2. Switch ON 415V Aux. supply in MCC-4,1R5 feeder for Pump, Aux. Fan and Control Trafo.
4. Put Ground Isolator switch in open (Unlocked) position. Both Unlocked and Offline indication
will glow.
6. Check whether Raw water circulation is available or not. Maintain the Raw water temperature
45 °C = Alarm
48 °C = Trip
7. Check all the Transformer relays are in healthy (Bucholz, Wdg temp.Oil temp).
9. Check whether line & Delta contactors are in ON and Star contactor should be OFF condition
10. Check the conductivity value in CDP and must be below 0.3µs.
16. If all the above conditions are satisfied, press the reset button in CDP (MV drive).
NOTE:
Ground isolator switch should be operate when 110V DC is ‘ON’ in MV Panel only the same