HV circuit breaker testing

 Are pre-insertion resistors in parallel with the main circuit breakers contacts?

Yes. The way a pre-insertion resistor works is that the resistor contacts will close first and
will be the only contact in the circuit, then the main contacts will close and both resistor
and main contact will be in the circuit at the same time in parallel. At this point the main
contacts have the vast majority of the current flowing since the resistance is in the micro-
ohm range compared to the 10-10 kilo-ohm range of the resistor (depending on design).
The design of the circuit breaker can vary but for the majority of the circuit breakers,
once the main contact is closed the resistor will open up shortly afterwards i.e. a few
milliseconds, for other designs the resistor may be left in the circuit while the CB is
closed.

 Are pre-insertion resistors left energized when a breaker is closed?

This depends on the design of the circuit breaker. For some designs the pre-insertion
resistor will close first, then shortly after the main contacts close, the pre-insertion
resistor will open. For other designs the pre-insertion resistor will stay closed while the
main contact is closed.

 Are there any standards regarding circuit breaker testing?

The two predominant standards are:


1. IEEE C37.09 IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers
Rated on a Symmetrical Current Basis.

2. IEC 62271-100 High-voltage switchgear and controlgear – Part 100: Alternating-


current circuit-breakers.

 Can I use circuit breaker testers to test 50/51 relays?

No. To test the 50/51 relays a secondary current injection test set is required. Megger has
a range of relay test sets that can be used to accomplish this.

 Can I use live tank breakers for a breaker and a half scheme?

A live tank breaker can be used for a breaker and a half scheme. From an operating
standpoint you can use either a live tank breaker or a dead tank breaker you just need to
take into consideration several design parameters such as physical dimensions, CTs
needed, etc.

 Does NETA require a motion test?


This depends on the type of circuit breaker. For medium vacuum CBs, time and travel
analysis is recommended but not required. For Oil CBs and SF6 CBs, they require a time
and travel analysis test. This is according to the NETA ATS-2013 and MTS 2011.

 How do I detect SF6 leaks?

There are a couple ways to look for an SF6 leak. One method is to use a gas “sniffer” that
you move around the breaker and it will give you an audible indication when it finds the
leak. Another method is to use and special infrared camera designed for SF6 leak
detection.

 How do I test distribution breakers?

Basic testing for all breakers is the same. You want to record coil current, station voltage,
contact resistance, contact times and travel, then calculate certain parameters from these.
The main difference from a vacuum CB compared to an SF6 or OCB is that the stroke
will be much shorter.

 If the manufacturer does not provide a ratio (conversion factor/table) for motion
analysis, should I still perform motion analysis?

Yes. Even if you don’t have the proper conversion factor or table you should still perform
a travel recording to help evaluate the breakers performance. You will not be able to
correctly determine the velocity of the contacts but you will still be able to trend the
motion over time. If you know the stroke length you can build a simple conversion factor
where the total angle or distance traveled is equal to the stroke length of the circuit
breaker. It should be noted that this method assumes that your circuit breaker is working
correctly at the time of measurement. You can then use these values moving forward.
Additionally you can still look at parameters such as overtravel, rebound and contact
wipe as a percentage of the total stroke to determine if you need to adjust the dampening
on the mechanism.

 Is measuring velocity important on vacuum breakers at the distribution level?

Yes. Velocity is important to all circuit breakers. When evaluating vacuum circuit
breakers, motion and subsequently velocity is often not measured. Additionally, the
manufacturer may not give you any specifications for the velocity. It is still an important
parameter that you can trend to verify correct operation. Even though the manufacturer
may not provide velocity specs, they may still provide stroke and overtravel
specifications.

 Is there an industry standard for determining the frequency and type of testing on
CBs?

There is no industry standard determining the test frequency and type of tests to be
performed. These vary by type of CB, manufacturer, and the type of application the
circuit breaker is utilized in. It is best to consult the circuit breaker manual to determine
proper maintenance and testing schedule. It is common to have 1, 3 or 5, and 10 year
maintenance intervals for different types of tests to be performed.

 Many manufacturers claim it is not necessary to test motion on a vacuum circuit


breaker. Is this true?

No. Travel measurements are a very valuable tool in circuit breaker analysis. One of the
common arguments against measuring motion on vacuum CBs is that the contact stroke
is so short that you are better off measuring stroke with a pair of calipers when the
breaker is in fully open position compared to fully closed position and you can verify the
CB is traveling fast enough from the contact times. If you don’t measure motion you will
lose valuable information about how the circuit breaker is behaving and won’t see if there
is a large amount of overtravel or rebound. If these parameters are too large it can cause
damage to the breaker or miss-operation. These parameters can often be easily adjusted in
the field and you may be able to find the tolerances on the nameplate.

 Should SF6 GCBs be Power Factor tested?

This is a frequently debated topic. If the circuit breaker has grading capacitors that you
have access to i.e. Live Tank CBs then it is recommended to test these to verify their
value. Most manufacturers don’t recommend Power Factor testing SF6 dead tank circuit
breakers. To check the quality of the SF6 gas i.e. the insulation of the CB, it is
recommended to perform a moisture and purity test on the SF6 gas.

There have been some reports that you can determine some issues within the CB contacts
with a Power Factor test, so several utilities still promote and perform these tests on SF6
circuit breakers. If you perform PF testing on your SF6 CBs remember that you will have
very small capacitance values and that your primary evaluation should be of the watts lost
and the leakage current. A hot collar test may also be performed to evaluate the condition
of the porcelain and the external insulation elements.

 What is a dashpot?

When the circuit breaker opens and closes it is traveling at a very high velocity. It then
must slow down very quickly without damaging the interrupter. This is accomplished by
using a dashpot which absorbs some of the energy to slow down the interrupter towards
the end of its travel. Dashpots are commonly applied on the opening side of the
mechanism but there are several designs with it on the closing side as well.

 What is Dynamic Resistance Measurement (DRM) in regards to circuit breaker


testing?

Dynamic resistance measurements are basically making a micro ohm measurement


simultaneously while performing time and travel on a circuit breaker. From this
measurement you can evaluate the arcing contacts on an SF6 circuit breaker.
 What is the difference of Coupling Capacitors and Grading Capacitors on the
circuit breaker?

Coupling capacitors are used to reduce the rate of rise of breaker transient recovery
voltage, and to limit the overvoltage caused by a short distance fault on a low capacitive
line while the Grading capacitors are used to distribute the high voltage equally.

Those are connected in parallel to the interrupters, but usually coupling capacitors on
some dead tank circuit breakers and grading capacitors on live tank circuit breakers.

 What is the minimum reclose time allowed?

According to IEEE C37.04 1999, the minimum reclosing time of a circuit breaker is 0.3
seconds (300ms).

 What should I measure when performing circuit breaker testing?

The manufacturer should provide a list of the parameters and the range of values that
should be expected. It can vary by breaker design but if no list is provided, at a minimum,
the following should be measured:

i. Contact times
ii. Max contact time difference between phases
iii. Stroke
iv. Overtravel
v. Rebound
vi. Velocity
vii. Coil current
viii. Station voltage
ix. Contact Resistance
 What type of transducer is more accurate - rotary or linear type?

Neither type of transducer is inherently more accurate than the other. Depending on the
circuit breaker/mechanism design a rotary or a linear transducer might be more suitable
for the particular application. Each circuit breaker should be evaluated individually for
the best connection and the manual or manufacturer should be consulted for proper
connection.

 Where can I find out more information on circuit breakers and circuit breaker
testing?

For further reading, download our HVCB testing guide or view some of our technical
papers.

 Where should I mount my transducer?


You should look for an easily attachable place where your transducer will move in
conjunction with the interrupter(s). You should also try to mount the transducer to a solid
piece of metal that won’t vibrate during operation of the circuit breaker. The closer you
are to the interrupter without mechanical linkages in between, the more accurate your
travel trace will become. Once a transducer mounting spot is established, you should
continue to test it at this spot for accurate trending purposes.