3) The main purpose of IFR is design for reduce vapor phase of liquid fuel (NGL) so the
design which required for 30 inch manhole which make more opening area will not
comply to design purpose. The offer for rectangular 600x500 mm (Or 24” manhole)
according to standard is better, not recommend for 30 inch as project specification.
4) Design of manufacture is rectangular 600x500 mm compare to round 24” manhole
the opening area is better. Please see below detail.