Asset no: Transformer - 01 STANDARD OPERATING PROCEDURE SHOP : Utility Center Management no: Transformer - 01

Factory Name Process No. Process Name Department Group Write Review Acknowledgment

(JAEI/VoltAmp-01)
Work standard Electrical
Approval
MOBIS 1MVA, 11 / 0.415KV,50HZ Dry Type Transformer Facility Management Energy group

Drawing.NO.3CRT-RD-63714/0 Serial No:63714/1 NO. Sequence of the work Remarks

◈ Photo ※ Switch 'ON'

1 Ensure all the Control MCB is 'ON' in Marshalling Chamber.

2 Ensure all the doors are closed.

3 Emergency Push button Should be opened & Trip Indication Lamp should be in 'OFF' condition in the HT Panel.

4 Chect the FAULT Status in Annunciator at Incoming HT Panel.

5 Switch 'ON' the Incoming & Outgoing Feeder-01 (VCB breaker) through Trip Neutral Close(TNC) Switch.

6 Check the Primary Voltage in MDM in Outgoing Feeder-1 at the HT Panel.

7 Check the Secondary Voltage of the Transformer-1 at Main Incomer of the PCC-01 Panel.

8 Select the Selector Switch in Manual mode, to operate Blower/Fan through Illumination Push Button.

9 In Auto mode Blower/Fan will run automatically when temperature rises above 90 degree celcius.

10 Ensure marine lamp is off, at closed condition of Transformer-01 door.

 ※ Switch 'OFF'
11 Ensure 110V DC & 415V AC Available.

12 Ensure Spring Charge Indication is Healthy in the Outgoing Feeder-01 at the HT Panel.

12 Ensure Trip Circuit is Healthy.

14 Check the Selector Switch is in Local Mode.

15 Switch 'OFF' the Outgoing Feeders-01 (VCB breakers) through Trip Neutral Close(TNC) Switch.

16 Ensure 'OFF' Symbol Indication in the VCB Breaker.

17 Check the Outgoing-01 VCB 'OFF' Indication Lamp.

Precautions Safety guard Operational Condition Revision basis Confirm

1) No abnormal Noise from the Transformer.


1) Only Authorised Person should allowed to operate.
2) Always Wear Proper Safety PPE'S at the time of Electrical operation in
the Panel. 2) Maintain the Room Temperature at 30degree Amendment
3) Keep Safety Equipments around the Transformer like HT & LT Mat, Earth celcius. Record
Discharge Rods etc,.
4) Keep all the necessary tools at the time of Shutdown.
6) Switch OFF the Power before working. 3) No Foreign material should be present.
7) Discharge the Busbar with 11KV Discharge Rod after switch OFF
Transformer.

4) Don’t open the door at Live condition.


Asset no: Transformer - 02 STANDARD OPERATING PROCEDURE SHOP : Utility Center Management no: Transformer - 02

Factory Name Process No. Process Name Department Group Write Review Acknowledgment

(JAEI/VoltAmp-01)
Work standard Electrical
Approval
MOBIS 1MVA, 11 / 0.415KV,50HZ Dry Type Transformer Facility Management Energy group

Drawing.NO.3CRT-RD-63714/0 Serial No:63714/1 NO. Sequence of the work Remarks

◈ Photo ※ Switch 'ON'

1 Ensure all the Control MCB is 'ON' in Marshalling Chamber.

2 Ensure all the doors are closed.

3 Ensure marine lamp is off in door closed condition.

4 Emergency Push button & Trip Indication Lamp is in 'OFF' condition.

5 Chect the FAULT Status in Annunciator at Incoming HT Panel.

6 Switch 'ON' the Incoming & Outgoing Feeder-02 (VCB breaker) through Trip Neutral Close(TNC) Switch.

7 Check the Primary Voltage in MDM in Outgoing Feeder-2 at the HT Panel.

8 Check the Secondary Voltage of the Transformer-2 at Main Incomer of the PCC-02 Panel.

9 Select the Selector Switch in Manual mode, to operate Blower/Fan through Illumination Push Button.

10 In Auto mode Blower/Fan will run automatically when temperature rises above 90 degree celcius.

 ※ Switch 'OFF'
11 Ensure 110V DC & 415V AC Available.

12 Ensure Spring Charge Indication is Healthy in the Outgoing Feeder-02 at the HT Panel.

13 Ensure Trip Circuit is Healthy.

14 Check the Selector Switch is in Local Mode.

15 Switch 'OFF' the Outgoing Feeders-02 (VCB breakers) through Trip Neutral Close(TNC) Switch.

16 Ensure 'OFF' Symbol Indication in the VCB Breaker.

17 Check the Outgoing-02 VCB 'OFF' Indication Lamp.

Precautions Safety guard Operational Condition Revision basis Confirm

1) No abnormal Noise from the Transformer.


1) Always Wear Proper Safety PPE'S at the time of Electrical operation in
the Panel.
2) Only Authorised Person should is allowed to operate. 2) Maintain the Room Temperature at 30degree Amendment
3) Keep Safety Equipments around the Transformer like HT & LT Mat, Earth celcius. Record
Discharge Rods etc,.
4) Keep all the necessary tools at the time of Shutdown.
5) Prepare the tools before working. 3) No Foreign material should be present.
6) Switch OFF the Power before working.
7) Discharge the Busbar with Discharge Rod before working.

4) Don’t open the door at Live condition.


Asset no: HT Panel - 01 STANDARD OPERATING PROCEDURE SHOP : Utility Center Management no: HT Panel-01

Factory Name Process No. Process Name Department Group write Review Acknowledgment

(Eaton) 11KV HT Panel Indoor


Work standard Electrical
Approval
MOBIS 11KV, 1250A, 3Phase, Type Facility Management
50Hz. Energy 1 group

Drawing.NO.LC18043M005 Panel Serial No:LC18043M00501 NO. Sequence of the work Remarks

◈ Photo ※ Switch 'ON'

1 Ensure all the Control MCB is 'ON' in Control Chamber.

3 Ensure 110V DC & 230V AC Available.

4 Ensure Line PT, Incoming/Outgoing VCB is 'Racked IN'.

5 Ensure 11KV is 'ON' through MFM, MICOM & R,Y,B Indidcation in the Incoming VCB feeder.

6 Ensure the Trip Circuit Indication & Spring Charge Indication is Healthy.

7 Ensure the Master Trip Relay is not flagged down.

8 Check the Selector Switch is in Local Mode.

9 Emergency Push button & Trip Indication Lamp is in 'OFF' condition.

10 Chect the FAULT Status in Annunciator.

11 Switch 'ON' the Incoming Feeder (VCB breaker) through Trip Neutral Close(TNC) Switch.

12 Switch 'ON' the Outgoing Feeders (VCB breakers) through Trip Neutral Close(TNC) Switch.

13 Check the Incoming/Outgoing VCB 'ON' Indication Lamp.

 ※ Switch 'OFF'
14 Ensure 110V DC & 230V AC Available.

15 Ensure Spring Charge Indication is Healthy.

16 Ensure Trip Circuit is Healthy.

17 Check the Selector Switch is in Local Mode.

18 Switch 'OFF' the Outgoing Feeders (VCB breakers) through Trip Neutral Close(TNC) Switch.

19 Switch 'OFF' the Incoming Feeder (VCB breaker) through Trip Neutral Close(TNC) Switch.

20 Ensure 'OFF' Symbol Indication in the VCB Breaker.

21 Check the Incoming/Outgoing VCB 'OFF' Indication Lamp.

22 Ensure Fire Fighting System is at Safety Zone.(Dial Indication should be Green Zone)

Precautions Safety guard Operational Condition Revision basis Confirm

1) No abnormal Noise from the Panel.


1) Always Wear Proper Safety PPE'S at the time of Electrical operation in
the Panel.
2) Only Authorised Person should is allowed to operate. 2) Maintain the Room Temperature at 30degree Amendment
3) Keep Safety Equipments around the Electrical Panels like HT & LT Mat, celcius. Record
Earth Discharge Rods etc,.
4) Keep all the necessary tools.
5) Prepare the tools before working. 3) No Foreign material should be present.
6) Switch OFF the Power before working.
7) Discharge the Busbar with Discharge Rod before working.
4) Keep Rack IN / OUT & Spring charge handles
for Panels / Line PT.
Asset no: PCC Panel - 01 STANDARD OPERATING PROCEDURE SHOP : Utility Center Management no: PCC Panel - 01

Factory Name Process No. Process Name Department Group Write Review Acknowledgment

(Eaton-01) Work standard Electrical


Approval
MOBIS 415VAC, 1600A, FP, EDO, LT Panel Indoor Type Facility Management
Energy group
50Hz.

Drawing.NO.LC18050L Panel Serial No:LC18050L0901 NO. Sequence of the work Remarks

◈ Photo ※ Switch 'ON'

1 Ensure the Panel is Clean.

2 Ensure all the Control MCB is 'ON' in all Control Chamber.

3 Ensure 24V DC & 230V AC Available.

4 Ensure Incoming, Outgoing & TIE ACB is 'Racked IN'.

5 Ensure R,Y,B Line Indication Lamp and MDM is working.

6 Ensure Trip Circuit is Healthy.

7 Ensure Spring Charge Indication is Healthy.

8 Check the Fault/Trip Indication in the Panel.

9 Ensure Main Incoming Supply of Capacitor Compartment is 'ON'.

10 Ensure the Fans are 'ON' in the Capacitor Bank Compartment.

11 Check the Power Cables which is connected in the Capacitors, Series Reactor & MCCB is free from burning issue.

12 Check all the illumination indication lamp is 'OFF' in Capacitor Compartment.

13 To operate Manually, select all the Selector switch in Manual mode and Close the TNC switch.

14 To operate in Auto, select all the Selector switch in Auto mode and it operates Automatically.

15 Ensure ACB is 'ON' through ACB ON Indication Lamp and symbol indicator in ACB.

 ※ Switch 'OFF'
16 Ensure 110V DC & 230V AC Available.

17 Ensure Spring Charge Indication is Healthy.

18 Ensure Trip Circuit is Healthy.

19 To operate Manually, put all the Selector switch in Manual mode and Trip the TNC switch.

20 To operate in Auto, put all the Selector switch in Auto mode and it operates Automatically.

21 Ensure ACB is 'OFF' through ACB OFF Indication Lamp and symbol indicator in ACB.

22 NOTE : If EB/TIE is ON, DG will not ON there is a Electrical Interlock between EB & DG.

23 NOTE : At Manual Mode, EB and DG will be ON, when TIE breaker is OFF.

Precautions Safety guard Operational Condition Revision basis Confirm

1) No abnormal Noise from the Panel.


1) Always Wear Proper Safety PPE'S at the time of Electrical operation in
the Panel.
2) Only Authorised Person is allowed to operate.
3) Keep Safety Equipments around the Electrical Panels like HT & LT Mat, 2) Maintain the Room Temperature 30 degree Amendment
Earth Discharge Rods etc,. celcius. Record
4) Keep all the necessary tools.
5) Prepare the tools before working.
6) Switch OFF the Power before working. 3) No Foreign material should be present.
7) Discharge the Busbar with Discharge Rod before working.
8) Do not Rack Out ACB at Live Condition.
4) Keep Rack IN / OUT & Spring charge handles.
Asset no: PCC Panel - 02 STANDARD OPERATING PROCEDURE SHOP : Utility Center Management no: PCC Panel - 02

Factory Name Process No. Process Name Department Group Write Review Acknowledgment

(Eaton-02) Work standard Electrical


Approval
MOBIS 415VAC, 1600A, FP, EDO, LT Panel Indoor Type Facility Management
Energy group
50Hz.

Drawing.NO.LC18050L Panel Serial No:LC18050L0101 NO. Sequence of the work Remarks

◈ Photo ※ Switch 'ON'

1 Ensure the Panel is Clean.

2 Ensure all the Control MCB is 'ON' in all Control Chamber.

3 Ensure 24V DC & 230V AC Available.

4 Ensure Incoming, Outgoing & TIE ACB is 'Racked IN'.

5 Ensure R,Y,B Line Indication Lamp and MDM is working.

6 Ensure Trip Circuit is Healthy.

7 Ensure Spring Charge Indication is Healthy.

8 Check the Fault/Trip Indication in the Panel.

9 Ensure Main Incoming Supply of Capacitor Compartment is 'ON'.

10 Ensure the Fans are 'ON' in the Capacitor Bank Compartment.

11 Check the Power Cables which is connected in the Capacitors, Series Reactor & MCCB is free from burning issue.

12 Check all the illumination indication lamp is 'OFF' in Capacitor Compartment.

13 To operate Manually, select all the Selector switch in Manual mode and Close the TNC switch.

14 To operate in Auto, select all the Selector switch in Auto mode and it operates Automatically.

15 Ensure ACB is 'ON' through ACB ON Indication Lamp and symbol indicator in ACB.

 ※ Switch 'OFF'
16 Ensure 110V DC & 230V AC Available.

17 Ensure Spring Charge Indication is Healthy.

18 Ensure Trip Circuit is Healthy.

19 To operate Manually, put all the Selector switch in Manual mode and Trip the TNC switch.

20 To operate in Auto, put all the Selector switch in Auto mode and it operates Automatically.

21 Ensure ACB is 'OFF' through ACB OFF Indication Lamp and symbol indicator in ACB.

Precautions Safety guard Operational Condition Revision basis Confirm

1) No abnormal Noise from the Panel.


1) Always Wear Proper Safety PPE'S at the time of Electrical operation in
the Panel.
2) Only Authorised Person is allowed to operate.
3) Keep Safety Equipments around the Electrical Panels like HT & LT Mat, 2) Maintain the Room Temperature 30 degree Amendment
Earth Discharge Rods etc,. celcius. Record
4) Keep all the necessary tools.
5) Prepare the tools before working.
6) Switch OFF the Power before working. 3) No Foreign material should be present.
7) Discharge the Busbar with Discharge Rod before working.
8) Do not Rack Out ACB at Live Condition.
4) Keep Rack IN / OUT & Spring charge handles.
Asset no: LVR Panel - 01 STANDARD OPERATING PROCEDURE SHOP : Utility Center Management no: LVR Panel - 01

Factory Name Process No. Process Name Department Group Write Review Acknowledgment

(LCP-01) Work standard Electrical


Approval
MOBIS 415VAC, 63A, 36KA TP, LT Panel Indoor Type Facility Management Energy group
50Hz.

Drawing.NO.LC18050L Panel Serial No:LC18050L011001 NO. Sequence of the work Remarks

◈ Photo ※ Switch 'ON'

1 Ensure the Panel & Bsttery is Clean.

2 Ensure all the Control MCB is 'ON' in all Control Chamber.

3 Ensure 415V AC is Available through MIMIC & Voltmeter.

4 Ensure the Panel is free from Fault and Trip, if any Acknowledge, Reset and Rectify the fault.

5 Ensure Battery Charging Selector Switch is in Auto Mode.

6 Ensure the Incoming MCCB is ON for Transformer.

7 Ensure Rectifier is Outgoing ON.

8 Ensure Tie MCCB is ON to Charge the 110V DC to the Batteries.

9 Switch 'ON' the Battery Charger Selector Switch.

10 Ensure the 110V DC is available through MIMIC and 110V DC Ammeter.

 ※ Switch 'OFF'
11 Ensure 110V DC & 415V AC is Available.

12 Switch OFF the Battery Charger Selector switch.

13 Switch OFF the Main Incoming Supply in the Incoming MCCB & Control MCB.

14 Ensure the Incoming Supply, Control Supply and Rectifier is OFF through 415V AC Voltmeter and MIMIC.

Precautions Safety guard Operational Condition Revision basis Confirm

1) No abnormal Noise from the Panel. If any


noise please rectify and Switch 'ON' the Battery
1) Always Wear Proper Safety PPE'S at the time of Electrical operation in Charger Panel.
the Panel.
2) Only Authorised Person is allowed to operate.
3) Keep Safety Equipments around the Electrical Panels like HT & LT Mat, 2) Maintain the Room Temperature 30 degree Amendment
Earth Discharge Rods etc,. celcius. Record
4) Keep all the necessary tools.
5) Prepare the tools before working.
6) Switch OFF the Power before working. 3) No Foreign material should be present.
7) Discharge the Busbar with Discharge Rod before working.

4) Keep the Fans always ON in the Battery


Compartment.
Asset no IRL-01 Management no.

Factory name PROCESS NO. Process Name Department Minor write

Utility center
1.(IngersollRand)
1250 hp-Low pressure COMPRESSOR Driving Work standard Energy Management Energy 1 group
Approval

Compressor Tips Team

◈ Photo NO Sequence of the work


Supply standard
Model name (SYS 'pressure) SERIAL NO Flow rate 1 ※ Driving

C1000 6.0 ㎏/㎠ NAR-10491357 2125 lpm 2 1) Check the power supply status of the start panel. (Voltage 3300V check)

3   2) Cooling water pressure and temperature, oil tank, intercooler, condensate trap

4 Check for leaks, leaks, etc. Check for back pressure of compressor

5   3) After confirming SEAL AIR (5.0㎏ / ㎠ ↑), turn on S / W of CONTROL panel

6 4) Press the START button to check the oil pump operation, oil pressure and direction of rotate.

7    5) Set the UNLOAD / AUTOLOAD switch to the UNLOAD position.

8    6) After checking the COMPRESSOR READY status, press the START button.

9    7) Check the condition of VIB and piping valve during START 1, 2, 3.

10    8) If there is no problem, switch the UNLOAD / AUTOLOAD switch to AUTOLOAD

11    9) Check the operation status of the condensate trap of the intercooler and the after cooler.

12  ※ Stop

13    1) Place the UNLOAD / AUTOLOAD switch in UNLOAD.

14    2) Press the STOP button.

15    3) Open the intercooler condensate trap drain valve.

16    4) Press RESET or STOP BUTTON to prepare for the next operation.

Precautions Safety guard Operational Condition Revision basis

1) No abnormality of oil system


(oil temperature 30 ℃ ↑) Compressor Installation
1)"1) Cut off the power before the compressor work,
install it on the screen during operation.   2) No abnormality in cooling water system
2) Pre-work accident risk pre-training. Amendment
(cooling water 2 ㎏ / ㎠ ↑) Record
3) Prepare the tools before working.
4) Maintain a regular arrangement around the
workshop.   3) No abnormality of instrument system
5) Ensure safety guard before work and work after
wearing.
6) Start the compressor within three times a day. "   4) No abnormality of AIR suction system
IRLCOMP-01

Review Acknowledgment

Remarks

Confirm
Asset no IRH -01 Management no:

Factory
Process No. Process Name Department Minor write
Name
1.(IngersollRand) COMPRESSOR Driving
Work standard Approval
Uility Center 1250 hp-High pressure
Tips Facility management Energy 1 group
Compressor

◈ Photo NO Sequence of the work

Model Name (System


C1000 Pressure) Serial No Flow rate 1 ※ Driving

SIZE(5.5m×2.7m×1.447m) 7.5 ㎏/ ㎠ 1 2 Check the power supply status of the start panel. (Voltage 3300V check)

3 Cooling water pressure and temperature, oil tank, intercooler, condensate trap check for leaks etc.

Check instrument air above 4 Bar Maintain

4 After confirming SEAL AIR (7.0 ㎏ / ㎠ ↑), turn on S / W of CONTROL panel

5 Press the START button to check the oil pump operation, oil pressure(above 1.5 bar).

6 Set the switch to the UNLOAD position.

7 After checking the COMPRESSOR READY status, press the START button.

8 Chect the shaft rotations then put the load conditions

9 Check the condition of drin piping valve during START 1, 2, 3.

10 If there is no problem, switch the LOAD condition

11 Check the operation status of the condensate trap of the intercooler and the after cooler.

 ※ Stop
12 Place the UNLOAD / switch in unload.

13 Open the intercooler condensate trap drain valve.

14 Press unload botton after 5 Minutes swith off botton press.

16 Now the oil pump is auto start again we run the oil pump for 30 minutes after compressor stop.

17 After 30 minutes stop the power supply switch and press the emergency button in the compressor panel.

18 Push off the emergency button in soft starter panel.

Precautions Safety guard Operational Condition Revision basis

1) No abnormality of oil system Compressor Installation


(oil temperature 30 ℃ ↑)
1) Cut off the power before the compressor work,
and install it on the screen during operation.  2) No abnormality in cooling water
2) Pre-work accident risk pre-training. Amendment
3) Prepare the tools before working. System (cooling water 3 ㎏ / ㎠ ↑) Record
4) Maintain a regular arrangement around the
workshop.
5) Ensure safety guard before work and work after 3) No abnormality of instrument system
wearing.
6) Start the compressor within three times a day. "
4) No abnormality of AIR suction system
IRHCOMP-01

Review Acknowledgment

Remarks

Confirm