BATTERY BANK CAPACITY TEST REPORT OF SV/IP STATIONS -GAIL KOCHI-MANGALORE (KKB

Work Bank Cells Healthy coditions

SL STATION MODEL RATING & MAKE MFG NO

NO OF CELLS
PER BANK
completed Healthy Below Remarks
Date condition 100% 80-100% 60-80% 40-60% 20-40% 20%

1SV-lM 1.2V KPL 850P BANK-1 AMCO SAFT MAKE,72 KPL 850AH Apr-19 72 19-09-2023 99% 72
2 SV-lM 1.2V KPL 850P BANK-2 AMCO SAFT MAKE,72 KPL 850AH Apr-19 72 21-09-2023 99% 71
3 SV-2M 1.2V KPL 850P BANK-1 AMCO SAFT MAKE,72 KPL 850AH Apr-19 72 23-09·2023 99% 70 2
4 SV-2M 1.2V KPL 850P BANK-2 AMCO SAFT MAKE,72 KPL 850AH Apr-19 72 23-09-2023 95% 62 5
5 SV-3M 1.2V KPL 850P BANK-1 AMCO SAFT MAKE,72 KPL 850AH Feb-19 72 23-09-2023 99% 72
6 SV-3M 1.2V KPL 850P BANK-2 AMCO SAFT MAKE,72 KPL 850AH Feb-19 72 20-09·2023 80% 12 58
7 SV-4M 1.2V KPL 850P BANK-1 AMCO SAFT MAKE, 72 KPL 850AH Feb-19 72 21-09-2023 99% 70 2
8 SV-4M 1.2V KPL 850P BANK-2 AMCO SAFT MAKE,72 KPL 850AH Feb-19 72 30-09-2023 96% 70 2
9 SV-5M 1.2V KPL 850P BANK-1 AMCO SAFT MAKE,72 KPL 850AH May-19 72 30-09-2023 99% 72
10 SV-5M 1.2V KPL 850P BANK-2 AMCO SAFT MAKE,72 KPL 850AH May-19 72 22-09-2023 99% 70 1

11 IP lM 1.2V KPL lOOP BANK-1 AMCO SAFT MAKE 265 KPL lOOAH Jul-18 265 03-10·2023 95% 259 2
12 IP·lM 1.2V KPL lOOP BANK-2 AMCO SAFT MAKE 265 KPL 100AH Jul-18 265 06-10-2023 99% 264 1

13 SV-6M 1.2V KPL 850P BANK-1 AMCO SAFT MAKE,72 KPL 850AH May-19 72 29-09-2023 98% 72

14 SV-6M 1.2V KPL 850P BANK-2 AMCO SAFT MAKE,72 KPL 850AH May-19 72 28-09-2023 90% 46 11 10

15 SV-7M 1.2V KPL 850P BANK-1 AMCO SAFT MAKE,72 KPL 850AH May-19 72 02-10-2023 100% 72

16 SV-7M 1.2V KPL 850P BANK-2 AMCO SAFT MAKE,72 KPL 850AH May-19 72 03-10-2023 99% 71 1

17 SV-8M 1.2V KPL 850P BANK·l AMCO SAFT MAKE,72 KPL 850AH Mar-19 72 11-10-2023 96% 72

18 SV-8M 1.2V KPL 850P BANK-2 AMCO SAFT MAKE,72 KPL 850AH Mar-19 72 10-10-2023 91% 18 54

19 SV-9M 1.2V KPL 850P BANK-1 AMCO SAFT MAKE,72 KPL 850AH Mar-19 72 06-09-2023 98% 67 5

Mar-19 Two cycle boost charging and

20 SV·9M 1.2V KPL 850P BANK-2 AMCO SAFT MAKE, 72 KPL 850AH 72 17-09-2023 75% 0 16 56

Electrolvte to be r

21 SV-lOM 1.2V KPL 850P BANK-1 HBL , 73 KPL 850AH Mar-19 73 20-08-2023 99% 73
22 SV-lOM 1.2V KPL 850P BANK-2 HBL ,73 KPL 850AH Mar-19 73 21-08-2023 99% 73
23 SV-11M 1.2V KPL 850P BANK-1 HBL ,73 KPL 850AH Mar-19 73 05-09-2023 96% 68 5
24 SV-11M 1.2V KPL 850P BANK-2 HBL ,73 KPL 850AH Mar-19 73 04-09-2023 98% 72 1
25 IP·02M 1.2V KPL lOOP BANK·l AMCO SAFT MAKE 265 KPL lOOAH Nov-18 265 09-09-2023 98% 242 21
26 IP-02M 1.2V KPL lOOP BANK-2 AMCO SAFT MAKE 265 KPL lOOAH Nov-18 265 14-09-2023 99% 244 20
27 SV-12M 1.2V KPt:-850P BANK-1 HBL ,73 KPL 850AH Mar-19 73 23-08-2023 90% 33 40
28 SV-12M 1.2V KPL 850P BANK-2 HBL ,73 KPL 850AH Mar-19 73 25-08-2023 99% 73
29 SV-13M 1.2V KPL 850P BANK-1 HBL ,73 KPL 850AH Mar-19 73 26-08-2023 98% 72 1
HBL ,73 KPL 850AH Mar-19 Two cycle boost c
30 SV-13M 1.2V KPL 850P BANK-2 73 27-08-2023 70% 0 0 72
' to be reolacement
31 SV-14M 1.2V KPL 850P BANK-1 HBL ,73 KPL 850M: Mar-19 73 01-09-2023 98% 67 5 1
32 SV-14M 1.2V KPL 850P BANK-2 HBL , 73 KPL 850AH Mar-19 73 03-09-2023 80% 0 21 49

33 SV-15M 1.2V KPL 850P BANK-1 HBL , 73 KPL 850AH ts Mar-19 73 21-08-2023 99% 73

34 SV-15M 1.2V KPL 850P BANK-2 HBL , 73 KPL 850AH ' Mar-19 73 23-08-2023 99% 73

0
p.. [\BL
'"-1 R.A ' "
35 IP-03 M 1.2V KPL OOP BANK-1 AMCO SAFT MAKE 265 KPL lOOAH Dec-18 265 10-09-2023

36 IP-03 M 1.2V KPL lOOP BANK-2 AMCO SAFT MAKE 265 KPL 100AH Dec-18 265 12-09-2023

37 SV-16M 1.2V KPL 850P BANK-1 HBL , 73 KPL850AH Mar-19 73 24-08-2023


38 SV-16M 1.2V KPL850P BANK-2 HBL , 73 KPL850AH Mar-19 73 26-08-2023
39 SV-17M 1.2V KPL 850P BANK-1 HBL , 73 KPL 850AH Mar-19 73 01-09-2023
40 SV-17M 1.2V KPL 850P BANK-2 HBL , 73 KPL 850AH Mar-19 73 02-09-2023
41 SV-18M 1.2V KPL 850P BANK-1 HBL ,73 KPL850AH Mar-19 73 03-09-2023
42 SV-18M 1.2V KPL850P BANK-2 HBL , 73 KPL850AH Mar-19 73 05-09-2023

06-09-2023
43 MCF-RT 1.2V KPL200P BANK-1 AMCO SAFT MAKE 253 KPL 205AH Dec-18 253
.

44 MCF-RT 1.2V KPL200P BANK-2 AMCO SAFT MAKE 253 KPL 205AH Dec-18 253 08-09-2023

.
RemarkAll stations Battery bank capacity test,cleaning and boost charging done.
Some stations weak cells found ( hylated colum) Below 60% capacity cells recommended to be replacement.
IP3 :- Battery bank two cycle boost charge and discharge conducted 1st cycle backup found 40% and 2nd cycle 70%,Recomended to be fres
SV13M :- Battery bank-2 two cycle charge and discharge conducted maximum improve 70% only,Recomended to be fresh electrolyte repla
All the stations Battery bank boost charging Recommended to be once in a 3 month 8 to 10Hsr for improving battery life.

()?
CHI-MANGALORE (KKBMPL)

99% 71 1 1cell to be replace


99% 70 2
95% 62 5 5 5 cell to be replace
99% 72
80% 12 58 2 2 cell to be replace
99% 70 2
96% 70 2
99% 72
99% 70 1 1 1cell to be replace

5% 259 2 z z 4 cell to be replace


99% 264 1

90% 46 11 10 5 5 cell to be replace

100% 72

99% 71 1

91% 18 54

98% 67 5

75% 0 16 56 discharge done maximum backup 75%

% 68 5
% 72 1
8% 242 21 1 1cell to be replace
99% 244 20
% 33 40

8% 72 1
Two cycle boost charging and
70% 0 0 72 1 discharge done maximum backup 70%

67 5 1
80% 0 21 49 3 3 cell to be replace
Two cycle boost charging and
70% 0 0 265 discharge done maximum backup 70%
Electrolvte to be reofacement
Two cycle boost charging and
70% 0 ·0 265 discharge done maximum backup 70%
Electrolvte to be reolacement
99% 73
98% 71 2
90% 0 68 5
95% 48 19 6
85% 0 56 17
90% 0 73
Weak cells Electrolyte replace and two
times revive!activity done 3 cell good
and 2 cell same condition to be replace 2
99% 242 6 5 cells

weak cells Electrolyte replace and two


cycle revival activity done all cells same
comdition , to be repace
99% 244 2 3 3 1 4 cells.

cycle 70%,Recomended to be fresh electrolyte replacemnet and boost charging.


ended to be fresh electrolyte replacemnet and boost charging.