Professional Documents
Culture Documents
2. Switchgear
4. Condition
Monitoring and
Maintenance
SF6 is widely used in high voltage gas circuit
breakers because of its high dielectric strength
and excellent arc interruption properties and
because it is non-toxic and recombines after
arcing. SF6 has a high global warming
potential, and while it is readily possible to
prevent SF 6 from being released to the
atmosphere when it is used in gas circuit
breakers, alternatives such as synthetic air or
CO2 have been proposed.
In 220 kV, 400 kV and 765 kV applications, the SF6 gas
pressure is maintained at 6.5 bar. You will be amazed that,
even though voltage level is increasing, same pressure of
SF6 i.e. 6.5 bar is used for 220, 400 and 765 kV applications
Combination of free
electrons with molecules
produces heavy and big
ions, which have
very low mobility. Because
of the absorption of free
electrons and low mobility
of ions SF6 has very
excellent dielectric property.
The dielectric strength of
SF6 gas is about 2.5 times
more than that of air.SF6
gas pressure is 14.2
kg/sq.cm
The pressure in a vacuum interrupter at the time of sealing off is
kept at about 10-6 torr. The moving contacts of the circuit
breaker are move through a distance of 5 to 10 mm depending
upon the operating voltage.
"Maximum
clearing time"
is the
total time from
the initiation of
the over current
to the breaker
being fully open
and the current
at zero.
In this situation the trip coil of the CB must not be energized to trip
the CB. So there must be NO contacts associated with gas
pressure and air pressure relays, connected in series with breaker
trip coil.
So if any of the intermediate contacts is detached, the
circuit breaker fails to trip. Not only that, if DC supply to
the trip circuit fails, the CB will not trip. To overcome this
abnormal situation, trip circuit supervision becomes
very necessary
The above scheme is for supervision while circuit
breaker is closed. This scheme is called post close
supervision. There is another supervision scheme which
is called pre and post close supervision.
This trip circuit supervision scheme is also quite simple.
The only difference is that here in this scheme, one NC
contact of same auxiliary switch is connected across the
auxiliary NO contact of the trip circuit. The auxiliary NO
contact is closed when CB is closed and auxiliary NC
contact is closed when CB is open and vice versa.
Thermal Test – Thermal tests are carried out to check the thermal behavior of the circuit
breakers. The breaker under test deal with the steady-state temperature rises due to the
flow of its rated current through its pole in a rated condition. The temperature rise for
rated current should not exceed 40° for current less than 800A normal current and 50°
for normal value of current 800A and above.
Dielectric Test – These tests are performed to check power frequency and impulse
voltage withstand capacity. Power frequency tests are kept on a new circuit breaker; the
test voltage changes with a circuit breaker rated voltage.
The test voltage with a frequency between 15-100Hz is applied as follows. (1) between
poles with circuit breaker closed (2) between pole and earth with circuit breaker open,
and (3) across terminals with circuit breaker open.
In impulse tests impulse voltage of specified magnitude is applied to the breaker. For
outdoor circuit dry and wet tests are conducted.
Short -Circuit Test – Circuit breakers are subjected to
sudden short-circuits in short-circuit test laboratories,
and oscillograms are taken to know the behavior of the
circuit breakers at the time of switching in, during contact
breaking and after the arc extinction.
The oscillograms are studied with particular reference to
the making and breaking currents, both symmetrical and
asymmetrical restriking voltages, and switchgear is
sometimes tested at rated conditions.
Pole Discrepancy Protection is an inherent feature of
Circuit Breaker which ensures that all the three poles of
Circuit Breaker is tripped / closed within a predefined
time period. If there is a mismatch of Breaker opening /
closing time then Pole Discrepancy Protection will
operate and will trip all the three poles of the Breaker.
On Line:
1, SF6 Gas Pressure
2.PDR
3.Trip Circuit Supervision
4.Spring Charge Indication (in case of spring charge
mechanism)
What is the necessity of monitoring CB
Timings?
What is meant by C,O, CO,OC, COC
and OCO Timings?
What are they for EHV CB?