You are on page 1of 1

FROM LOCAL ELECTRICITY BROAD

DETAILS OF TRANSFORMER

TRAFO - 1
RATING 100kVA, 11KV/433V
WITH OFF CIRCUIT TAP CHANGER
COOLING ONAN AS PER IS1180
VECT. GROUP Dyn 11
HIGH VOLTAGE +5% 11000 -10%
LOW VOLTAGE 433 IN 7 STEPS
INSULATION LVL. HV 28 KV EACH 2.5%
LV 3 KV
WINDING MATERIAL COPPER

METERING CUBICLE DG 125 KVA

FROM
METERING CUBICLE

EB DL: 50 kW
EB CL: 80 kW FROM
MAIN LT PANEL MAIN LT PANEL

EB DL: 15 kW
EB CL: -- kW
PUMP PANEL

FROM MAIN LT PANEL FROM MAIN LT PANEL

TWIN ROOM DB 12 WAY SPN DB 8 WAY SPN DB SINGLE ROOM DB


TYPICAL TYPICAL
RCBO 25A
30mA DP
DP 30mA
25A RCBO

1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6

T
63A,415V,50HZ,16KA TPN+E AL.BUS BAR
CURRENT
DENSITY-
0.8A/Sq mm
25A,
TPN 25A, DP
MCB MCB
(10KA) (10KA)
(TYP) (TYP)

SPARE

SPARE
RYB1

RYB2

RYB3

RYB4

RYB5

RYB6

RYB7

Y9

B9
R8
UP TO 1 PHASE CONNECTOR BOX , 16 AMP
WHETHER PROOF SOCKETS ARE LOOPED
LOOPING WITH 2.5 SQMM COPPER
CABLE IN 25 MM DIA CONDUIT