KYF Escalator Controlling System Function
1 Automatic Through the upper and down start (1)Turn the inspection/auto switch
Operation switch of the skirting, start escalator to auto position.
operation. (2)Upper and down decking are
closed.
(3)Upper and down inspection
plug (XSU, XSD) is closed.
Inspection switch (SAJU,SAJD) is
“OFF”
2 Inspection Through the upper and down (1)Turn the inspection/auto switch
operation direction operation button on the to Inspection position.
inspection box, inspection operation (2)Upper and down decking are
can be done. closed.
(3)Upper and down inspection
plug (XSU, XSD) is closed.
Inspection switch (SAJU,SAJD) is
“ON”
6 Fault stopping When fault happens, escalator will Display panel on the escalator
operation stop operating. show fault code
7 function Escalator will stop operating when Escalator wills emergency brake
Emergency emergency brake. when safety circuit is cut off or
brake function emergency brake button is pushed.
1 Main power When main power phase faults Relative fault code is E09
phase happen, phase relay KA1 activate,
monitor(KA1) safety loop cuts off and escalator
stops operating
4 Upper, down System auto inspect upper, down Relative fault code is E02
contactor fault contactor, when inspecting that wire
protection loop is cut off or connector links,
(KMU, KMD) safety circuit cuts off, escalator
stops operating
5 Star, delta System auto inspect star, delta Relative fault code is E03, E04
operating operating contactor, when inspect
contactor fault that wire loop cuts off or connector
protection links, safety circuit cuts off and
(KMX、KMS) escalator stops operating
7 Brake contactor System auto inspect brake contactor. Relative fault code is E01
fault protection When inspecting that wire loop
(KMB) cuts off or contactor links, safety
circuit cuts off and escalator stops
operating
9 Main drive When main drive chain breaks Relative fault code is E10
chain protection or over elongations during the
switch (SP1L、 operation, system inspect that drive
SP1R) chain protection switch is “OFF”,
safety circuit will cut off and
escalator stops
10 Step chain When step chain breaks or extends Relative fault code is E10
protection during the operation, system
switch (SP2L、 inspects that step chain protection
SP2R) switch is “OFF”, safety circuit will
cut off and escalator stops operating.
11 Step sagging Sagging will result in meshing of Relative fault code is E11, E18
protection entrance and comb not assuring
switch (SP3U、 the requested gap. Then, system
SP3D) inspects that step sagging protection
switch is “OFF”, safety loop will
cut off and escalator stops operating
12 Upper handrail During the operation of escalator, Relative fault code is E12, E13
entrance some bodies are stuck in the
protection entrance of upper deflecting end;
switch (SP4L、 the safety switch will be “OFF”.
SP4R) The safety circuit will cut off and
escalator stops operating.
13 Down handrail During the operation of escalator, Relative fault code is E19, E20
entrance some bodies are stuck in the
protection entrance of down deflecting end; the
switch (SP5L、 safety switch will be “OFF”. The
SP5R) safety loop will cut off and escalator
stops operating
16 Upper skirting During the operation of escalator, Relative fault code is E16, E17
protection some bodies are stuck in the front
switch (SP8L、 edge of upper skirting board and
SP8R) step and upper skirting protection
switch will be “OFF”. Safety loop
will cut off and escalator stops
operating.
17 Down skirting During the operation of escalator, Relative fault code is E23, E24
protection some bodies are stuck in the front
switch (SP9L、 edge of down skirting board and
SP9R) step and down skirting protection
switch will be “OFF”. Safety loop
will cut off and escalator stops
operating.
18 Traction speed During the operation of escalator, Relative fault code is E06
monitoring main controller of controlling
switch (SE1L、 system inspects traction running
SE1R) speed all the time. When running
speed≤80%or≥120%, main
controller send stop order and
escalator stops operating.
19 Handrail During the operation of escalator, Relative fault code is E07, E08
under speed main controller of controlling
protection system inspects handrail running
switch (SE2L、 speed all the time. When handrail
SE2R) running speed≤80%, main controller
send stop order and escalator stops
operating.
20 Auxiliary brake Auxiliary brake is needed to add Relative fault code is E25
protection when rise height≥6m to assure that
safe brake of escalator
1 Motor speed Motor speed monitor function When escalator stops by fault,
monitor the relative fault code is E06. In
function parameter setting, set whether
motor speed monitor function is
on or not
2 Left handrail Left handrail under speed monitor When escalator stops by fault,
under speed function the relative fault code is E07. In
monitor the parameter setting, set whether
function left handrail under speed monitor
function is on or not.
3 Right handrail Right handrail under speed monitor When escalator stops by fault,
under speed function the relative fault code is E08. In
monitor the parameter setting, set whether
function right handrail under speed monitor
function is on or not
4 Auto start Auto start by photocell sensors In the parameter setting, set
by photocell function whether auto start by photocell
sensors sensors function is on or not. If
function this function is setting on, it will
start with the escalator starting.
1 Fire-control linked
function
2 Auto-spray
function
3 Auto pre-heating
function
4 Handrail lighting
5 Comb lighting
6 Water height
inspection
7 Automatic bailing
function
9 Remote control
start, stop function
10 Smoke alarm
11 Traffic light
J202 J202_2 IN20 T2040 Upper right handrail entrance switch (SP4R) input
J202_3 IN21 T2042 Upper right gear switch (SP6L) input
J202_4 IN22 T2044 Upper right gear switch (SP6R) input
● :System date. It helps to set time exact to the year, month and day. It can save
time record by battery when electricity breaks off. If battery is not used or doesn’t work, escalator
works as normal, but affect error historical record.
● :System time. It helps to set time exact to the hour and minute. It can save
time record by battery when electricity breaks off. If battery is not used or doesn’t work, escalator
works as normal, but affect error historical record.
● :It helps to set the options, for instance, the work type, VVVF or Star-delta,
photocell start, master computer speed inspection, handrail speed inspection, step missing, reversal
protection, brake wearing protection etc.
● :Parameter: It helps to set the upper/down limit of master computer speed and
of handrail speed, cycle of each step signals, and other parameters.
● :Error history: It helps to check the exact time when the errors occur and it can
save as much as 1000pcs of error historical record.
Push Enter, into setting menu, then push Shift, into setting menu display circularly and then
push Esc into setting escape.
→ → Esc
3.1.1 RS485 address of communication slave
The address of the slave can be chosen between 1 and 32. Two escalators can’t share the same
address when many escalators under monitoring.
→ Enter → → → Shift→ Esc
3.1.2 RS485 Communication baud rate
The baud rate of the slave can be chosen from 9600, 4800, 2400 and 1200.
→ Enter → → → → Shift → Esc
Enter → → → Esc
3.2.1 System date-year
System year can be added from the year 2008.
→ Enter → → → Shift → Esc
Enter → → → Esc
3.3.1 System time -hour
System hour can be chosen between 0 and 23.
→ Enter → → → Shift → Esc
→ Enter → → → Enter → → →
→ Enter → → → Enter → → →
→ Enter → → → Enter → → →
→ Enter → → → Esc
3.4.1 Common/VVVF
On: star-delta OFF: VVVF
→ Enter → → → Shift → Esc
3.4.10 Escalator low-speed operation with none on by photocell start (only for VVVF
escalator)
On:Low-speed operation with none on the escalator under photocell start
OFF:Stop operation with none on the escalator under photocell start
→ Enter → → → Enter → → →
→ Enter → → → Enter → → →
→ Enter → → → Esc
3.5.1 Low limit of motor speed
Low limit of motor speed can be chosen between 5 and 30, which means the number of pulses
sent by motor speed sensor in 5 seconds.
→ Enter → → → Shift → Esc
3.5.8 No person on escalator time when there is auto-start by phone cell function
The auto-start by phone cell function is setting on; the escalator will stop or run with lower
speed (inventor escalator). No person on escalator time can be chosen during 10-60 and the unit is 1
second.
→ Enter → → → Shift → Esc
The above shows there are five pcs of history records and error occurred at 15:22 on Feb.19,
2008. The first piece is the latest error.
ON
OFF main contactor
ON
OFF operating contactor
ON
OFF upper contactor
ON
OFF down contactor
ON
OFF start contactor
ON
OFF triangle contactor
ON
OFF bracke contactor
Fig 4-1 Time sequence of all contactors under the working type of star-delta
Fault
Definition Solving method
code
KMC wire loop cut off or contactor inspect KMC contactor parts and connector, check
E00
accretion decking switch input
Brake contactor (KMB) wire loop cut Inspect KMB contactor and connector, change if
E01
off or contactor accretion damaged
1. KMY wire loop cut off or contactor 1. Inspect KMY contacting parts and connector,
accretion(VVVF) change if damaged
E02
2. KMU,KMD wire loop cut off or 2. Check KMU,KMD contacting parts and
contactor accretion (star-delta) connector, change if damaged
1. KMYR wire loop cut off or contactor 1. Check KMYR contacting parts and connector,
accretion(VVVF) change if damaged
E03
2. KMSL,KMXL wire loop cut off or 2. Check KMSL, KMXL contacting parts and
contactor accretion(star-delta) connector, change if damaged
1. frequency-converter fault 1. check frequency converter
E04 2. KMSR,KMXR wire loop cut off or 2. Check KMSR, KMXR contacting parts and
contactor accretion(star-delta) connector, change if damaged
check input circuit and parts (SPBL、SPBR、
E05 Motor brake unopened
SPJB), change if damaged
Check motor speed measuring parts and motor
E06 Traction speed inspection fault
operating status, change if damaged
Check left handrail speed measuring parts and
E07 Left handrail under speed mal-function
motor operating status, change if damaged
Check right handrail speed measuring parts and
E08 Right handrail under speed mal-function
motor operating status, change if damaged
Check power connector and contactor KA1 parts,
E09 Main power circuit fault
change if damaged
E10 step chain fault Check step chain parts, change if damaged
E11 Upper step sagging fault Check upper step parts, change if damaged
Check upper handrail left entrance protection
E12 Upper handrail left entrance fault
switch parts, change if damaged
Check upper handrail right entrance protection
E13 Upper handrail right entrance fault
switch parts, change if damaged
Special Notice