.0, Xg /Rg =5.0 3
K21 = 2 [Xg Vi0 Vj sinθij0 − Rg Vi0 Vj cosθij0 ]
Rg , Lg 8.9, 200 mΩ, µH Weak grid with SCR=1.5, Xg /Rg =7
Rg + Xg2
Rg , Lg 20, 191.6 mΩ, µH Weak grid with SCR=1.5, Xg /Rg =3
Rg , Lg 44.9, 142.8 mΩ, µH Weak grid with SCR=1.5, Xg /Rg =1
3
Inverter parameters K22 = 2 [Xg (2Vi0 − Vj cosθij0 ) − Rg Vj sinθij0 ],
Smax 5.0 MVA Inverter rated power Rg + Xg2
Pmax 4.0 MW Inverter rated active power
Qmax 3.0 MVar Inverter rated reactive power
(12)
vdc 3000 V DC Bus voltage where 0 denotes the steady-state operating point, Vi0 is the
fsw 5 kHz Inverter PWM carrier fequency
Lf 95 µH Filter inductance steady-state RMS value of the PCC line-to-ground voltage,
Rf
Cf
0.01
1
Ω
mF
Filter resistance
Filter capacitance
and θij0 is the power angle at the steady-state point.
Fixed parameters for the conventional VSG Fig. 3 shows the small-signal model of the VSG connecting
Dp 1.273 × 106 W/Hz Damping coefficient
J 4052 kg.m2 Inertia coefficient
to a resistive-inductive grid. It can be observed that this model
Kpq 1.5× 10−5 VAR/V Proportional gain of reactive power controller consists of two main parts: Power Control and Power Flow.
Kiq 1× 10−3 1/s Integral gain of reactive power controller
The Power Control represents the small-signal model of the
standard VSG, and the Power Flow represents the small-signal
model of the grid in which both the grid resistance and grid
supplying and absorbing reactive power. In the GCM, it is inductance are considered resulting in cross-coupling terms
recommended to add an integral term Kiq to the reactive power (K12 and K21 ). As shown in Fig. 3, the active and reactive
controller Kpq in order to track the reactive power reference power are coupled via the power angle and voltage magnitude,
with zero steady-state error [19]. Therefore, this paper uses a as presented in (9)-(12). In addition, the grid/line impedance
PI controller for the reactive power control channel. (i.e., Rg and Xg ) has a significant impact on both the
coupling and direct-through terms. Therefore, the independent
control of active and reactive power is challenging in resistive-
C. Control of the Conventional VSG in the GCM inductive grids due to the inherent coupling between the active
and reactive power [11], [13].
In the GCM, the main control objective of the VSG is to 2) The VSG Performance in the GCM: In Section II-B,
regulate its output active and reactive power to the desired the VSG parameters are designed based on the rated power
reference commands. To further investigate the performance of and the RoCoF requirement in the IM. In this section, the
the VSG in the GCM and how the grid impedance parameters VSG performance with the same parameters listed in Table I
affect its performance, a small-signal model that considers the is tested in the GCM to illustrate the shortcomings if the same
inherent power flow coupling is derived in this subsection, VSG parameters are used in the GCM.
based on which the stability analysis is further investigated. Three test cases are conducted. First, the performance of
1) Power Flow Analysis and Small-Signal Modeling of the the VSG is tested against the grid strength. In this test, the
VSG in the GCM: Considering Fig. 1, the active and reactive SCR indicator is adopted, which is a widely used index in the
power injected by the VSG into the grid can be calculated as existing literature for system strength studies. In summary,
3 SCR defines the ratio of the short-circuit capacity at the
Ppcc = [Rg (Vi2 −Vi Vj cosθij )+Xg Vi Vj sinθij ], (9) PCC to the rated capacity of the grid-connected inverter, i.e.,
Rg2 + Xg2
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY 5
Power Control Power Flow GCM introduces minor changes in the loop gain of the system
Pref
G11−OL (s) and G21−OL (s), yet the closed-loop frequency
1 1 1
K11 response is inherently stable. However, the grid strength and
J 0 s s Ppcc
the Xg /Rg ratio variations have obvious effects on the VSG
Dp K 21
transfer functions G11−OL (s) and G21−OL (s).
K iq 1
K12
s
Qref V Qpcc D. Summary of the VSG Control Challenges in GCM
K pq K 22
In Section II-B and Section II-C, it is shown that the VSG
Fig. 3: Small-signal model of the VSG in the resistive-inductive grid. cannot meet the desired performance in both the IM and GCM.
In the IM, the VSG parameters have to be designed according
to several constraints, such as the rated active power and the
Sg /Srated [38]. Generally, the utility grid is considered strong RoCoF requirement to avoid a sharp increase or decrease in the
for SCR > 3, weak for 2 ≤ SCR ≤ 3, and very weak for frequency response when loads are disconnected or connected.
SCR < 2 [39]. As the strength of the utility grid is constantly In the GCM, if the parameters are not properly selected,
changing, an effective controller of the inverter should be the VSG has a poor dynamic response due to significant
capable of working in a wide range of conditions. Therefore, oscillations, a long settling time, and a large overshoot. Such
the performance of the controller has to be examined at poor performance is related to the grid conditions such as the
different SCRs. After that, the performance of the VSG in grid- grid strength SCRs, Xg /Rg ratio, and variation of Zg with
connected mode is examined in this section for different values the same Xg /Rg ratio. For example, the VSG performance is
of Xg /Rg and for different amplitudes of Zg while Xg /Rg worsened further in strong grid conditions.
remains unchanged. In all test cases, the VSG is operated at Given the above analysis, it can be concluded that there is an
the unity power factor, i.e., Qref = 0 MVar. inherent trade-off between meeting the RoCoF requirements in
Fig. 4(a) and (b) shows the simulation results of the VSG the IM and the fast and robust power regulation in the GCM,
step responses under different SCR values as the Xg /Rg is which prevents accurate control of the VSG with assigned
3.0 and 1.0, respectively. It can be seen that the SCR of the fixed values for its control parameters. Hence, to obviate these
grid significantly affects the VSG performance. Specifically, shortcomings, an adaptive VSG control strategy that takes into
the step responses deteriorate in terms of overshoot, settling account the grid parameters is presented in the next section.
time, and oscillations under strong grid conditions. In addition,
the VSG performance further deteriorates in all strong, weak,
and very weak grids with smaller Xg /Rg ratios, as shown III. P ROPOSED A DAPTIVE C ONTROL OF VSG
in Fig. 4(b), where Xg /Rg is set as 1.0. Fig. 4(c) and (d) Fig. 6 and Fig. 7 show the control structure and the detailed
further illustrates the effects of the grid impedance on the implementation of the proposed AVSG control strategy. The
VSG performance. It can be seen that the VSG performance control structure is very similar to the conventional VSG
deteriorates when connected to grids with small Xg /Rg ratios. presented in Fig. 1. However, the control parameters Dp ,
However, the effects of varying Xg /Rg are much smaller than J, Kpq , and Kiq of the AVSG are adaptively tuned based
those of varying the grid SCR. Additionally, increasing the on the online grid impedance estimation (GIE) to achieve
grid impedance magnitude while keeping the Xg /Rg ratio reliable operation upon grid impedance variations. The tuning
unchanged results in significant impacts on the step response procedure is established based on the small-signal model of
of the VSG active power output. the power flow. Therefore, it requires the grid impedance
To further explain the effects of the grid conditions on the parameters, which are estimated online by the inverter itself.
VSG performance, Fig. 5 presents the Bode plots for the Further explanation on the proposed AVSG is provided next.
test cases presented in Fig. 4. Note that the reactive power
command is set to zero, so K12 and K22 are not considered
in the analysis. Furthermore, K11 and K21 are obtained based A. Adaptive Tuning Strategy for the VSG
on the linearized small-signal model of the power flow shown
The small-signal model of the VSG-grid system introduced
in (12), which are calculated from the steady-state operation of
in (11) and (12) is employed to obtain the relationship between
the VSG. The open-loop transfer functions of the active power
the VSG controller parameters and the system response. The
loop considering both K11 and K21 can then be calculated as
VSG controller parameters are tuned adaptively to obtain the
∆Ppcc 1
desired response. As stated previously, Gp (s) and Gq (s) are
G11−OL (s) = ∆P = K11 ,
ref s(Jω0 s + Dp ) defined as the transfer functions of the VSG and the reactive
(13)
∆Qpcc 1 power controller in Fig. 3, i.e.,
G21−OL (s) = = K21 .
∆Pref s(Jω0 s + Dp ) 1
Gp (s) = (14)
s(Jω0 s + Dp )
Fig. 5(a) and (e) presents the Bode plot of the VSG at two
operating points, i.e., Pref = 2 MW and 4 MW. It can be and
Kiq
observed the variation of the operating point of the VSG in the Gq (s) = Kpq + , (15)
s
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY 6
6 6 6 6
5 5 5 5
4 4 4 4
3 3 3 3
2 2 2 2
1 1 1 1
0 10 20 30 40 0 10 20 30 40 0 10 20 30 40 0 10 20 30 40
Fig. 4: VSG performance in GCM upon a change in the active power reference form 2 MW to 4 MW where the J and Dp are kept constant and equal to
the designed values in Subsection II-B: (a) effects of SCR when Xg /Rg = 3.0, (b) effects of SCR when Xg /Rg = 1.0, (c) effects of Xg /Rg parameter
when SCR = 15.0, and (d) effects of variation of Zg for Xg /Rg = 3.0.
Fig. 5: Bode plots of the VSG transfer functions in the GCM under Qref = 0 MVar and different scenarios of the active power operating points and grid
impedance: (a), (e) at two different operating points Pref = 2 MW and 4 MW for same SCR= 15.0, and Xg /Rg = 3.0, (b), (f) effects of the SCR when
Pref = 4 MW and Qref = 0 MVar for same Xg /Rg = 3.0, (c), (g) effects of the Xg /Rg when Pref = 4 MW for the same SCR = 15.0, and (d), (h) effects
of variation of Zg for same Xg /Rg =3.0 and Pref = 4 MW and Qref = 0 MVar.
idq, pcc vdq, pcc idq, inv ∆Ppcc H11 H12 ∆Pref
abc
= , (19)
dq t P Control Dp ∆Qpcc H21 H22 ∆Qref
Power calculation
vdc t 1 1 1 Ppcc
where
Reference generator
which is a second-order transfer function with the natural J, Dp , Kpq , and Kiq are functions of K11 and K22 , which
frequency being ωn and the damping ratio being ζ. On the are further determined by the operating point, i.e., Rg , Xg ,
one hand, by replacing for H11 (s) from (20) in (25) and then Vi0 , Vj0 , and θij0 .
replacing for Gp (s) and Gq (s) from ((14) and ((15) in the It is worth mentioning that the proposed controller is
obtained equation, one can have designed based on the full power flow expressions presented in
ωn2 1 (M Kpq + K11 )s + M Kiq (9) and (10). Hence, the desired performance criteria (settling
= . time, overshoot, and rising time) are always met regardless of
s(s+2ζωn ) s(Jω0 s+Dp ) (K22 Kpq + 1)s + K22 Kiq
(26) the grid strength (strong or weak) and regardless of the grid
Having (26), the right term should satisfy the following type (resistive or inductive).
conditions:
M Kpq + K11
Jω0 = 2 , (27) B. Online Event-based Grid Impedance Estimation Algorithm
ωn (K22 Kpq + 1)
It is demonstrated above that to tune the VSG to cope with
M Kiq
Dp = 2 , (28) both strong and weak grids, the grid impedance information
ωn (K22 Kpq + 1) should be known in advance. However, one key challenge is
1 that the impedance of the grid varies over time, which hinders
Kiq = 2ζωn (Kpq + ). (29) the optimal design if only fixed values for the grid impedance
K22
are used. Therefore, accurate control can only be achieved
On the other hand, by replacing for J, Dp , and Kiq from (27),
based on the actual value of the grid impedance. To solve
(28), and (29) in (23), one can have
this problem, online GIE algorithms that use the inverter itself
ωn2 M +sK22 (Jω0 s+Dp ) can be used [30]. This approach is cost-effective as it does
H22 (s)= . (30)
s +2ζωn s+ωn2
2
M + KpqsK11
s+Kiq
not require additional hardware and uses only the available
local measurements to estimate the grid impedance seen by
By defining the inverter at the PCC.
M
σ =1− , (31) In this paper, the grid impedance estimation technique based
K11 K22
on single frequency injection at 75 Hz is implemented into the
and control loop of the VSG. The injected frequency signal for
M (K22 Kpq + 1)
γ= , (32) grid impedance measurements is chosen at 75 Hz for several
K22 (M Kpq + K11 )
reasons. First, to ensure accurate impedance measurement: the
H22 (s) can be rearranged as grid impedance changes at low frequencies are insignificant
γσ and can be neglected. Therefore, using 75 Hz injection pro-
γ−1+σ s+ γ−1+σ 2ζωn s2 +2ζωn γs+γωn2
H22 (s)= . (33) vides accurate approximation results of the fundamental grid
γσ s+2ζωn γ s2 +2ζωn s+ωn2 impedance [31]. Second, to avoid interference: for impedance
By selecting estimation, harmonic frequencies (e.g., 100 Hz, 150 Hz, 200
1 Hz) could be used. However, there is a great chance of
Kpq = , (34)
K22 interference between the injected harmonic frequency and the
it can be calculated that same harmonic that is usually presented in the grid background
2 − 2σ due to, for example, other non-linear load/ converters. In this
γ= . (35) case, using an inter-harmonics frequency such as 75 Hz that
2−σ
is unlikely to be presented in the grid background ensures the
Thus, since the cross-coupling terms K12 and K21 are not
avoidance of any possible interaction with the grid background
dominant, i.e., |K12 K21 | 6 |K11 K22 |, it can be concluded
harmonics. Finally, to avoid discrete Fourier transform (DFT)
from (31) that 0 6 σ 6 1, and therefore, 0 6 γ 6 1. As a
leakage: the DFT calculation of the voltage and current at 75
result, in addition to a pair of poles similar to those of H11 (s),
Hz with a minimum window length equal to 40 ms ensures
H22 (s) has a real pole and three zeros in the left-half plane
avoiding the DFT leakage. Here, if 25 Hz is considered the
and stable. Finally, by replacing (34)) in ((27), (28), and (29),
fundamental frequency of the DFT, 50 Hz and 75 Hz become
one can have
2 − σ K11 the second and third harmonics. However, choosing any other
J= , (36) injection frequency such as 60 Hz results in DFT leakage
2ω0 ωn2
as there is no correlation between 50 Hz and the injected
2ζ(1 − σ)K11 harmonic 60 Hz.
Dp = , (37)
ωn To address the impacts of the perturbation currents on
and power quality and the trade-off between active and passive
4ζωn
Kiq = . (38) techniques, this paper proposes a new algorithm to automat-
K22 ically trigger the grid impedance estimation algorithm only
Based on (34), (36), (37), and (38), the VSG and the reactive when required. Therefore, the possible adverse impacts of
power controller can be tuned such that H11 (s) and H22 (s) disturbance amplitude on power quality can be significantly
have the desired responses with the desired natural frequency reduced [26], [40]. Additionally, to ensure a fast and accurate
ωn and damping ζ. However, as can be seen in these equations, estimation of the grid impedance, the perturbation currents
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY 8
Control Mode
fast response of the inner loop. mode?
Selection
Simultaneously with the injection of id−inj and iq−inj , the Grid-connected mode
current and voltage responses (vres (75 Hz), ires (75 Hz)) at the
Enable
PCC of phase A, B, or C are recorded. Then, the fundamental No
AVSG?
grid impedance (Zg (50 Hz)) is estimated by approximating its
Yes
value to Zg (75 Hz) as follows [27], [41].
Impedance
Initialize
- Inject iqd, inj
∼ vres (75 Hz) ∼ 1 vres (75 Hz) - Estimate Rg , Lg : Eq. (39)
Rg = < , Lg = = . (39)
ires (75 Hz) ω0 ires (75 Hz)
Define paramters of
C. Online Implementation of the Proposed AVSG Use the designed fixed values for
the desired response
Impedance
- Delay Qref,d =Qref (t − TGIE )
Update
Therefore, the inverter can now connect to the grid, and - Inject iqd, inj
the desired response with the desired natural frequency - Estimate Rg , Lg : Eq. (39)
and damping is ensured.
4) Afterwards, the inverter power reference commands AVSG
Yes
are read and continuously monitored for any changes. ON?
0.974 0.945 0.9 0.82 0.66 0.4 0.992 0.984 0.968 0.935 0.86 0.6
0.997
5 0.99
5
Imaginary Axis
Imaginary Axis
0.997 0.999
035 30 25 20 15 10 5
070 60 50 40 30 20 10
0.997 0.999
-5 0.99
-5 0.997
0.974 0.945 0.9 0.82 0.66 0.4 0.992 0.984 0.968 0.935 0.86 0.6
-35 -30 -25 -20 -15 -10 -5 0 5 -70 -60 -50 -40 -30 -20 -10 0
Real Axis Real Axis
(a) (a)
0.974 0.945 0.9 0.82 0.66 0.4 0.992 0.984 0.968 0.935 0.86 0.6
0.997
5 0.99
5
Imaginary Axis
Imaginary Axis
0.997 0.999
035 30 25 20 15 10 5
070 60 50 40 30 20 10
0.997 0.999
-5 0.99
-5 0.997
0.974 0.945 0.9 0.82 0.66 0.4 0.992 0.984 0.968 0.935 0.86 0.6
-35 -30 -25 -20 -15 -10 -5 0 5 -70 -60 -50 -40 -30 -20 -10 0
Real Axis Real Axis
(b) (b)
Fig. 8: Poles and zeros map of the closed-loop transfer function H11 : (a) the Fig. 9: Poles and zeros map of the closed-loop transfer function H22 : (a) the
conventional VSG and (b) the proposed adaptive VSG. conventional VSG and (b) the proposed adaptive VSG.
origin, which indicates better system performance with less is worth noting that Dp value at 100% is the optimal tuned
oscillations. value proposed in this paper. Here, the real zero and pole
Similarly, Fig. 9(a) and (b) shows poles and zeros locations cancel each other; hence, these real zero and pole are not
of the closed-loop transfer function H22 of the conventional shown in this figure. Fig. 11(b) shows the changing pattern of
and the proposed adaptive VSG, respectively. Again, placing the system poles with the variations of its inertia. It can be
the system poles of the proposed adaptive VSG control scheme seen that increasing J reduces the stability margin as the two
far away from the origin improves the system performance. complex-conjugate closed-loop poles move towards the origin.
However, compared to the conventional VSG, the poles of the
2) Sensitivity to Controller Parameters: To test the system
system under the proposed control scheme are still roughly far
robustness, both the conventional and the proposed adaptive
from the origin.
VSG control schemes with various damping and inertia values
are tested. In each case study, to obtain the root loci, the
damping is varied with ±10% of the nominal value while IV. S IMULATION AND E XPERIMENTAL R ESULTS
the inertia is fixed at the nominal value. Then, another test is A. Simulation Results
conducted by varying the inertia with ±10% of the nominal To evaluate the performance of the proposed AVSG and the
value while maintaining the damping fixed at the nominal conventional VSG, the system shown in Fig. 6 is simulated
value. in MATLAB/Simulink and PLECS toolbox. The simulation
Fig. 10(a) and (b) presents the poles and zeros of H11 for the parameters are listed in Table I. The investigated test cases
conventional VSG during variations of the damping and inertia include active and reactive reference command changes for
values, respectively. On the one hand, Fig. 10(a) shows that by both weak and strong grid conditions. For each grid condition
increasing DP [90%, 100%, 110%], the system performance with the same SCR, different tests are conducted considering
is improved as the two complex-conjugate closed-loop poles two different X/R ratios.
move far from the origin. On the other hand, increasing J 1) Strong Grid with SCR = 8.0: In this part, the perfor-
adversely impacts the system stability as these poles are moved mance of the AVSG is compared with that of the conventional
towards the origin in the s-plane. VSG for strong grid conditions with two Xg /Rg ratios. For
The robustness of the proposed adaptive VSG is tested. The the Xg /Rg = 5, the grid impedance parameters are chosen as
obtained results are shown in Fig. 11(a) and (b). Similarly Rg = 2.3 mΩ and Lg = 37.1 µH. To simulate a strong grid
to the conventional control, increasing the damping moves with Xg /Rg = 7, the grid impedance parameters are set to
the two complex-conjugate closed-loop poles far from the Rg = 1.68 mΩ and Lg = 37.5 µH.
origin; see Fig. 11(a). However, the real pole moves in the The obtained results are shown in Fig. 12. Initially, the
opposite direction after increasing Dp from 90% to 110%. It inverter active and reactive power reference commands are
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY 10
3.49
reference command changes from 0 to 2 MW. Then, it changes
5 0.993 at t =25 s to 4 MW. Finally, at t =40 s, the reactive power
3.48
Imaginary Axis
0.999
reference command changes from 0 to 1.5 MVar. Fig. 12(a)
3.47
and (d) shows the dq components of the PCC voltage for
040 35 30 25 20 15 10 5
3.46
-0.6 -0.4 both the VSG and AVSG corresponding to Xg /Rg = 5 and
0.999
Real Axis
1
0 30 Xg /Rg = 7, respectively. Overall, it can be seen that the AVSG
-1
-5
0.993
-31 -30 -29 -28 ensures seamless transient performance without oscillations
Real Axis
0.984
0.964 0.935 0.87 0.74 0.45
with a settling time of around 0.8 s.
-40 -30 -20 -10 0 10 Additionally, as shown in Fig. 12(b) and (e), the dq com-
Real Axis ponents of PCC current change within the desired system
(a) response. The zoom-in view in Fig. 12(b) and (c) presents
0.984
0.964 0.935 0.87 0.74 0.45
the small variations in the dq current required to estimate the
3.8 grid impedance in real-time. As stated previously, these small
5 0.993
3.6
variations result from the injected 75 Hz perturbations in the
Imaginary Axis
0.985
to obtain Xg /Rg = 1.
010 8 6 4 2
0.985 the grid resistance and inductance which are being estimated
in real-time. Consequently, the proposed AVSG is capable of
010 8 6 4 2
800 8000 6
6000
600 4
564 4000
400 570
563
2000 2
566
0.5
200 0 100
562 10 0
10 11 12 -0.5 0 0
10 10.2
-2000 -10
0 -100
9 10 11 12 10 10.1 10.2
-4000 -2
0 10 20 30 40 50 0 10 20 30 40 50 0 10 20 30 40 50
600 1
564 0.5 5
568
400
566 563 0
564 0.5 100 20
200 -0.5 0
562 0 0
10 11 12 13-0.5 -1
0 10 10.2 -100 -20
9 10 11 12 10 10.1 10.2
-1.5 -5
0 10 20 30 40 50 0 10 20 30 40 50 0 10 20 30 40 50
Fig. 12: The simulation results of the conventional VSG and the AVSG upon changes in the active and reactive power references when the inverter is connected
to a strong grid SCR = 8.0 and: (a), (b), (c) Xg /Rg = 5 and (d), (e), (f) Xg /Rg = 7.
800 8000 6
6000
600 4
580 564 4000
400 563.5
560
2000 2
563
0.5
200 0 5
540 0 100
10 11 12
0
-0.5 -2000 0 0
0 10 10.2 -100 -5
10 11 12 10 10.1 10.2
-4000 -2
0 10 20 30 40 50 0 10 20 30 40 50 0 10 20 30 40 50
600 4000 4
600 564
800
4000 4
600 750 564
700 563.5 2000
400 650 563
2
0.5
600
200 0 0 100 5
550 0
10 12 -0.5 0 0
0 10 10.2
-2000 -100 -5
10 11 12 10 10.1 10.2
-200 -2
0 10 20 30 40 50 0 10 20 30 40 50 0 10 20 30 40 50
Fig. 13: Simulation results of the conventional VSG and the AVSG upon changes in the active and reactive power references when the inverter is connected
to a weak grid SCR = 1.5 and: (a), (b), (c) Xg /Rg = 7; (d), (e), (f) Xg /Rg = 3; and (g), (h), (i) Xg /Rg = 1.
GIE algorithm is enabled automatically at 10, 25, and 40 s Fig. 14(c) compares the estimated grid components (Rest and
due to changes in the inverter active and reactive reference Lest ) with their true/reference values. It is evident that the
commands. Fig. 14(a) also depicts the perturbation currents, proposed implementation of the GIE is reliable and provides
i.e., id−inj and iq−inj , required for the impedance estimation. very accurate results.
It can be seen that the GIE algorithm has minimal impact
on the system as it does not disrupt the system continuously, Fig. 15 shows the control parameters of the proposed
and the injected perturbation currents have relatively small adaptive tuning scheme. For t < 5 s, the original control
amplitudes of 3.3 A. Fig. 14(b) shows the PCC current with a parameters listed in Table I are used. Then, these parameters
zoom-in view of the time duration when the GIE is enabled. are tuned adaptively when the proposed control scheme is
enabled for t ≥ 5 s. To ensure desired performance under
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY 12
Fig. 14: The simulation results of the AVSG in a very weak grid (SCR = 1.5, Xg /Rg = 1): (a) enable signal and dq current injections for GIE; (b) PCC
current; and (c) references and estimated grid resistance and inductance.
2500 Filter
0 Grid Impedance
0 10 20 30 40 50
(a) Interface
-4
10
1
DC Power Supply
0.5
Fig. 16: The experimental setup.
0
10-3 TABLE II: Parameters of the experimental setup.
2
Quantity Value Unit Description
1 Grid parameters
vg 110 V Grid voltage (L-L)
f 50 Hz Nominal frequency
0 Rg , Lg 0.85, 3.0 Ω, mH Strong grid with SCR=6.74, Xg /Rg =1.1
0 10 20 30 40 50 Rg , Lg 0.67, 10.5 Ω, mH Weak grid with SCR=2.54, Xg /Rg =4.92
Inverter parameters
Sbase 1.4142 kVA Inverter rated power
(b) Pbase 1.0 kW Inverter rated active power
vdc 320 V DC Bus voltage
Fig. 15: The simulation results of control parameters tuning of the proposed fsw 20 kHz Inverter PWM carrier frequency
AVSG in a very weak grid (SCR = 1.5, Xg /Rg = 1): (a) control parameters Lf 4 mH Filter inductance
of the active power channel and (b) control parameters of the reactive power Rf 0.06 Ω Filter resistance
channel. Cf 30 µF Filter capacitance
Fixed parameters for the conventional VSG
Dp 318.3 W/Hz Damping coefficient
J 1.013 kg.m2 Inertia coefficient
−3
Kpq 7.18× 10 VAR/V Proportional gain of reactive power controller
different operating points, the control parameters are re-tuned Kiq 1× 10 −5
1/s Integral gain of reactive power controller
after applying the step changes in the active power reference
at t =10 and 25 s and the reactive power reference at t =40 s.
The performance of the controllers is tested in both strong
and weak grids. In each test, step changes in the active and
B. Experimental Results reactive power reference commands are applied. The times of
In this section, the experimental results based on a scaled- application of these tests are referred to as t1 , t2 , and t3 in
down setup are presented to validate the effectiveness of the Fig. 17 and Fig. 18. Initially, both inverters operate in the
proposed control. The tested systems are the conventional VSG steady-state where the power reference commands are Pref =
and the AVSG as presented in Fig. 1 and Fig. 6, respectively. 200 W and Qref = 0 VAR. Then, for the proposed AVSG, the
The system parameters used for the experiment are listed control algorithm is enabled at t1 , and the values of id−inj and
in Table II. Fig. 16 shows the experimental setup used to iq−inj are set to 0.25 A. After 5 s of enabling the AVSG, a
evaluate the control performance. It consists of a DC power step change in the active power reference command from 200
supply, a SiC-based two-level three-phase Imperix inverter, to 800 W is applied at t2 . Finally, a step change in the reactive
an LC filter, an RL grid impedance, and a Regatron grid power reference command from 0 to 150 VAR is applied at
simulator. The control algorithm is implemented directly from t3 .
MATLAB/Simulink into the BoomBox Imperix Controller. Fig. 17 shows the experimental results in a strong grid.
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY 13
t2 t3 t2 t3
[3 s/div] [4 s/div]
Pref changes Qref changes Pref changes Qref changes
[2 A/div] ia ib ic [2 A/div] ia ib ic
[4 ms/div] [4 ms/div]
(a) (a)
[3 s/div] [4 s/div]
Pref changes Qref changes Pref changes Qref changes
[2 A/div] ia ib ic [2 A/div] ia ib ic
[4 ms/div] [4 ms/div]
(b) (b)
(c) (c)
Fig. 17: The experimental results of the conventional and the AVSG in a Fig. 18: The experimental results of the conventional and the AVSG in a
strong grid (SCR=6.74, Xg /Rg =1.1): (a) PCC current waveforms of the weak grid (SCR=2.54, Xg /Rg =4.92): (a) PCC current waveforms of the
conventional VSG, (b) PCC current waveforms of the proposed AVSG, and conventional VSG, (b) PCC current waveforms of the proposed AVSG, and
(c) PCC power waveforms. (c) PCC power waveforms.
Fig. 17(a), (b) and (c) compares the PCC currents and the parameters of the traditional VSG are kept fixed at those
power tracking capability of the VSG and the proposed AVSG, values presented in Table II. These fixed values are based
respectively. It is evident that there are significant oscillations on the rated power of the inverter and the desired RoCoF.
in the output power waveform of the conventional VSG for However, the control parameters of the proposed control are
almost 10 s. In contrast, the AVSG ensures the desired dy- automatically tuned during this test based on the proposed
namic performance. After changing the active power reference equations in this paper, i.e., (34), (36), (37), and (38). The
command, the AVSG takes around 1 s to settle down (0.2 s corresponding steady-state control parameters of the proposed
for the GIE and 0.8 s for tracking the new power reference controller are presented in Table III.
commands). Similarly, Fig. 18 shows the experimental results in a weak
It is worth emphasizing that during the test, the control grid. Fig. 18(a), (b) and (c) compares the PCC currents and
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY 14
tended Kalman filter,” IEEE Transactions on Power Electronics, vol. 29, MOHAMMAD HASAN RAVANJI (Member,
no. 2, pp. 631–641, 2013. IEEE) received his B.Sc., M.Sc. and Ph.D. degrees
[29] S. Cobreces, E. J. Bueno, D. Pizarro, F. J. Rodriguez, and F. Huerta, all in electrical power engineering from Sharif Uni-
“Grid impedance monitoring system for distributed power generation versity of Technology (SUT), Tehran, Iran, in 2012,
electronic interfaces,” IEEE Transactions on Instrumentation and Mea- 2014, and 2020, respectively. He was a visiting
surement, vol. 58, no. 9, pp. 3112–3121, 2009. student with the University of Waterloo, Waterloo,
[30] M. Ciobotaru, V. Agelidis, and R. Teodorescu, “Line impedance estima- ON, Canada from Oct. 2017 to April 2018. Further,
tion using model based identification technique,” in Proceedings of the he was with the Iran Grid Management Company
2011 14th European Conference on Power Electronics and Applications. (IGMC), Tehran, Iran, as a researcher in their system
IEEE, 2011, pp. 1–9. planning and dynamic studies group from Feb. 2019
[31] L. Asiminoaei, R. Teodorescu, F. Blaabjerg, and U. Borup, “Implementa- to July 2020. He is currently a post-doctoral research
tion and test of an online embedded grid impedance estimation technique fellow at Monash University, Clayton, Australia. His current research interests
for PV inverters,” IEEE Transactions on Industrial Electronics, vol. 52, include power system stability, renewable energy systems and the application
no. 4, pp. 1136–1144, 2005. of grid forming and grid following inverters in weak power grids.
[32] T. Roinila, T. Messo, and A. Aapro, “Impedance measurement of
three phase systems in DQ-domain: Applying MIMO-identification
techniques,” in 2016 IEEE Energy Conversion Congress and Exposition
(ECCE). IEEE, 2016, pp. 1–6.
[33] N. Mohammed and M. Ciobotaru, “Fast and accurate grid impedance
estimation approach for stability analysis of grid-connected inverters,”
Electric Power Systems Research, vol. 207, p. 107831, 2022.
[34] W. Uijlings and J. Timpert, “Rocof alternative solutions technology
assessment,” DNV GL Energy Advisory, 2015.
[35] N. Modi, R. Yan et al., “Low inertia power systems: Frequency response WEIHUA ZHOU (Member, IEEE) was born in
challenges and a possible solution,” in 2016 Australasian universities Anhui, China, in 1993. He received the B.Eng. de-
power engineering conference (AUPEC). IEEE, 2016, pp. 1–6. gree in electrical engineering from the Honors Col-
[36] J. M. Guerrero, M. Chandorkar, T.-L. Lee, and P. C. Loh, “Advanced lege, Northwestern Polytechnical University, Xi’an,
control architectures for intelligent microgrids—part i: Decentralized China, in 2014, the M.Sc. degree in electrical engi-
and hierarchical control,” IEEE Transactions on Industrial Electronics, neering from the School of Automation, Northwest-
vol. 60, no. 4, pp. 1254–1262, 2012. ern Polytechnical University, in 2017, and the Ph.D.
[37] J. M. Guerrero, J. C. Vasquez, J. Matas, L. G. De Vicuña, and degree in power electronics from the Department
M. Castilla, “Hierarchical control of droop-controlled AC and DC micro- of Energy Technology, Aalborg University, Aalborg,
grids—A general approach toward standardization,” IEEE Transactions Denmark, in 2020.
on industrial electronics, vol. 58, no. 1, pp. 158–172, 2010. From November 2015 to May 2016, he was a
[38] W. Rui, S. Qiuye, M. Dazhong, and H. Xuguang, “Line impedance Junior Research Assistant at the Department of Mechanical and Automation
cooperative stability region identification method for grid-tied inverters Engineering, The Chinese University of Hong Kong, Hong Kong. From
under weak grids,” IEEE Transactions on Smart Grid, vol. 11, no. 4, August 2020 to November 2020, he was a Visiting Scholar at the Department
pp. 2856–2866, 2020. of Marine Technology, Norwegian University of Science and Technology,
[39] D. Zhu, S. Zhou, X. Zou, and Y. Kang, “Improved design of PLL Trondheim, Norway. In 2021, he was a Postdoctoral Fellow at the Department
controller for LCL-type grid-connected converter in weak grid,” IEEE of Electrical Engineering, KU Leuven, Leuven, Belgium. He is currently a
Transactions on Power Electronics, vol. 35, no. 5, pp. 4715–4727, 2019. Postdoctoral Research Fellow with the Department of Electrical and Computer
[40] P. Garcia, M. Sumner, Á. Navarro-Rodrı́guez, J. M. Guerrero, and Systems Engineering, Monash University, Melbourne, Australia. His research
J. Garcia, “Observer-based pulsed signal injection for grid impedance interests include modeling and control of power electronic converters, energy
estimation in three-phase systems,” IEEE Transactions on Industrial storage systems, and stability analysis and enhancement of power electronic-
Electronics, vol. 65, no. 10, pp. 7888–7899, 2018. and underground cable-based modern power systems.
[41] A. V. Timbus, R. Teodorescu, F. Blaabjerg, and U. Borup, “Online
grid impedance measurement suitable for multiple pv inverters running
in parallel,” in Twenty-First Annual IEEE Applied Power Electronics
Conference and Exposition, 2006. APEC’06. IEEE, 2006, pp. 5–pp.