You are on page 1of 1

Form 150.68-O1.EN.

CE (0311)

Anti-Recycle Timer Lead/Lag Control


Each system has its own anti-recycle timers. The The unit may be set up for AUTO or MANUAL lead/lag.
anti-recycle time under the PROGRAM key can be This is accomplished by programming the option under
programmed between 240 - 600 seconds and sets the the ‘OPTIONS’ key.
minimum start-to-start time of the lead compressor in a
system. A second non-programmable anti-recycle timer, When AUTO lead/lag is used, the microprocessor
stop to start is fixed at 90 seconds, starts to countdown attempts to balance run time between the systems. A
when the lead compressor in a systems cycles off. On number of conditions can occur which will prevent this
power up only this timer is set to 120 seconds not 90 from happening. Factors determining lead/lag selection
seconds. and the resulting lead/lag determination are:

The lag compressor(s) in a system, are not controlled The microprocessor automatically defaults the lead to
by the anti-recycle timer. system 1 and the lag to system 2 if both systems are
ready to start (Anti-recycle Timers timed out) and the
Anti-Coincidence Timer systems have equal run time.

The anti-coincidence timer prevents both systems from If both systems are waiting to start (Anti-recycle timers
starting simultaneously. This assures that the inrush have not timed out), the microprocessor will assign the
current is kept to a minimum. A 60 second time delay lead to the system with the shortest anti-recycle time to
will always separate motor starts. This timer is not provide duty quickly.
programmable.
If the lead system is locked out, faulted and waiting to
Refrigerant to Water Heat Exchanger Heater restart the lag system is swapped to the lead.
Control
MANUAL lead/Lag selection will be automatically
The water heat exchanger heater is controlled by overridden by the microprocessor to allow the lag
ambient temperature. When the ambient temperature is system to automatically become the lead anytime the
below 4.4 °C the heater will be switched on. When the selected lead system shuts down due to, lead system
temperature rises above 7.2°C, the heater is switched faults.
off. An under voltage condition will keep the heater off
until full voltage is restored to the system. Automatic switch over in MANUAL mode is provided
to try to maintain unit liquid temperature as close to
The 110 Vac control supply must remain ON
‘SETPOINT’ as possible.
for freeze protection. Otherwise, the water
heat exchanger must be drained. Units without Soft Start
The strategy for compressor loading within a system
is to maximize individual compressor run time and
Compressor Crankcase Heaters ensure that the same compressor does not start twice
in a row.
Each compressor is fitted with a crankcase heater
which is ‘ON’ when the compressor is ‘OFF’, being This is achieved by rotating the lead/lag sequence of
feed via a normally closed contact on each compressor the compressors in a system when a compressor other
contactor. than the lag most compressor in that system stops.
In achieving this objective no attempt will be made to
equalize each compressors individual total run hours
within a system.
Units with Soft Start
These units have a soft starter fitted to the last
compressor in each system. SOFT START ENABLED
must be displayed under the ‘OPTIONS’ key. With this
option enabled the controls ensure that the compressor
fitted with the soft starter is the last compressor to start
in the system. Compressors are always started in the
same order, No.1 compressor first.

EN 15

You might also like