The EHTC system with Proportional valve is used for the control of direct operated high
response valves STW and uses two stage position controls. In first stage demand signal from
speed /load, controller is compared with EHC piston position and a difference is applied as
differential input command value to Amplifier module. In second stage actual value of pilot valve
spool position is measured through inductive position feedback transmitter and compared with
the externally applied command value. Any differences between the actual and command
values drive the proportional valve.
System Overview –
12a). Differential Input (4-20mA or ±10V) from the DCS module is applied to the Amplifier Card
(Pin 4 & 5), which can be measured in voltage form ±5V at the front panel of the Amplifier
Card.
12b). With hydraulics and the Electronics/Power supply “ON” apply Differential Input of
12mA or 0V from the DCS module to the Amplifier card, correspondingly measure the
Voltage at ports 2(Voltage point on the Multi meter) and 3 or 4 (Common point on the
Multi meter) given on the front panel of the Amplifier Card. The voltage reading on the
Multi meter should be 0V; if not tune the R1 potentiometer till it reads 0V.
12c). With Differential input of 12mA or 0V from the DCS module to the Amplifier card the
Voltage measured at ports 1(Voltage point on the Multi meter) and 3 or 4(Common
point on the Multi meter) given on the front panel of the Amplifier Card should be 0V,
else tune the R21 potentiometer till it reads 0V or the zero point on the valve is
achieved.
12d). Apply the Differential Input (4-20mA or ±10V) in steps from the DCS module to the
Amplifier Card and correspondingly measure the Voltage at the Ports on the front
panel of the Amplifier card. Command value should match the Actual Value.
Scaling of Differential Input applied and the Voltage measured on the front panel of the
Amplifier Card.
Differential Input.
4mA 12mA 20mA
-10V 0V +10V
Voltage on the Front Panel of the Amplifier Card (Command Value & Actual Value).
-5V 0V +5v
The supplied position valve is susceptible to Signal interference. Hence utmost care
shall be taken during power supply and earth checks of the system.
Annexure –B
POSITION CONTROLLER