Cooling Mode If all the fans are running at full speed they can be The reason for two speed fans it to reduce unit noise forced to run at slow speed to reduce fan noise in two by running the fans in slow speed over as wide a range ways. First method is by closing a voltage free contact of conditions as possible, only going to full speed as a terminals 13 and 15 on -XTBC1. The second method last resort. This is achieved by raising the pressure at is by programming a Daily Fan Speed Inhibit time zone which the last fan stage occurs, switching from all fans under the SCHEDULE/ADVANCE DAY key. running in slow speed to all fans running in fast speed.
The Fan On Pressure is programmable under the
PROGRAM key. When the discharge pressure is > Fan On Pressure and the fan delay timer has expired, the fan stage is incremented by 1. After incrementing the fan stage the fan delay timer is set to 5 seconds and the Fan On Pressure is ramped from 1.4 BARG over the original value back to the original value over the next 20 seconds.
On a fan stage incrementing so that the next incremented
fan stage would result in the fans switching from slow to fast speed, the fan delay timer is set to 5 seconds and the Fan On Pressure is raised by 5.5 BARG. The Fan OFF Pressure is not move at this time. If the discharge pressure then rise above this new value and the fan delay timer has expired, the fan stage is incremented by 1. The fan delay timer is set to 5 seconds and the Fan OFF Pressure is raised by 5.5 BARG. All fans on full speed.
On a fan stage decrements resulting in the fans switching
from fast to slow speed, the fan delay timer is set to 5 seconds and the Fan OFF Pressure is lowered by 5.5 BARG back to the programmed Fan OFF Pressure. No further lowering or ramping back up, occurs when this stage decrements. All fans now running on slow speed.
The Fan Off Pressure is equal to the Fan On Pressure
minus the Fan Diff Off Pressure which is programmable under the PROGRAM key.
On a further fall in discharge pressure when the
discharge pressure is < Fan Off Pressure and the fan delay timer has expired, the fan stage is decremented by 1. After decrementing the fan stage the fan delay timer is set to 5 seconds and the Fan Off Pressure is ramped from 1.4 BARG below the original value back to the original value over the next 20 seconds.