INSPECTION RESISTANCE & POLARIZATION INDEX (PI)

Standard
Phase To Ground Phase To Phase
IEEE 43
RESULT
NILAI RATING TEGANGAN (VOLT)
MOTOR & MEGGER
RATING VOLT RATING VOLT
No.
MOTOR MEGGER (VDC)
1 <1000 500
2 1000 - 2500 500 - 1000
3 2051 - 5000 1000 - 5000
4 5001 - 12000 2500 - 5000
5 >12000 5000 - 10000
STANDAR MINIMUM TAHANAN ISOLASI

TAHANAN ISOLASI
MINIMUM

IR (1 Menit) = {kV + 1} 𝙈 𝙊𝙝𝙢

IR (1 Menit) = 100 𝙈 𝙊𝙝𝙢

IR (1 Menit) = 5 𝙈 𝙊𝙝𝙢

𝚔𝚎𝚝:
𝙸𝚁 = 𝙸𝚗𝚜𝚞𝚕𝚊𝚝𝚒𝚘𝚗 𝚁𝚎𝚜𝚒𝚜𝚝𝚊𝚗𝚌𝚎 (𝚃𝚊𝚑𝚊𝚗𝚊𝚗 𝙸𝚜𝚘𝚕𝚊𝚜𝚒)
10 𝚔𝚊𝚕𝚒 𝚃𝚎𝚜𝚝 = 1 𝙼𝚎𝚗𝚒𝚝/𝚝𝚎𝚜𝚝

𝙋𝘼𝙍𝘼𝙈𝙀𝙏𝙀𝙍 𝙉𝙄𝙇𝘼𝙄 𝙋𝙊𝙇𝘼𝙍𝙄𝙕𝘼𝙏𝙄𝙊𝙉 𝙄𝙉𝘿𝙀𝙓 (𝙋𝙄)

𝙉𝙄𝙇𝘼𝙄 𝙋𝙄

<1, 0
1,0 - 1,4
1,5 - 1,9
2,0 - 2,9
3,0 - 4,0
>4, 0
𝙿𝚎𝚛𝚜𝚊𝚖𝚊𝚊𝚗 1
𝙋𝙄 = 𝙄𝙍 𝚖𝚎𝚗𝚒𝚝 𝚔𝚎 10 ÷ 𝙄𝙍 𝚖𝚎𝚗𝚒𝚝 𝚔𝚎 1
MUM TAHANAN ISOLASI (Standard IEEE 43)

OBJEK UJI

1} 𝙈 𝙊𝙝𝙢 𝚆𝚒𝚗𝚍𝚒𝚗𝚐 𝚢𝚊𝚗𝚐 𝚍𝚒𝚋𝚞𝚊𝚝 <1970

𝙰𝚛𝚖𝚊𝚝𝚞𝚛𝚎 𝙳𝙲 / 𝚆𝚒𝚗𝚍𝚒𝚗𝚐 𝙰𝙲
𝚢𝚊𝚗𝚐 𝚍𝚒𝚋𝚞𝚊𝚝 >1970

𝚄𝚗𝚝𝚞𝚔 𝙼𝚘𝚝𝚘𝚛 < 1000𝚅

𝚎𝚜𝚒𝚜𝚝𝚊𝚗𝚌𝚎 (𝚃𝚊𝚑𝚊𝚗𝚊𝚗 𝙸𝚜𝚘𝚕𝚊𝚜𝚒)

𝙄𝙇𝘼𝙄 𝙋𝙊𝙇𝘼𝙍𝙄𝙕𝘼𝙏𝙄𝙊𝙉 𝙄𝙉𝘿𝙀𝙓 (𝙋𝙄) 𝙎𝙩𝙖𝙣𝙙𝙖𝙧𝙙 𝙄𝙀𝙀𝙀 43

𝙆𝙚𝙩𝙚𝙧𝙖𝙣𝙜𝙖𝙣

𝘽𝙚𝙧𝙗𝙖𝙝𝙖𝙮𝙖
𝙎𝙖𝙣𝙜𝙖𝙩 𝙅𝙚𝙡𝙚𝙠
𝙅𝙚𝙡𝙚𝙠
𝙉𝙤𝙧𝙢𝙖𝙡
𝘽𝙖𝙞𝙠
𝙎𝙖𝙣𝙜𝙖𝙩 𝘽𝙖𝙞𝙠

÷ 𝙄𝙍 𝚖𝚎𝚗𝚒𝚝 𝚔𝚎 1
STANDAR MINIMUM TAHANAN ISOLASI
(Standard IEEE 43)
TAHANAN ISOLASI
OBJEK UJI
MINIMUM

IR (1 Menit) = {kV + 1} 𝙈 𝙊𝙝𝙢 𝚆𝚒𝚗𝚍𝚒𝚗𝚐 𝚢𝚊𝚗𝚐 𝚍𝚒𝚋𝚞𝚊𝚝 <1970

𝙰𝚛𝚖𝚊𝚝𝚞𝚛𝚎 𝙳𝙲 / 𝚆𝚒𝚗𝚍𝚒𝚗𝚐 𝙰𝙲
IR (1 Menit) = 100 𝙈 𝙊𝙝𝙢
𝚢𝚊𝚗𝚐 𝚍𝚒𝚋𝚞𝚊𝚝 >1970

IR (1 Menit) = 5 𝙈 𝙊𝙝𝙢 𝚄𝚗𝚝𝚞𝚔 𝙼𝚘𝚝𝚘𝚛 < 1000𝚅

𝚔𝚎𝚝:
𝙸𝚁 = 𝙸𝚗𝚜𝚞𝚕𝚊𝚝𝚒𝚘𝚗 𝚁𝚎𝚜𝚒𝚜𝚝𝚊𝚗𝚌𝚎 (𝚃𝚊𝚑𝚊𝚗𝚊𝚗 𝙸𝚜𝚘𝚕𝚊𝚜𝚒)
10 𝚔𝚊𝚕𝚒 𝚃𝚎𝚜𝚝 = 1 𝙼𝚎𝚗𝚒𝚝/𝚝𝚎𝚜𝚝

𝙋𝘼𝙍𝘼𝙈𝙀𝙏𝙀𝙍 𝙉𝙄𝙇𝘼𝙄 𝙋𝙊𝙇𝘼𝙍𝙄𝙕𝘼𝙏𝙄𝙊𝙉 𝙄𝙉𝘿𝙀𝙓 (𝙋𝙄)


𝙎𝙩𝙖𝙣𝙙𝙖𝙧𝙙 𝙄𝙀𝙀𝙀 43

𝙉𝙄𝙇𝘼𝙄 𝙋𝙄 𝙆𝙚𝙩𝙚𝙧𝙖𝙣𝙜𝙖𝙣

<1, 0 𝘽𝙚𝙧𝙗𝙖𝙝𝙖𝙮𝙖
1,0 - 1,4 𝙎𝙖𝙣𝙜𝙖𝙩 𝙅𝙚𝙡𝙚𝙠
1,5 - 1,9 𝙅𝙚𝙡𝙚𝙠
2,0 - 2,9 𝙉𝙤𝙧𝙢𝙖𝙡
3,0 - 4,0 𝘽𝙖𝙞𝙠
>4, 0 𝙎𝙖𝙣𝙜𝙖𝙩 𝘽𝙖𝙞𝙠
𝙿𝚎𝚛𝚜𝚊𝚖𝚊𝚊𝚗 1
𝙋𝙄 = 𝙄𝙍 𝚖𝚎𝚗𝚒𝚝 𝚔𝚎 10 ÷ 𝙄𝙍 𝚖𝚎𝚗𝚒𝚝 𝚔𝚎 1

𝙈𝙀𝙉𝙂𝙀𝙏𝘼𝙃𝙐𝙄 𝘼𝙍𝙐𝙎 𝘽𝙊𝘾𝙊𝙍


𝙿𝚎𝚛𝚜𝚊𝚖𝚊𝚊𝚗 2
𝙄𝙍 𝚛𝚊𝚝𝚊-𝚛𝚊𝚝𝚊 = 𝙅𝙪𝙢𝙡𝙖𝙝 𝙄𝙍 (𝙈 𝙤𝙝𝙢) ÷ 𝙣
𝚔𝚎𝚝:
𝙸𝚁 = 𝙸𝚗𝚜𝚞𝚕𝚊𝚝𝚒𝚗𝚐 𝚁𝚎𝚜𝚒𝚜𝚝𝚊𝚗𝚌𝚎 (𝙈 𝙤𝙝𝙢)
𝚗 = 𝙹𝚞𝚖𝚕𝚊𝚑 𝙳𝚊𝚝𝚊 (𝚃𝚎𝚜𝚝)

𝙿𝚎𝚛𝚜𝚊𝚖𝚊𝚊𝚗 3
𝙄 𝚒𝚜 = 𝙑 (𝙻𝙻) ÷ 𝙄𝙍 𝚛𝚊𝚝𝚊-𝚛𝚊𝚝𝚊(𝙆 𝙤𝙝𝙢)
𝙺𝚎𝚝:
𝙄 𝚒𝚜 = 𝙰𝚛𝚞𝚜 𝙱𝚘𝚌𝚘𝚛 𝙱𝚘𝚌𝚘𝚛 (𝙢𝘼)
𝙑 (𝙻𝙻) = 𝚃𝚎𝚐𝚊𝚗𝚐𝚊𝚗 𝙻𝚒𝚗𝚎 𝚃𝚘 𝙻𝚒𝚗𝚎 (𝙑)

𝙎𝙏𝘼𝙉𝘿𝘼𝙍𝘿 𝙀𝘼𝙎𝘼 𝘼𝙍 100


𝙉𝙞𝙡𝙖𝙞 𝘿𝙚𝙫𝙞𝙖𝙨𝙞 𝙙𝙖𝙧𝙞 𝙏𝙖𝙝𝙖𝙣𝙖𝙣 𝘽𝙚𝙡𝙞𝙩𝙖𝙣 = +/- 5%