ME150-2
QUIZ 4
ME150-2/C1
2019135731
SCHEMATIC DIAGRAM OF AIR DUCTS (LENGTH OF DUCT & CFM PER BRANCH)......2
i
STATEMENT OF THE PROBLEM
Supply air duct design using equal friction method:
1. Schematic diagram (initial) air ducts showing length of Duct & CFM per branch.
2. Selection of duct velocity and initial computation
3. Tabulation of air duct design; sections, cfm, duct area, duct sizes, etc.
4. Longest Run; tabulation & figure (section, length of duct, elbows, etc.)
5. Total external static pressure/losses in feet
6. Diffuser velocity selection and initial computation of diffuser sizes
7. Tabulation of quantity of diffuser sizes, velocity, cfm, etc.
8. Schematic diagram (final) air ducts showing dimensions of ducts & diffuser (with
rating).
1
1. SCHEMATIC DIAGRAM (INITIAL) AIR DUCTS SHOWING LENGTH OF DUCT
AND CFM PER BRANCH.
2
3
2. SELECTION OF DUCT VELOCITY AND INITIAL COMPUTATION
𝑇𝑜𝑡𝑎𝑙 𝐶𝐹𝑀 = 𝟖𝟒𝟖𝟎 𝒄𝒇𝒎, 𝐹𝑟𝑜𝑚 𝑇𝑎𝑏𝑙𝑒 7: 𝑖𝑛𝑖𝑡𝑖𝑎𝑙 𝑣𝑒𝑙𝑜𝑐𝑖𝑡𝑦 𝑜𝑓 𝟐𝟎𝟎𝟎 𝒇𝒑𝒎
8480 𝑐𝑓𝑚
𝑑𝑢𝑐𝑡 𝑎𝑟𝑒𝑎 = = 𝟒. 𝟐𝟒 𝒔𝒒 𝒇𝒕
2000 𝑓𝑝𝑚
4
3. TABULATION OF AIR DUCT DESIGN; SECTIONS, CFM, DUCT AREA, DUCT
SIZES, ETC.
Air CFM
Duct Area Area Duct Size
Duct Section Quantity Capacity
(%) (sq ft.) (in.)
(cfm) (%)
To A 8480 100 100 4.24 26 x 26
A to C 5300 63 70 2.97 22 x 22
C to D 4240 50 58 2.46 20 x 20
D to 7 2120 25 32.5 1.38 16 x 14
7 to 8 1590 19 26 1.10 14 x 12
8 to 9 1060 13 19.5 0.83 12 x 12
9 to 10 530 6 10.5 0.45 10 x 8
5
Table 13:
6
4. LONGEST RUN; TABULATION & FIGURE (SECTION, LENGTH OF DUCT,
ELBOWS, ETC.)
Duct Section Item Length (ft)
To A Duct 20
Duct 7
A to C
Elbow 12
Duct 12
C to D
Elbow 11
Duct 12
D to 7 Elbow 9
Duct 8
7 to 8 Duct 12
8 to 9 Duct 12
9 to 10 Duct 12
Total 127
7
5. TOTAL EXTERNAL STATIC PRESSURE/LOSSES IN FEET
From Chart 7:
8
6. DIFFUSER VELOCITY SELECTION AND INITIAL COMPUTATION OF
DIFFUSER SIZES
9
8. SCHEMATIC DIAGRAM (FINAL) AIR DUCTS SHOWING DIMENSIONS OF
DUCTS & DIFFUSER (WITH RATING).
10