Escalator Control System
Catalogue
3.1 SAFETY MONITOR BOARD ES.11/A EXTRINSIC FEATURE AND INSTALLATION DIMENSION ......................................... 11
3.2 SAFETY MONITOR BOARD ES.11/A PORT DEFINITION ............................................................................................... 12
3.3 MAIN ACCESSORY TYPE AND LOCATION ................................................................................................................... 14
3.3.1 Sensor type and location .................................................................................................................................. 14
3.3.2 Switch type and location ................................................................................................................................. 15
3.3.3 Switch power type ........................................................................................................................................... 16
6 TRANSFER BOARDSL305........................................................................................................................................ 25
-I-
8 PARAMETER INTRODUCTION ............................................................................................................................. 39
-II-
Escalator Control System
1 Function Introduction
Function(Standard) Function(Optional)
-1-
1.2 Function instruction
Standard function
1、Automatic run
When inspection/automatic input point is effective (switch closed), it is automatic mode. Under this mode,
switch the key and set escalator running direction. When the buzzer is ringing, release the key and the escalator
starts. Key switch is self reset type one.
2、Inspection run
When inspection/automatic input point is invalid (switch open), it is inspection mode. Point move running
can be controlled by inspection handle up and down running button.
Users can choose star-deltar mode or VVVF mode by parameters (detail in chapter 7).
4、Relaxation mode
It is divided into Relaxation low speed mode and relaxation stop mode. It can be set by parameter (detail in
chapter 8). If set the parameter 0, it is no relaxation. Other sets are as follows:
Star-delta mode: relaxation stop mode only, set parameter 2.
VVVF mode: if it is relaxation low speed mode, set parameter 1; relaxation stop mode 2.
It can record maximum 50 piece of fault code, happening date and time.
6、Maual stop
Turn the key to the direction opposite to running direction for 3s, the escalator will stop automaticly.Under
VVVF drive mode, it is soft stop and the sequence is the same as No.3 relaxation stop, which is relaxaztion low
speed before stop. Under star-delta drive mode, it stops directly.
7、Fault stop
The escalator will stop directly after detecting fault. All output points will be cut off (auxiliary brake cut
delay).
Under automatic operation, the system can oil by itself. Set oiling time and gap time by parameter (detail in
chapter 8). If power off in the middle run, the program will record running hour automaticly and continue to add it
when power on, deviation is within 1 hour.
-2-
扶梯控制系统
Running direction signal is output by relay and indicated by external pilot light.
10、Alarm bell
Under automatic condition, start key switch, the buzzer will ring. Under relaxation condition, the buzzer will
ring if people enter in the opposite direction. Ringing time can be set by parameter (detail in chapter 8). If safety
circuit is open, the buzzer rings.
Inspection starts, the buzzer rings, and ringing time can be set by parameter (detail in chapter 8).
11、Fire function
When motor thermal switch input is effective, the escalator will stop with fault, and it recovers automaticly
after switch input reset.
13、auxiliary brake
Normally, auxiliary brake delayed work to increase brake results after power off. If auxiliary brake is
installed, enable the function by setting Bit 0 of F12 as 1.
Inspection condition:
Down running: if auxiliary brake is not open, the escalator can up run first, and down run after opening.
Up run: open the auxiliary brake directly.
The opened auxiliary brake will not be closed after inspection.
Automatic comdition:
Turn around the key switch, and the auxiliary brake is open.
Down run: if auxiliary brake is not open, the escalator can up run first, and down run after opening.
Whether the auxiliary brake is open or not, the escalator will up run both, and then check the auxiliary brake
switch, the escalator will stop if the switch can’t be stopped in 3s. If it is failed after trying 3 times, reset it by
cutting power.
Relaxaztion escalator: the auxiliary brake will not be released. In normal stop, auxiliary brake delayed
release.
When water level input point is effective, the escalator will stop with fault report.
When oil level is too low, and oil detection input is effective, the controller output fault information to
remind user to oil. The escalator still can run. Automatic oiling become invalid if oil level is too low. It can
recover after switch input reset.
When brake abrasion switch input is effective, the escalator will stop with fault report. It can recover after
-3-
switch input reset.
1)Cut off the power of motor and brake before step speed reach 120% of nominal speed. Restart it after
manual reset.
2)Cut off the power of motor, brake and auxiliary brake before step speed reach 140% of nominal speed.
3)When reversion occurs, cut off the power of motor, brake and auxiliary brake. Restart it after manual reset.
a)Signals of speed monitoring sensor A and B are in opposite directions, that is the escalator being reversal;
b)In normal running, the speed will decrease from rated relaxation speed to 1/3 relaxation speed, which is
2)reversion
Check whether the status of auxiliary brake switch and contactor is correct (check whether the auxiliary
brake is in normal operation). If it is not in normal run, cut off the power of motor and working brake to prevent
escalator restarting.
Cut off the power of motor, brake and auxiliary brake after detecting the disconnect drive chain, and restart it
after manual reset.
If missing step or tread is detected, cut off power of motor and working brake, and restart it after manual
reset.
When running contactor is closed, the normal closed point of working brake detecting switch should be
disconnect, normal open be closed.
When running contactor is disconnect, the normal closed point of working brake detecting switch should be
closed, normal open be disconnect.
If the real condition is not the same as required status when the escalator or moving walkway starts, cut off
the power of motor and working brake, restart it after manual reset.
-4-
扶梯控制系统
When the handrail speed is 15% over the step speed lasting 15s, cut off the power of motor and working
brake.
Make sure whether escalator or moving walkway is in inspection or automate by condition of inspection
switch. The cover can be opened normally in inspection condition; once the cover is opened in normal condition,
cut off the power of motor and working brake.
When then actual brake distance is 1.2 time of the allowed maximum distance, keep the escalator stop and
restart it after manual reset.
25、Linkage function
Linkage function can be realized by setting escalator location through parameter (detail in chapter 8). Set
escalator location by parameter after the function is actived to realize the linkage function (detail in chapter 8). Up
running escalators can run up under any condition; down running escalators can run down at any time. In other
condtion, if running direction is up and the escalator of exit direction is stop, then the escalator stop immediately.
In static condition, if escalator of exit direction is stop, try to start for 2mins, if it doesn’t run, stop the escalator.
26、Dynamic password
1)Main board running time CN and the instant time of operator can be monitored in the interface of
monitoring status. The data should be input in special machine and work out dynamic password SP, using SP
restart the operator can provide superauthority.
2)dynamic password is effective in half an hour, users can repeat login with the same password in half an
hour.
4)Escalator running times can not be reset. Reset can only be done by sending the main board to the factory
Optional function
It can display escalator status and fault information related to main controller and safety monitor board; 8*8
space lattice display escalator status and fault code.
If fault points of safety circuit are needed, please choose ES.02/G.
Using STEP software with added monitor board OT.EM/A, monitoring the detailed status of escalator by PC.
3、Voice announcement
-5-
Add voice announcement device OT.VA/C, connecting CAN wiring with main boardcan realize voice
announcement.
-6-
Escalator Control System
Main control board SL3000 has 21 routes of low voltage input, 2 routes of high voltageinput, 11 routes of
relay output, 3 routes of transistor input, 2 routes of CAN ports (one for connecting fault collecting board,
display board and voice announcement device), 1 route RS232 port (the other for connecting hand held operator).
See 2.1
Hand held
24VDC operator port
Power
port ?
High voltage
input
Relay output
Transistor output
2.1.2Main control board installation cover dimension
-7-
160,5
38,8 82,9 38,8
5,1
JP5 47,8
DB1
1
主控制板
1
22,4
6
145,5
114,8
134,5
125
31,8
9
5
4
9,7
14,2
45,2
136,9
1 JP6 4 1 10 1 JP8 6
3,9 4-Φ3.6*11.6
148,8
156,6
-8-
Escalator control system
CANH 和 CANL
JP4
Need twisted-pair
JP4.3 CANL CANL
Note: terminal
resistance is already
fixed in main board,
dial is not needed.
JP5.1 Power 24VDC Power 24VDC
Switch power
JP5 JP5.2 Power 24VDC Power 24VDC
24VDC input
JP5.3 Power 0V Power 0V
-9-
JP5.4 Power 0V Power 0V
JP6.1 HX0 Safety circuit high voltage 1 Safety circuit high voltage 1 110VAC/220VAC
JP6.2 COM1 HX0 common port HX0 common port High voltage input
JP6.3 HX1 Safety circuit high voltage 2 Safety circuit high voltage 2 High voltage detection
JP6
2 is the redundancy
JP6.4 COM2 HX1 common port HX1 common port check of high voltage
detection1
JP7.1 Y0 Backup Running contactor1
JP7.2 Y1 Backup Running contactor2
JP7.3 Y2 Brake contactor Brake contactor
JP7.4 Y3 Auxiliary brake contactor Auxiliary brake contactor
JP7.5 COM3 Y0~Y3 common port Y0~Y3 common port
JP7
JP7.6 Y4 Backup Backup
JP7.7 Y5 Backup Backup
JP7.8 COM4 Y4~Y5 common port Y4~Y5 common port
JP7.9 Y6 Automatic oiling Automatic oiling
JP7.10 COM5 Y6 common port Y6 common port
JP8.1 Y7 Up run contactor Up run signal output
JP8.2 Y8 Down run contactor Down run signal output
JP8.3 Y9 Star contactor Inverter multi speed output 1
JP8
JP8.4 Y10 Delta contactor Inverter multi speed output 2
JP8.5 Y11 Backup Inverter running enable output
JP8.6 COM6 Y7~Y11 common port Y7~Y11 common port
JP9.1 Y12 Inspection signal output Inspection signal output
Transistor output
JP9.2 Y13 Up run signal output Up run signal output
JP9 provide safety board
JP9.3 Y14 Down run signal output Down run signal output
withES.11/A
JP9.4 COM7 Y12~Y14 common port Y12~Y14 common port
JP10.1 CANH CANH Monitor port
JP10.2 CANL CANL CANH and CANL are
twisted-pair
JP10 Note: terminal
JP10.3 GND GND resistance is already
fixed in main board,
dial is not needed.
DB1 Hand held operator port Hand held operator port
-10-
Escalator Control System
《FSCS functional monitoring system user manual》). Please comply with the GB16899-2011 new standard
design.
ES.11/A includes 19 routes of low voltage input point, 4 routes of safety relay ouput, 5 routes of signal relay
output, 4 routes of transistor output, 1 route of RS232 hand held operator port, 1 onboard reset button.
ES.11/A extrinsic feature is as drawing 3-1 shows. Proetection level of controller should be at leastIP5X with
non-cover installation. See drawing 3.1, 3.2
- 11 -
3.2 Safety monitor board ES.11/A port definition
-12-
Escalator control system
JP5.1 Optocoupler24V
JP5 JP5.2 Optocoupler0V
JP5.3 Common port
Safety condition relay 3
-13-
1、Pulse output indicates normal operating
stop)
inspection condition
Note 1:Control board is configured with operator port, users can set parameters and check fault information by hand held
operator.
Note 2:Control board is configured with fault reset button for fault reset manually (same function with input point X17).
Note 3: Open down machine room cover to detection input (X10、X18), suit for machine room cover wired with safety monitor
system. Use sensor or limit switch for detection. In order to finish self-inspection, these two detection point must be wired to
tadem signals of up cover and down cover, that is 1st up cover detection board (or sensor) to X10 detection point after 1st
down cover detection switch (or sensor); 2nd up cover detection board (or sensor) to X18 detection point after 2nd down
cover detection switch (or sensor).
Note 4: Speed optional switch input X9 is only used with 2 rated speed.
Main accessories used with ES.11/A includes: sensors for main drive wheel speed detection, handrail speed
detection, step missing detection, brake switch, auxiliary brake switch, inspection cover detection switch and
switch power. Details of types and locations are as drawing 3-2 and 3-4.
NBN8-12GM50-E0-V1
P+F 2PC
(NBN8-12GM50-E0)
DW-AS-631-M12
Main drive KERUI 2PC
(DW-AD-631-M12)
wheel speed Main drive 4 kinds of sensor brand
sensor BI4U-M12-AN6X-H1141 wheel side for option
TURCK 2PC
(BI4U-M12-AN6X)
XS218BLNAM12C
Schneider 2PC
(XS218BLNAL2C)
NBN4-12GM40-E0-V1
P+F 2PC
(NBN4-12GM40-E0)
DW-AS-631-M12-120
KERUI 2PC
(DW-AD-631-M12-120)
Handrail speed Handrail 4 kinds of sensor brand
sensor Ni4-M12-AN6X-H1141 wheel side for option
TURCK 2PC
(Ni4-M12-AN6X)
XS212BLNAM12C
Schneider 2PC
(XS212BLNAL2C)
NBN40-L2-E0-V1
P+F 2PC
(GLV18-55/25/102/115)
DW-AS-611-M30-002
Step missing KERUI 2PC
(DW-AD-611-M30-002) Step return 4 kinds of sensor brand
detection
station side for option
sensor Ni50U-QV40-AN6X2-H11
TURCK 2PC
41
XS230BLNAM12C
Schneider 2PC
(XS230BLNAL2C)
表 3.3 开关信号及安装位置
-15-
Schmersal TS 236-02Z 2PC
Brake detection switch Main brake side 2 optional type
Schmersal TS 236-11Z 2PC
auxiliary brake Schmersal TS 236-02Z 1PC Auxiliary brake
2 optional type
detection switch Schmersal TS 236-11Z 1PC side
Cover board detection
Schmersal Z1R236-11Z 4PC Machine cover
switch
Note: please contact us to get information of new added sensor, switch and power and type of switch.
-16-
Escalator Control System
- 17 -
图 4.1 fault collecting board physical picture
4.2 Dimension
8
1 1 1 HCOM
90,4
67,7
故障采集板
145,5
134,5
114,8
125
17,3
1
JP7
88,9
1
8
3,9 4-Φ3.6*11.6
59
100,5
108,4
112,5
-18-
Escalator control system
-19-
Both switch to
SW1 CAN terminal set CAN terminal set “ON”, terminal
resistance is valid.
Location set
Location set
SW2.1 switch to “ON”,
SW2.1 switch to “OFF”,
SW2
SW2.2 switch to “OFF”, up SW2.2 switch to “ON”,
down part.
part.
-20-
Escalator Control System
vvv
picture5.2 Entrance display board installation dimension
- 21 -
Display board installed in up exit: SW2.1 switch to ON、SW2.2 switch to
OFF;
switch to ON.
Refer to above 4 pictures when in all kinds of condtions. Introduction of entrance displaying is as follows:
Fault condition:Up and down entrances show as picture 4(fault code 01)。
Normal down run condition:Up and down entrances show rollingly as picture 2
-23-
Escalator Control System
6 Transfer boardSL305
Picture 6.1 transfer board SL305 extrinsic feature 6.2 transfer board SL305 installation dimension
- 25 -
Tag Up collecting board
Terminal No. Remarks
number function
JP1.1 Power 24V
Power input
JP1.2 Power 0V
JP1
JP1.3 CANH
Twisted-pair
JP1.4 CANL
JP2.1 INPORT0
JP2.2 INPORT1
JP2.3 INPORT2
JP2.4 INPORT3 5 routes opto-coupler
JP2
JP2.5 INPORT4 input
JP2.6 VISO+
JP2.7 VISO-
JP2.8 VISO-
JP3.1 TXDA
JP3.2 TXDB
JP3
JP3.3 Power 0V 422 port
JP3.4 RXDA
JP3.5 RXDB
As a transfer board of communication protocol, SL05 transforms 422 and CAN correspondence, 5 routes of
optocoupler input are reserved.
-26-
Escalator control system
Hand held operator is specialized in escalator control system debugging, the extrinsic feature is as follows,
and the button function is detailed in table 7.1.
-27-
Table 7.1 function of operator key
Key Function
-28-
Escalator control system
Press , , can adjust resolution ratio of LCD screen. Users can adjust
screento suitable contrast ratio. The firtst line is resolution ratio of LCD screen。
Login interface
Escalator status display Press F1 can go back to the interface if there is no fault check, contents include:
Escalator status(automatic/inspection/fault etc.)
Escalator running status (up/down/stop etc.)
Time
Note: this is the initial status if no special instruction.
Function option
Users can choose follow functions: monitoring, parameter setting, reset command, time
setting, password revising, re-login etc. part of the functions have submenus.
Password login is as table 7.3 shows after operator is conntected and powered (take initial password 1234 as
an example).
-29-
1 Eenter Go to login interface
2
Press 4
times
4
Press 3
times
6
Press 2
times
Lift status
Enter ESC
Monitor
Input type
Para.type
Input &
Para. F
Reset
Error record
Reset Lift Pa.
Add. Func.
中文选择
Version
Time setup
Relogin
Fire Mode
Chg. Pwd
Reset Errcode
——
—— Reset Lift
——
This chapter is mainly about referring common menu items and revising parameters.
-31-
Table 7.4 fault record view
sequen
Key Operator status introduction
ce
- Status display
and to go up and
5
down
Note:
For other functions of monitoring, please follow the above table. Using and for check.
7.4.2.2Parameter setup
-32-
Escalator control system
6 Down to F1 parameter
Take set X10 input type from normal open to normal close as an example.
-33-
2 Parameter set selection
输入类型
4 Eenter
F16 = 64
输入类型X0-15
按 10 次
Note: under input type menu, ON is normal close, OFF is normal open.
按2次
-34-
Escalator control system
3 Eenter
2
Press 4
times
3 Eenter
4 Eenter
Press 2
-35-
times
6
Press 9
times
时间设定
8 06年10月10日
Press 6 5
15:20:30
times
9 Eenter
For users convenience, we adopt , , (F1, F2, F3)three shortcut keys, which lead to fault
code check, status monitor main interface, version check interface.
In any interface, enter fault refer page fastly by F1, as table 7.9 shows.
-36-
Escalator control system
In any interface, enter input and output monitor interface fastly by F2, as table 7.10 shows.
7.5.3 Shortcut F3
In any interface, enter program version interface fastly by F3, as table 7.11 shows.
-37-
Escalator Control System
8 Parameter introduction
- 39 -
Bit0:auxiliary brake
Bit2:oiling mode
Bit5:linkage function
F25 X21input re-definition 21 0~37 Set F25 as i,then X21 replaces the X i
-40-
Escalator control system
Error
!
Hype
rlink
Voice announcement exit How long will the exit will report
F29 15 1-100 refer
delay after entrance reporting.
ence
is
invali
d 1s
0:no relaxation mode 1:relaxation mode is slow speed relaxation 2:relaxation mode is slow speed
0:no
2:yes, once receive fire signal, enter down running dispersion mode.
F3——same direction turn to relaxation slow speed time t1. t1 range is 100~10000, unit is 0.1s, that is 10s~
1000s, users can also keep the key not released in normal up running, make one person take the escalator from
down exit to up exit, then release the key, the time will +10s.
F4——opposite direction turn to relaxation slow speed time t2. t2 range is 1~10000,unit is 0.1s, that is
0.1s~1000s.
F5——relaxation slow speed turn to relaxation stop time t3. t3 range is 1~600, unit is 0.1s, that is 0.1s~60s.
If anyone neither enters in same direction in t1 time, nor the opposite direction in t2 time, the escalator will
turn into relaxation slow speed mode first, then to t3, turn into relaxation stop mode for inverter mode. If enter
relaxation stop mode directly, set t3 as minimum one; for star-delta drive, there is no relaxation slow speed mode,
the escalator turns into relaxation stop directly after passing t1(t2)+t3 time.
F6——common auxiliary brake release time. Normal stop: auxiliary brake release delay time.
F7——expension board set. If there is no expension board: 0; if first expension board is valid: Bit 0 is 1; if
-41-
sencondexpension board is valid: Bit1 is 1; if third expension board is valid: Bit 2 is 1.
F8——star-delta switch time. Star type wring enabled. After that time it turns into deta wiring.
F11——enter opposite direction to alarm time. Passengers enter in opposite direction, the buzzer reminds time.
F12——function enable
Bit2 0:keep oiling in F15 setting time 1:pulse oiling in F15 setting time
Bit3 0:X20 is valid as safety circuit high voltage detection point 1:X20 is backup point
Bit6 0:not detection safety board short circuit status 1:detection safety board short circuit status
Input point X0~X19、F used for main board setting, input type of first expension board input point X22~X31
(print X0~X9 in board)and second expension board input point X32~X41(print X0~X9 in board).
These three parameters are 16 bit data. For example, F16: lowest bit is X0, highest bit is X15. When one of the
points is normal open contact, the response bit is 0; normal close contact is 1. In actual operation, parameter
setting is one by one, so it is no need to calculate the data value.
-42-
Escalator control system
Input type of setting up fault collecting board input point TX0~TX13 and down fault collecting board input point
TX16~TX29.
F21——single oiling actuation time. When in pluse oiling mode, single period oiling relay actuation time.
F22——single oiling release time. When in pluse oiling mode, single period oiling relay actuation time.
Note: up fault collecting board input point is from TX 0, down from TX16.
(400*1.5=600)
-43-
F12 Low speed protection 0 0~5 s
Set as stop(includes
delay
relaxation stop)speed is
F2——rated speed 1 of escalator. The range is 1~2000, unit is 0.001m/s, that is 0.001m/s~2m/s.
F3——rated speed 2. Some projects require two escalator running speeds (switch by outside switch). Forexample,
the rated speed is 0.6m/s, and it is required to run at 0.5m/s. This value is used to set the second speed of
F4——inspect rated speed, that is inspection speed. Range is 1~2000, unit is 0.001m/s, that is 0.001m/s~2m/s.
F5——relaxation slow speed time. That is speed entering relaxation slow speed status only for escalators with
relaxation slow speed.
F6——pulse per circle. That is pulse number input from each speed sensor when main drive wheel turns one
circle. It is gear number of main drive wheel.
F7——running distance per circle. That is escalator running distance when main drive wheel turns one
F8——step has no pulse distance, that is the running distance between two step signals. This is the reference
value to judge step missing. Range is 1~2000, unit is 0.001m, that is 0.001m~2m. Normally, set the value as 1.5
F10——pulse number of handrail wheel. That is pulse number input from each speed sensor when main drive
wheel turns one circle.
F11——speed detection delay.
F12——slow speed protection delay.
-44-
Escalator control system
In addition to rated uniform speed, escalator has 0 speed to full speed, full speed to relaxation speed,
relaxation slow speed to stop of acceleration and deceleration progress (as the T1,T2,T3 shows). During the speed
changing, it can not be detectioned by uniform speed measures, in case to trigger the under speed fault. Set
transmission section time by F11, do not trigger under speed protection, and take the maximum value in T1, T2,
T3.
When escalator is in soft stop, stop time is relatively long. Under this condition, the reversal protection may
be triggered (one of the judge terms of reverse is the speed drop from rated speed to under 1/3 relaxation speed
when the escalator is in normal running). So set delay time between 1/3 relaxation speed to stop, during this time
(time period response to T4), reversal protection will not happen.
-45-
9 Fault instruction
1 KPH
相序
2 SAU
上控制箱急停
3 SBU
上部钥匙开关急停
4 SBU2
人行道上出入口急停
5 SASP-UR
上右围裙板开关
6 SACP-UR
上右梳齿板开关
7 SAHR-UR
上右出入口开关
8 SADRR
右驱动连断链开关
9 SADRL
左驱动连断链开关
10 SAHR-UL
上左出入口开关
11 SACP-UL
上左梳齿板开关
12 SASP-UL
上左围裙板开关
13 SADD-U
上梯级下陷开关
14 SASU-U
上梯级上跳开关
15 SBYS/SBZ
保养锁开关
Escalator control system
17 SBD
下部钥匙开关急停
18 SBD2
人行道下出入口急停
19 SASP-DR
下右围裙板开关
20 SACP-DR
下右梳齿板开关
21 SAHR-DR
下右出入口开关
22 SACR-DR
下右曳引链开关
23 SACR-DL
下左曳引链开关
24 SAHR-DL
下左出入口开关
25 SACP-DL
下左梳齿板开关
26 SASP-DL
下左围裙板开关
27 SADD-D
下梯级下陷开关
28 SASU-D
下梯级上跳开关
32
33
34
抱闸开关故障 Brake Switch Err
35
安全触点故障 Safe Relay Err
36
附加制动开关故障 Aux Switch Err
37
附加接触器故障 Aux Relay Err
38
温度故障 Temp. Err
39
40
Fault code Chinese Fault details English Fault details
41
42
油位检测故障 Oil Low
43
星角上行故障 S/T UpRelayAdh.
44
星角下行故障 S/T DnRelayAdh.
45
46
47
模式异常切换 Mode Tran Err
48
星角接触器粘连 S/T Relay Adh.
49
变频器故障 Inverter Err
50
上盖板被盗 Top Cover Stolen
51
下盖板被盗 Bot Cover Stolen
52
机械磨损 Mech. wear
53
水位故障 Water Err
54
故障采集板无通讯 ES02G No Commu.
55
安全板短接 ES11A Short
56
联动运行故障 Linkage Err.
57
转换板与 PLC 无通讯 PLC Link Err
62
冗余检测错误 Uart Comm. Err
63
参数 CRC 错误 Para Crc Err
64
故障 CRC 错误 Fault Crc Err
65
参数不合适 Para not Approp.
Escalator control system
67
安全板继电器故障 Safety Relay Err
68
超速超过 120% Over Speed 120%
69
超速超过 140% Over Speed 140%
70
欠速低于 80% Low Speed 80%
71
AB 相反接 Direction Err
72
速度异常降低 Speed Reduce Abn
73
驱动链断开 Safety Dcs Err
74
停车制动距离过大 Braking Dis Over
75
附加制动器故障 Aux Err
76
上梯级缺失 Up Step Lost
77
下梯级缺失 Down Step Lost
78
检修盖板缺失 Insp. Cover Lost
79
检修盖板开关故障 Insp. Cover Err
80
工作制动器粘连 Brake Adhesions
81
工作制动器不吸合 Brake not work
82
左扶手带欠速 L Handrail Slow
83
左扶手带超速 L Handrail Fast
84
右扶手带欠速 R Handrail Slow
85
右扶手带超速 R Handrail Fast
86
上下和运行不一致 Up Dn Run incons
Fault code Chinese Fault details English Fault details
87
停梯时刻溜车 Sliding Protect
88
2 个通道 IO 不一致 2 Channel incons
89
AB 相缺相 AB Phase Lost
12 Speed unusually drops Speed drops to under 1/3 of relaxation speed in normal running.
14 Stop distance is too long Stop distance is 1.2 times of maximum brake distance.
15 Auxiliary brake fault Auxiliary brake contactor disaccords to auxiliary brake switch action
16 Upper step missing Upper step missing sensor detects step missing
17 Down step missing Upper step missing sensor detects step missing
18 Inspection cover missing Inspection cover is detected open in normal running (not inspection)
20 Working brake adjoin Brake contactor is released, but brake switch is not released.
21 Working brake not actuation Brake contactor acts, but brake switch doesn’t acts.
26 Up and down running disaccord Escalator has running signals without up and down signal, or on the contrary.
10 Tuning instructions