Professional Documents
Culture Documents
Technical Bulletin
CS3 product series are a safety pressure switch with fixed switch-
point settings for R744 applications.
Features
• Maximum Working Pressure of 140 bar; Test Pressure of 154
bar
• Narrow differential (approx. 3 bar) between cut-out and cut-in
(in Microswitch version)
• Precise switching and repeatability; Snap Action Contacts =>
Chatter Free (Bounce free) and Accurate Operation
• Contacts are designed as SPDT (Single pole double throw) for CS3
control function and alarm/status reporting
• Direct compressor mounting with adapter option Standards
• 2 million cycles reliability (TÜV EN 12263 approved)
• per Low Voltage Directive
• Manual reset versions available
• IP65 protection if used with PS3-Nxx with plug • per PED Directive 97/23/EC
(acc. EN 175301-803), no additional gasket required (molded
• Manufactured and tested to VDE standards on our own
into plug)
responsibility
• pending
Selection table
1. Standard types (Minimum order quantity 60pcs)
Fixed setting [bar] Pressure
Type Part No. Reset Electrical Switch
Cut-out Cut-in connection
Pressure Limiter
0718003M 106 bar Approx. 75 bar Standard switch
CS3-W8S
Automatic
Pressure Limiter
0718000M 106 bar Approx. 103 bar Micro switch
CS3-WQS 7/16"-20 UNF
Pressure Cut-out Approx. 30 bar female thread with
0718001M 108 bar External manual Standard switch
CS3-B8S below cut-out Schrader opener
Safety Pressure
Approx. 30 bar
Cut-out 0718002M 108 bar Internal manual Standard switch
below cut-out
CS3-S8S
Note: cables with plug must be ordered separately (see page 3).
CS 3 - W 8 S
Product Name
Function
W= Pressure limiter, automatic, type approval
EN 12263, PSH
B= Pressure cut-out, external manual reset
Pressure Range / Contacts
type approval, EN 12263, PZH
S= Safety pressure cut-out, internal manual reset Standard Contacts Microswitch
type approval, EN 12263 PZHH 8 = 90…140 bar Q = 90...140 bar
www.emersonclimate.eu
Pressure Controls Series CS3
General Information
bellows
Technical Data
Protection class IP 65 with PS3-Nxx Storage and transportation -40°C…+70°C
acc. to EN 60529 IP00 without appliance socket temperature
Ambient temperature -40°C…+70°C
Max. working pressure PS 140 bar
(housing) *
Test pressure PT 154 bar Medium temperature -40°C… +150°C
Vibration resistance 4g (at 10…475 Hz)
Medium compatibility R744 Marking
Note: CS3 are not released for acc. Low voltage Directive
use with flammable refrigerants! 0035 acc. To PED 97/23/EC
pending
Tm = Medium temperature
Ta = Ambient temperature
Tm [°C]
Electrical Data
Standard
Micro switch (SPDT)
(SPDT)
Inductive load (AC15) 3A / 230VAC 1.5A / 230VAC
Inductive load (DC) 0.1A / 230VDC 0.1A / 230VDC
Motor rating amps (FLA) 6A / 120 / 240VAC 2.5A / 120 / 240VAC
Lock rotor amps (LRA) 36A / 120 / 240VAC 15A / 120 / 240VAC
2
CS3_TB_EN_1505_R00.docx
Pressure Controls Series CS3
Accessories
Cables Assemblies
Diameter Temperature Cable length
Type Part No. No of leads
of leads Range °C [m]
PS3-N15 804 580 1.5
2
PS3-N30 804 581 3 0.75 mm -50…+80 3.0
PS3-N60 804 582 6.0
Other Accessories
7/16”-20UNF
13
30 SW 14
10
1/8”NPT
Adapter 1/8”NPT (male) -7/16”-20UNF-(male)
(for compressor direct mounting)
Part No.: 800 316
Dimensions [mm]
41 28
22
PS3-Nxx
43
3543
20
48 39
Connection S
7/16-20 UNF female with Schrader valve opener
3
CS3_TB_EN_1505_R00.docx
Pressure Controls Series CS3
CS3_TB_EN_1505_R00.docx
Emerson Climate Technologies GmbH shall not be liable for errors in the stated capacities, dimensions, etc., as well as typographic errors. Products, specifications, designs and technical data contained
in this document are subject to modification by us without prior notice. Illustrations are not binding.
The Emerson Climate Technologies logo is a trademark and service mark of Emerson Electric Co. Emerson Climate Technologies Inc. is a subsidiary of Emerson Electric Co.