Local Mode
dwg.no.: 5800029_doc.013
Rev.: 00 dated: 02.12.10
Block diagram HMQ-F-250-2000 JITPL Angul
For Local Mode
Before Start with Automatic Signal from
Remote/Control Room the mode switch on ABEL- Local
Display panel has to be in “Local” and the Release Start
signal (Pump system ready for start)has to be sent. Indication error on operator panel
(Release signal is a signal the main PLC sends in - Control power off
order of control of the whole system. If the line is - Filter element dirty
free this pump will work with, than this signal is
- Low oil pressure Correction
send to our PLC. It´s a control for the operator on
- High oil temperature of faults
side before he pushes the start bottom) yes
Faults from Abel - Level water box 1-4
display panel - min. pressure suction pipe
The Compressor is always - max. pressure in discharge pipe
active (standby). no - General error
no
The compressor has to be all no - Motor temperature high main motor
Power ON Motor
the time in ON with power M031 Compressor - Alert compressor
supply to the motor and to the - “Pump ready for start “was not send(Release)
control box on the yes
compressor. The max. no
pressure has to be 40 bar on Motor M 005 and booster pump ON Indication error on operator panel
the gauge. The compressor - Motor protection ON
starts to run down 33bar. If yes
the compressor was in OFF, it no If the fault ”min. pressure PIC030” is on in
needs 30 minutes to load the Lubrication pressure OK? operator panel, please push “QUIT”
Red letters are action vessel to 40 bar before you Oil temperatur OK?
coming from main can start the pump.
PLC. yes