DC SOP-3 Auto Start with SLC ON and both AC SOP-1 & 2 OFF or discharge pressure of both pumps
2 are __KSC or DP between seal oil and H2 Pr. Is less.
DC SOP-3 will auto start after __ sec if either AC SOP-1 &2 is running and their discharge pressure is
3 __ KSC and DP between Seal Oil and H2 pr. Is inadequate.
H2 side seal oil PP can only be manually switched ON if SOT level is adequate and their of air side seal
4 oil Pp-1/2 is ON and air side seal oil Pr. Is adequate.
H2 side seal oil Pp trips with __ Secs time delay if SOT level is less than minimum value or air side seal
5 oil pressure is less.
6 Air side seal oil Pp-1 will start on auto (SLC should be ON)
When air side seal oil Pp-2 trips or its discharge pr. Is less and same logic is with air side seal oil Pp-2.
7
PRIMARY WATER SYSTEM ALARM LIST
1
After switching ON the SLC, both P.W. pps-1 & 2 start automatically if PW tank level is adequate. If
discharge pressure of both pumps are more , P.W. Pp-2 continues to run and PW pp-1 is switched off.
2
If discharge pr. Of running PW pp (1 or 2 ) is low, standby PW PP (2 or 1) takes start and first pump
trips if discharge pr. Of second pump is more provided SLC is ON
3 With SLC ON ,both PW pp (1 or 2 ) can not be run simultaneously until the discharge pressure of both
P.W pumps are less.
CF Recirculation pumps-1 & 2 will trip if dry protection tank level is low or if fire protection acts.
5
CF Recirculation Pp-2 will auto start if C.F Recirculation Pp-1 is off and HP CF pr. Is >__KSC
6
C.F heater will get ON release if C/F recirculation Pp-1 or 2 is running and CF temp. control valve is
7 close.
8 CF heater will auto ON if temp. in heater is <__°C or tank temp. <__°C
9 CF heater will auto OFF if temp in heater is >__°C or tank temp. > __°C.
10 CF heater trip protection will initiate if temp. in heater is >__°.
11 C.F. Temp controller (3-way) set point id __°C (C.F. tank temperature).
6 Spray C.V BPE-1/BPE-2 will close if pressure C.V BP-1/BP-2 opening is < __%.
7 BPE-1/BPE-2 opens in case of fast opening
8 BPE-1/BPE-2 switch over to auto if BP valve >__% open.
9 BPE-1/BPE-2 get stay put if oil pr. Is very low.
10 BP-1/BP-2 will close fully if its position is <__% open.
LP BYAPASS ALARM LIST
1 Condenser wall temp. port ( LPBP closed)
2 Condenser Vacuume protection
3 HPSU Energency off
4 When position conttrol valve demand >__% stop valve open.
water injection flow trip- ( Actual LPBP spray - LPBP down streem press. Equivalen flow)
5