You are on page 1of 12

CP 3 :Chap.

IV: 1962
CP 3 : Chap. IV : 1962
reduce the risk that the smoke will penetrate the smoke.-stop door which pro-
tects the corridor. Provided the corridor is protected throughout its length in this (ii) The provision of means of ventilation as distinct from permanent venti-
manner a limited length of dead-end will not prove unsafe. Hence the possibility lation may contribute to personal safety in a more general way. It will assist
of increasing the number of flats per floor in a single staircase building. The exit the fire service and will thereby reduce the risk that smoke will spread within the
doors from the flats must, of course, be arranged to comply with the principle building. This Code therefore contains recommendations for a measure of venti~
referred to in (iii) above. lation to corridors (Clause 207) but as this provision is for the use of the fire
(viii) The travel distance limitation of 15ft referred to in (iii) above is devised service and is not directly related to safety during early esc~pe, it is not necessarily
as an escape measure and as a means of reducing to a minimum the risk that provided in ·the form of permanent openings. Windows or doors that can be
persons might be trapped on a public escape route. This risk cannot be elimi- opened when desired will suffice. The permanent openings to lobbies recom-
nated, however, and the safety of the occupants of dwellings which are not mended in c (vii) above serve a different purpose since their purpose is to be
provided with an alternative exit must rest ultimately upon the protection effective at the time of escape. These openings, together with the doors that
afforded by the fire resisting entrance doors mentioned in (i) above. In that sub- separate the lobbies from the corridor, may be used for venting the latter at the
paragraph, the purpose of the doors is to hold back fire or smoke within a later stage to which this sub-paragraph refers.
dwelling in order to keep the public escape passages clear. The same door will Although the general recommendation is that corridors should be capable of
serve to hold back from entering a dwelling fire or smoke which has reached the being ventilated independently of staircases, where any corridor is connected to
public escape passage from another dwelling. The occupants, therefore, will be two or more staircases these may safely be used for ventilation purposes. The
safe if they remain in the dwellings until the fire is extinguished. staircases should, however, have permanent ventilation at every floor level to
d. Corridor-approach maisonnettes. The principles stated above for flats reduce the risk that they will act as flues. Where permanent openings are pro-
apply equally to maisonnettes. It will be found in practice, however, that a vided, the percolation of sno\v cannot be prevented but fixed louvres will reduce
solution similar to that described in c (ii) above will be the normal one because the amount and will eliminate any penetration of rain. Because the penetration of
of the need to provide alternative exits from maisonnettes in connection with snow cannot be wholly prevented, the alternative method of venting, indepen-
Stage one. dently of staircases, is to be preferred.
e. Ventilation. (i) The provision of cross~ventilation (i.e. ventilation at two (iii) The above recommendations for ventilation may call for modifications
points to produce a through draught) to a main corridor can contribute to safety in designs which are based only on earlier considerations. For example, if the
by diluting and dispersing smoke, but the principle has some practical objections staircases in Fig. 3 are not permanently ventilated as described above, the
and weaknesses. The amount of smoke generated by a fire can be considerable. corridor must be extended to the external walls as shown in Fig. 5.
If the entrance door of a flat which opens on to a corridor should fail to restrain 204. Stage three. a. General. This stage is concerned with the safety of occupants
the smoke (and this possibility is assumed throughout) only the rapid movement using a main vertical escape route, i.e. a staircase (lifts must be disregarded for
of a large quantity of fresh air would make the escape route reasonably safe. escape purposes, primarily because of the delay that may be experienced before
.But, in the .first instance, it is not possible to ensure this condition at all times, a lift answers a call, and of the limited capacity of the lift when it arrives). The
since the horizontal movement of air within a building will depend upon the main objectives are:
direction and speed of the wind at the time of the fire. And, secondly, as the (i) to remove sufficiently the risk that smoke or fire might enter a stair-
provision must be a permanent one if credit is to be given to it at all, there will case at any point and render it impassable above that point,
be many occasions when the draught will make the corridor unbearable for ·.' (il) to ensure that the escape route from the bottom of the staircase to
normal use. Any attempt to remedy the second objection by reducing the size i the outside air is adequately protected.
of the permanent openings will increase the first objection that the movement of The importance of the second of these objectives is frequently overlooked.
air at the tin1e of a fire may be inadequate for the purpose. For these reasons the A satisfactory ground floor plan cannot always easily be developed from a satis-
principle of using cross-ventilation as a basis for the design of means of escape factory upper floor plan and occasionally a satisfactory upper floor plan will
has not been adopted in this Code, but this is not to deny that facilities for the produce problems at ground level which are incapable of solution. Upper and
removal of smoke from corridors will prove beneficial. If permanent ventilation ground floor plans should therefore be developed together. The problems and
can be afforded by some means without producing too severe an effect upon the precautions necessary with maisonnettes are the same in Stage three as with
living conditions in the building, some gain·in safety will result. flats.
14 b. Staircase arrangement and protection. (i) The minimum protection that
15
LFB00060984/1

LFB00060984_0001
CP 3 : Chap. IV : 1962
CP 3 : Chap. IV : 1962
building is shown in Fig. 4, a design developed initially to provide adequate
should be given to any staircase is to ' enclose ' it,. i.e. to surrou~d it with fire-. safeguards in Stage two (203 c (vii)). Here, the arrangement described in the
resisting walls with self~dosing fire-resisting access doors. As a likely source of previous paragraphs is reversed. All the dwellings open directly into permanently
fire is a dwelling, no dwelling should be entered directly from a staircase. In ventilated lobbies and the corridor, out of which the staircase is entered, is itself
corridor access blocks, therefore, the corridor and in balcony access blocks, the entered only from these lobbies, through smoke-stop doors. It will be observed
balcony, should separate dwelling entrance doors from a staircase. ~imilarly, and that in this system, as in the system described in the preceding paragraphs, the
particuhirly in a single staircase building, no store or other fire nsk sue~ as a staircase is protected by two smoke-stop doors and a ventilated lobby but that
gas meter room, an electric intake, or a cleaner's cupboard should open dtrectly the relationship of the ventilated lobby to the staircase is different in the two
systems (see Figs. l and 4).
into a staircase.
(ii) Even with this precaution there remains some risk that smoke will enter (vi) The methods of protection to staircases described above can be sum-
a staircase, and in high buildings this risk must be countered. There are two marized as follows:
methods. One is to provide two staircases in a building, on the assumption that A. where there is more than one staircase there should be a smoke-stop
smoke is unlikely to enter more than one staircase at any time. This assumptio? door across the corridor between the doors in the enclosing walls of any
may prove false, particularly if the staircases are close together. A safeguard 1s two staircases.
to provide a smoke-stop door across the interna~ communic~ting s~cc b~tween n. where there is only one staircase there should be a smoke-stop door
the staircases so that, if a fire occurs at any pomt, one starrcase will enjoy the
across the corridor between the door in the enclosing wall of the staircase
protection of an additional smoke-stop door on that floor. Such a door is .shown
and any door covering a potential source of fire (e.g. a dwel!lng entrance
in Fig. 3. It was provided, initially, in order to meet the 15ft. travel distance
door or a door to a storage space) and at least one of the spaces resulting
limitation of the second stage. It will be seen, however, that the same door also
should take the form of a lobby which is permanently ventilated through an
contributes to safety in the third stage, as there will always be the protection of
adjoining external wall.
two smoke-stop or fire resisting doors between one of the staircases and a smoke-
logged corridor (see Figs. 3 a and 3 b). (vii) In the recommended methods of prot~tion to staircases provision is
(iii) The other, and more effective, method is to enter the staircase from a made in certain cases for ventilating the common access space leading to the
lobby which is permanently ventilated to the open air and which is itself entere~ staircases-by means of doors or windows which can be opened where there are
only from the internal communicating space through a smoke-stop door. In thts two staircases, or through a permanent vent in an external wall where there is
case, the staircase will have the protection of two smoke-stop doors and a only one staircase (see Clause 203 e (ii) ). Where this provision is made it is
ventilated lobby. This arrangement is so safe that, provided the staircase en- considered that staircases can safely be located in the interior of a building, if
closure has no weakness, a building with a single staircase so arranged can be desired, and not necessarily on an external wall. When they are so located they
regarded as having safe means of escape in the third stage. Fig. 1 illustrates such should have permanent ventilation at the top. The exits at ground floor should
an arrangement. It will be noted that there is no requirement in Stage two for take the form described later. Any inlet air that may be necessary for the nonnal
the lobby (Fig. 1) to have pennanent ventilation, since this lobby cannot be ventilation of the staircase can be obtained by keeping open the ground floor
attacked by smoke or heat in this stage and thus form a trap for those wishing entrance doors.
to escape from the flat Should a fire not be extinguished early, however, smoke c. Protection of the escape route from the bottom of a staircase to the open air
might eventually reach the lobby and the permanent ventilation is a necessity at ground lel'el. (i) On the upper floors of a building, the staircase enclosure
to ensure the dissipation of smoke and heat in Stage three, as a protection to and the fire resisting access doors in the enclosure protect any occupants who
the staircase. may be on the staircase and passing a floor on which there is a fire. At ground
(iv) In balcony approach dwellings, where the staircase enclosure is entered · level, however, the direction of escape changes, becoming horizontal instead of
from the balcony or from a corridor which is entered from the balcony, the .) vertical, and the same measure of protection must be given to the hori;wntal
measure of safety is equivalent to that provided by a ventilated lobby and a part of the route against a fire on the ground floor as is given to the vertical part
sina1e staircase may again be regarded as safe in the third stage. Safety in the of the route against a fire on an upper floor.
sec~nd stage must, however, be assured as described earlier and the staircase. {ii) The mistake has been made of adopting the same form of enclosure at
must be enclosed and entered through smoke-stop doors on all floors. ground level as on the upper floors, i.e. of placing a door in the staircase
(v) An alternative method of protecting the staircase in a single staircase 17
16
LFB00060984/2

LFB00060984_0002
CP 3 :Chap. IV : 1962 CP 3 : Chap. IV : 1962

enclosure at ground level in a position similar to that on the upper floors. A (vii) A lift introduces a negligible fire hazard providing landing doors are
door in this position cannot serve the same purpose on the ground floor as on fire resisting, the motor room is at the top, and permanent ventilation is provided
the upper floors since on the upper floors the doors to the staircase are both a at the top of the shaft. There is, therefore, no objection to arranging lifts within
means of access to the stairs and a protection to people on the stairs, but on the a staircase enclosure on any floor, inCluding the entrance floor.
ground floor the door can only be a means of egress from the stairs; it cannot (viii) Stores and ancillary accommodation are often planned at ground level
protect people once they have passed through it. Such an arrangement does not, and the same protection should be provided between staircases and the public
therefore, meet the requirement described in c (i) above, that the whole of the space that serves such accommodation as is provided between staircases and the
route to the external air must be equally protected. public space that serves the flats themselves.
(iii) The mistake described in c {ii) above is illustrated in Fig. 6 which shows (ix) Easementfires can lead to particularly hazardous conditions and where
a possible form of ground floor arrangement for the upper floor plan shown in any dwelling has access to only one staircase, the staircase should not continue
Fig. 5. It is clear that Fig. 5 is satisfactory because the smoke-stop doors to the to a basement nor should a staircase to a basement open out of any part of the
staircases protect the staircases for the benefit of all the occupants above the building which has any connection to the main staircase. Even where every
floor on which the fire occurs. Yet the same arrangement is not satisfactory on dwelling has access to two staircases, neither staircase should be continued
the ground floor under the same circumstances (Fig. 6) because, in order to direct!y to a basement, but if one stops at ground level it need not be regarded as
reach the exit door from the building, it will be necessary for the persons on the unsafe to continue the other one indirectly, i.e. by placing a smoke-stop door
staircase to pass from the protection of the staircase through the smoke-logged across the basement stairs in order to protect the ground floor escape route
entrance corridor in order to make their escape. from the upper floors.
(iv) Another not uncommon mistake has been to discharge two staircases
through a common exit on the ground floor, e.g. into the main entrance. Whilst RECOI'vi:MEJ'lDATlONS
some means of access between the public space at ground level and at least one 205. GeneraL The principles expressed in general terms in Clauses 202 to 204
of the staircases will clearly be convenient, any such means of access will not above are set out below in the form of specific recommendations. The subject is
necessarily provide safe means of egress from the stairs. Moreover, if staircases one which calls for elasticity of approach, however, and the specific recommen~
are linked at ground level by the public space, there may be a risk that both will dations which follow should be interpreted in the light of the previous discussion.
be attacked by a fire commencing on the ground floor. Staircases should there~
fore be separated at ground level as they are on upper floors and each staircase 206. Stage one: internal planning of fiats and maisonnettes. a. Flats. All flats
should have a means of egress which is independent of and properly separated should have a private entrance hall in which there is no fire risk, and bedrooms
from the means of egress from the other staircase. should either:
(v} The measures of protection which are necessary are summarized in (i) open directly out of the entrance hall and be nearer to the entrance
Clause 204 b (vi). The ground floor plan illustrated in Fig. 7 meets the standard door of the flat than is the door of a dining room, a living room or a kitchen.
of protection recommended where there are two staircases and Fig. 8 illustrates a The doors of a dining room, living room and kitchen opening out of the hall
ground floor plan suitable for the upper floor plan shown in Fig. 1 and which should be fire resisting and fitted with a self-closing device, or [202 b (ii)J
meets the standard of protection recommended where there is only one staircase. (ii) have an alternative exit leading directly (i.e. not through an adjoining
The communicating doors shown in Figs. 7 and 8 are not, of course, essential. flat) to a main escape route outside the fiat. If it is necessary to pass from one
Should they be omitted there would be no need for protecting the stairs at. ground bedroom to another in order to reach the alternative exit, the bedrooms
level as described in Clause 204 b (vi). should be connected by a pass door or by an inner hall which is cut off by a
(vi) The exit at ground level should, as far as possible, be in a position which self-closing fire~resisting door from any other part of the flat. [202 b (iii)J
is free from risk from adjoinihg doors or windows. Whilst a degree of risk can b. lvfaismmettes. All ma.isonnettes should have a private entrance hall and an
be tolerated where there are .t\vo staircases with separate exits no such degree of alternative exit from the floor which is not the entrance floor. This exit should
risk should be accepted where there is only one staircase. One solution, if lead directly (i.e. not through an adjoining dwelling) to a main escape route
there is difficulty in the latter respect, is to provide two exits from the one outside the maisonnette. If the escape route from any room on the upper floor of
entrance hall, either of which may be subject to some risk, but not both at the the maisonnette passes across the landing at the head of the stairs, this landing
same time from the same fire {see Fig. 9). should be cut off from the stairs by a fire-resisting screen incorporating a smoke-
18 19
LFB00060984/3

LFB00060984_0003
CP 3 : Chap. IV : 1962

r stop door. Alternatively if the plan permits, pass doors between rooms may be
CP 3 : Chap. IV : 1962

provided in order to remove the necessity for passing across the landing at the ii Flat~ alte~ative
~ain s~airc~e, the entrance door of every such dweHing should either:
onlv Where any dwelling is not provided with an exit
head of the stairs. [202 c] to ; .
o en into a corridor and be not more than 15 ft away from a door m
207. Stage two: escape routes from flats or maisonnettes to main staircases. the ~~d~sing wall of a main staircase or from a smoke-stop doo.r acr~ss the
a. Dwellings witlz balcony approach. Escape from each dwelling should be corridor between the entrance d oor o f the dwelling and[203
a mam
c (iii)stutrcase.
and (vi)]
possible:
In the latter case if the entrance door of any other dwelling op~ns ~n~ the
(i) along the balcony to a main staircase without passing another
dwelling, or corridor on the staircase side of the smoke-stop door, there .s ou 1 e ~
alternative route from the entrance door of the ?rigin~l dwe.llm~ to a m~~n
(ii) along the balcony in opposite directions, to two main staircases, or staircase (e.g. along the corridor to anot11er mam staircase m t e ;;p~~~a:
(iii) along balconies on opposite sides of the block to at least one main direction) .. In al! cases tl:e corridor should be extended to an exter~203v e (li)]
staircase, [203 bJ described m b (1) D abo>e, or
b. Dwellings with corridor approach. (i) Flats or maisonnettes. Where every B o en into a corridor and be not more than 15ft away. from a s~oke-
dwelling is provided with an alternative exit to a main staircase: to do;r se aratin the corridor from a ventilated lobby W~lc~
opens _mto a
A. the alternative exit should be wholly independent of the normal
~Jn staircafe, is co~ected
only with public access space_, adJOinS an external
approach route, e.g. by a balcony leading directly to a main staircase or by a wall and has
a permanent opening in the external wall Wlt~;O~~e(~~~::J ~v~;
less than 15 sq ft, or
private staircase leading directly to the common corridor on another floor
(this staircase may serve more than one dwelling provided it can be entered . to a ventilated lobby and be not more than 15ft away from.a
from each flat independently of the normal approach route), [203 c (ii)J smocke:~~~ ~:or separating the lobby from a corri?or whi~ _1efd~~o :n~a~~
if the alternative exit is a balcony and, ln escaping from one dwelling, staircase All dwellings on the floor should open mto sue a o y .
such lobbies should adjoin an external wall and have a pennan~nt ope:~:
B.
it is necessary to pass another dweUing in order to reach a main staircase, the
balcony should lead in both directions to a staircase or the dwelling should in the external wall with a free area of not less than 15 sq [~;:d(ii~ =~ ~vii)J
have access to balconies on opposite sides of the block, [203 c (ii)J
c. the entrance doors of every dwelling should be not more than IOO ft b ot more than 100 ft from a main staircase if it lies ~etw~n two
from a main staircase, D.
main en
staircnses, .
and othenVJse not more t h an 50 ft from a mam[203stmrcase.
c (vii)]
o. the corridor should be extended to an external wall either directly or
through a lobby, or, if there is more than one staircase, through the staircases.
If the corridor does not exceed 30 ft in length a connection with the external 208. Stage three: main staircases in blocks of flats or maiso~nett.es. .
wall at one point will be sufficient. If the length exceeds 30 ft the corridor a. All main staircases should be enclosed throupho~t their height as ~~~r~~~~
should be extended to an external wan at its extremities, and intermediately in Clause 306 except under the circumstances descnbed me below. . .
if necessary, so that the distance bet\veen the points of contact with the ex~
ternal wails is nowhere more than 150ft measured along the corridor. At the b. No fiat, store, or other fire risk should open directly into a mam[~~r~)~
enclosure.
points of contact with the external wall there should be either a door to an
open balcony, or a window with opening lights having an area of not less c. If any dwelling has access to only one main staircase the staircase enclosure
than 15 sq ft when open, or a permanent opening with a free area of not less ~ ,.·-
should be entered on all floors from either:
than 15 sq ft. If the connection is through a staircase, there should be perma- {i) a balcony, or [204 b (iv)l
nent openings in the extemal wan of the staircase having a free area of not (ii) a ventilated lobby which adjoins an external wall and has a pe.rnm~ent
less than 15 sq ft in every storey height of the staircase. This connection opening in the external wall \vith a free area of not less th~ 15 sq ft an~ mto
should not be through the staircase in a single staircase building. r203 e (ii)J which no dwelling, store or other fire risk opens and which commurucates
20 only with the staircase, with a lift or lifts if desired and through a smoke-stop
21
LFB00060984/4

...
LFB00060984_0004
CP 3 :Chap. rv: 1962
CP 3 :Chap. IV : 1962
209. Smokf'~stopping between staircases. If more than one main staircase is
door with a common approach hall or corridor, or with an external balcony, provided in a building in order to comply with the recommendations of this
or [204 b (ill)] Code and the several staircases are inter-connected by a corridor or other en~
(iii) a corridor into which no dwelling, store or other fire risk opens and closed space, there should be at least one smoke-stop door across the corridor or
which communicates only with the staircase, with a lift or lifts if desired, enclosed space between the doors in the enclosing walls of any two staircases.
and, through a smoke-stop door either with a private or common balcony, [204 b (ii)J
or with a private or common ventilated lobby which adjoins an external wall
210. Refuse chutes. Hoppers to refuse chutes should be situated in well-ventilated
and has a permanent opening in the external wall with a free area of not less
positions, and the chutes should be continued upwards with an outlet above
than 15 sq ft. [204 b (v)J
roof level and enclosed as described in Clause 30fJ:. The hoppers should not be
d. At ground level a staircase enclosure should be arrunged so that the situfited within the enclosure of a staircase that provides the only means of
external exit door can be reached without passing through any door other than escape from any dwelling to the ground.
a door provided to form a draught lobby. The space which has to be tr1j.versed
between the bottom step of the staircase and the exit door should be regarded 211. Service ducts and service hatches. Service hatches for fuel or food and access
as an extension of the staircase enclosure and the walls enclosing it should be doors to ·service ducts should not open out of any staircase that provides the
subject to tbe same conditions as are recommended in a, b and c above for the only means of escape from any dwelling to the ground. Service ducts should be
walls enclosing a staircase, [204 c] protected as described in Clause 30.9 and service hatches should be constructed
e. Where the ground storey is designed as a permanently open pedestrian as described in Clause 310.
space, and is kept free from fire risk, the staircase enclosure at ground level may
he omitted. No enclosure is necessary above the level of the roof of the top
storey of the building. SECTION THREE: CONSTRUCTION
f. Where a dwelling has access to only one main staircase, that staircase 301. General. The foregoing recommendations on planning are made on the
should terminate at ground level and any staircase to a basement should be
assumption that the fire resistance of the structural elements of any building to
entered from the open air. The arrangement of the exit from the main staircase
which this part of the Code applies will not fall below the standards set out in
should be such as sufficiently to reduce the risk that smoke issuing from a fire
current building byelaws and regulations, and that the following recommenda-
in the basement or ground floor would obstruct the exit from the staircase.
tions on construction and .finishes, which cover items which are of particular
[204 c (ix)]
importance or which are additional to tho_se that are subject to building control,
g. Where all dwellings in a building lmve access to more than one main
are adopted. No recommendations are included for general standards of safety,
staircase, one of these should terminate at ground level, but the other may be
such as minimum height of balustrades, which may be considered matters of
continued to a basement provided the basement is cut off from the staircase by
normal good building practice.
two self-closing doors having a fire resistance of half an hour, one of which, at
It should be noted that the grade of fire resistance recommended below for
least, is at ground level, and the space between these two doors has a window
some parts of a structure may be in excess of that required in byelaws or regula-
or other means of ventilation to the. open air through an opening not less than
tions. Where this is so the view is held that a larger factor of safety is desirable
15 sq ft in area. [204 c (ix)]
than is provided by the byelaws or regulations.
h. Where a main staircase is not situated against an external wall, or has no
opening windows it should have a permanent vent at the top having a free area 302, Materials. Load-bearing elements of construction (other than stairs con-
of not less than 25 sq ft. [204 b (vii)] necting the upper and lower floors of maisonnettes) and elements of construction
j. Main staircases should have a minimum width of 3 ft 6 in measured for which the recommended or required fire resistance is one hour or more
between walls or 3 ft 3 in between a wall and the inside of a balustrade handrail. should be of non-combustible materials. Within dwellings, walls and ceilings
A continuous handrail should be provided. Treads should not be less than 9 in should be non-combustible, or they may have a Class 1 surface (as defined in B.S.
wide measured from riser to riser, and risers should not be more than 7~ in 476*) provided they possess this property inherently. Elsewhere wall and ceiling
high, and there should be not less than 2 nor more than 16 risers in a flight. linings should be non-combustible or of plasterboard. This recommendation
The head room should be not less than 6 ft 6 in measured vertically above • B.S. 476: Part 1, ' Fire tests on building materials and structures '.
the line of the nosings. 23
22
LFB00060984/5

LFB00060984_0005
CP 3 :Chap. IV: 1962 CP 3 :Chap. IV; 1962

applies also to solid staircase balustrades. Balustrades on main staircases should If the stairway separates one fiat or maisonnette from another, the stairway should
not be constructed of wood. Combustible finishes should not be used on the have a fire resistance equivalent to one hour or more.
floors of corridors or on the steps and landings of staircases which provide the Access to main staircases should be gained through doors of the type des-
only means of escape from a dwelling to the ground. cribed in Clause 310 c placed in the enclosing walls of the staircases. Access to
private escape stairs of the type described in Clause 207 b (i}, and the exit doors
303. Structure. The fire resistance of columns and load bearing walls, and of from such staircases on to common circulation spaces should, whether the stair-
beams and floors which are essential to the stability of a building in the event cases lead upwards or downwards, be of the type described in Clause 310 c.
' of a fire should be not less than one~and-a·half hours. Floors which are not T?ere should be no glazing or glass bricks in any internal enclosing wall of
essential to the stability of the building should have a fire resistance of not less a staJrcase if the recommended fire resistance of that wall is one hour or more.
than one hour unless they are the upper floors of maisonnettes when a fire
resistance of half an hour will be sufficient. The floor of any balcony that serves 307. Lift enclosures. The walls enclosing lift shafts should have a fire resistance
as an escape route from any dwelling should have a fire resistance of not less of not less than one hour, except where the lifts are in a staircase enclosure.
Shafts should have permanent vents at the top not less than 1 sq ft in area. Lift
than one hour.
motor rooms should be separated from lift shafts by the enclosing wall of the
304. Protection of structurnl mcmbeFS. Structural members which do not possess shaft or by the floor of the motor room. Landing doors in lift enclosures should
s.ufficient inherent fire resistance for their purpose must be protected, If this be as described in Clause 310 e.
protection takes the form of membrane or hollow protection weaknesses may
occur, e.g. at joints. For this reason systems of protection that consist entirely of 308. Refuse chutes. Refuse chutes should conform to the recommendations of
dry joints are not recommended. Protection of several members by means of CP 30?, ' The storage and collection of refuse from residential buildings '. The
continuous membrane, such as a suspended ceiling should not be used in any enclosmg structure should have a fire resistance of not less than one hour and
be of non-combustible materiaL
circumstances. If hollow protection takes the form of the encasement of indi-
vidual members by a membrane, e.g. plaster on expanded metal, the cavities
309. Service and ventilation ducts and trunks. Service ducts should be enclosed
which result should not pass through any floor or waU the recommended fire
by walls having a frre resistance of not less than one hour. Any doors for inspec-
resistance of which is one hour or more.
tion or access should, in conjunction with their frames, have a fire resistance of
305. Internal walls and partitions. Walls separating corridors from areas of floor half an hour. If the cross-sectional area of the duct exceeds 500 sq in it should
that are used for any purpose other than circulation should have a frre resistance be sealed where it passes a floor by carrying the floor through the duct. The
of not less than one hour. There should be no openings in such walls other than floor within the duct should be pierced for any service pipe or ventilation trunk
for doors or delivery hatches and no glazing other than fixed fanlights having a and should fit as closely as possible around any such pipe or trunk. Wrapping
fire resistance of half an hour placed over the entrance doors to dwellings. to the pipes, unless non-combustible, should not be carried through the thick-
ness of the floor.
306. Staircase enclosures. The internal enclosing walls of a main staircase should Ventilation trunks within service ducts constructed as described above may
have a fire resistance of not less than one hour, except that half an hour is be of metal or other non-combustible material. Ventilation ducts (not within
sufficient if the wall separates a staircase from: service ducts) should be made of clay or concrete blocks and should have a fire
a. a lobby of the type described in Clause 208 c (ii), or resistance of not less than one hour. Inlets should not be taken directly from
b. a common internal approach hall or corridor of the type described in dwellings into a common extract duct or trunk but should be connected either
Clause 208 c (ill), or through shunt flues or through horizontal branches having a length of not less
c. any common circulation space from which access can be gained to another than 3 ft. The junctions between horizontal branches from separate dwellings
staircase. and a common ver?cal ~uct or trunk should be separated one from another by at
least one storey he1gbt (1.e. they should not enter a common vertical duct at the
Any wall which separates a private escape staircase of the type described in same level). Ventilation openings should be no larger than is necessary for their
Clause 207 b (i) from any part of the dwelling which it serves should have a purpose.
fire resistance of not less than half an hour. If the wall separates the staircase Dual purpose ducts supplying combustion air to gas appliances and ventila-
from any other space, it should have a fire resistance of not less than one hour,
25
24
LFB00060984/6

LFB00060984_0006
CP 3 : Chap. IV : 1962
CP 3 :Chap. IV: 1962
ting the products of combustion from such appliances should be constructed
of non-combustible materials having a fire resistance of not less than one hour. SECI'ION FOUR: ANCILLARY ACCOI\1J.\110DATION

310. Doors'* and servic-e hatches. a. Entrance doors to dwelli11gs. All entrance 401. General. Ancillary accommodation in which a fire may occur, such as that
doors to dwellings should, unless they are entered from the open air, have a fire described in the following paragraphs, should not open directly out of any part
resistance, in conjunction with their frames, of half an hour. They should be of an exit that provides the only means of escape from any dwelling or except
hung on rising butt hinges or be fitted with some other self-closing device. for accommodation described in Clause 402 out of a main staircase.
b. Interior doors irz dwellings. \"/here the interior doors of flats are fire
resisting and fitted with a self-closing device in order to comply with the recom- 402. Reception desks and porters' offices. Provision may be made in a public
mendations of Clause 206 a (i), the doors should have a fire resistance of half entrance hall for a reception desk and for a few upholstered chairs. If an office
an hour, but rebates to frames need only be Y2 in deep. The self-closing device is required it should be separated from the entrance hall by a waH or screen
may consist of rising butt hinges. containing a smoke-stop door.
c. Doors in staircase enclosures. Internal doors in main staircase enclosures
403. Cupboanls and storerooms. Accommodation for clothes drying cabinets,
and exit doors from secondary escape staircases on to internal common drcu:la-
perambulators, cleaning materials, service intakes, etc., should be enclosed with
tion spaces should, in conjunction with their frames, have a fire resistance of half
walls, floors and ceilings having a fire resistance of one hour and be entered from
an hour. They should be single-leaf single-swing doors and should open in the
the conunon circulation space through a door having a fire resistance of half an
direction of escape. They should be fitted v.>:ith check action door closers, and
hour. The door should be provided with a check action closer.
should be marked with a warning notice intimating that the door is provided
for fire safety and should not be kept open. 404. Transformer chambers. Any transformer chamber forming part of a block
d. Smoke-stop doors. Smoke-stop doors should be fitted in walls or screens of flats or maisonnettes should be located against an external wall and should be
having a fire resistance of not less than half an hour. The walls or screens may entered only from outside the building.
incorporate fixed glazing if desired, so long as the fire resistance is maintained. Any wall or floor which separates a chamber from the remainder of Lhe
The doors should have a fire resistance of half an hour, but rebates to frames building, and any beam or stanchion situated within the chamber, should be of
need be only % in deep. They should preferably be single·leaf single-swing non-combustible construction and have a fire resistance of two hours. If more
doors and should open in the direction of escape. If placed across corridors in than, say, three gallons of oil are contained in any oil immersed gear, a retaining
such a position that they give access to staircases in either direction they should cill should be provided around the gear or at the door threshold.
be two-leaf doors having rebated meeting styles, each leaf single-swing and
swinging in the opposite direction to the other leaf. They should be fitted with 405, Boiler rooms. Boiler rooms should be separated from the remainder of the
check action door closers and marked as described in c above. building by walls and ceilings with a fire resistance of two hours. Further recom-
_e. Doors in lift shaft enclosures. The doors in the enclosing walls of lift shafts mendation on fire precautions for oil fired heating installations are contained
should, in conjunction with their frames, have a fire resistance of half an hour. in CP 3002, ' Oil firing '.
They should be fitted with an automatic closing device which will ensure that the
doors are kept closed at aU times except when persons are entering or leaving 406. Refuse chambers. Refuse chambers should have walls and floor or roof
the lift. The doors, when closed, must be effectively smoke tight. constructed of non-combustible and impervious materials and have a fire resis-
.f. Doors to lift motor rooms. The doors to lift motor rooms, where locat.ed tance of one hour. Further recommendations are contained in CP 306, ' Storage
within the building, should, in conjunction with their frames, have a fire resis- and collection of refuse from residential buildings'.
tance of half an hour, and be made self-dosing.
407. Lift motor .rooms. Lift motor rooms should preferably be sited at th; top
g. Service hatches for fuel or food. Where service hatches for fuel or food
of the shaft and should always be so sited if the lifts open out of a common
open out of an internal common circu:lation space, the hatches should have a
approach route or staircase that provides the only means of escape from a
fire resistance of half an hour. dwelling.
'" Particulars of tllfl fire resistancu obtained by gluzing in doors may be found in CP 152, 408. Ventilation plant rooms. These should be sited as recommended in Clause
' Oluzing and fixing of glass for buildings '.
401 above.
26
27
LFB00060984/7

LFB00060984_0007
CP 3 :Chap. IV: 1962
CP 3 :Chap. IV: 1962
entails the installation of fire lifts and internal fire mains or ' risers '. The loca~
SECTION FIVE: ENGINEERING SERVICES tion of fire main, fire lift and main staircase must be inter-related so that if a
fire lift opens into an area on an upper floor that might become smoke-logged,
501. Staircase and corridor lighting. Staircase and corridor lights should be ready access to the fire main can be had from another floor.
supplied by' protected circuits', i.e. sub-main circuits, exclusive to the staircase
and corridor lighting, and restricted to routes of negligible fire risk. Stair- 702. Access for fire appliances. A road or paved courtyard or other consolidated
cases should be illuminated by a circuit direct from the main switchboard, area having a minimum width of 10ft and capable of carrying a pumping appli-
with no switches on landings. Where a staircase has no natural lighting its ance weighing 10 tons should be provided and so sited as to enable the appliance
lighting circuit should be independent of the corridor lighting. to be brought to a reserved position within 60 ft of and in sight of the inlets to
any rising main. This position and the approach to it should as far as possible be
502. Gas and electricity services. Gas and electricity meters should preferably
rendered permanently free of obstruction from parked cars by the placing of
not be located in the entrance hall of a dwelling, but if a meter is so positioned,
removable bollards, etc., restricting parking to other areas. The approach roads
it should be contained within a suitably constructed metal cupboard. Any
should be designed for an appliance having a minimum turning circle of 27 ft
cupboard containing a meter should not be large enough to hold anything
radius, a wheel base approximately 13 ft 6 in and a track approximately 7ft 6 in.
other than the meter itself; gas and electricity meters should be in separate
Where approaches or forecourts are enclosed by fences or walls there should be
cupboards.
a clear opening which has a width of at least 8 ft 6 in and a height of at least
To facilitate the reading of meters from outside dwellings, the meters may
11 ft 6 in. Access gates should be openable from either side. Paving or roads
be located in a common circulation space. They should be placed in separate
around a building for the approach of wheeled ladders are not considered
cupboards of non-combnstibie construction with strong metal doors which
necessary where all the specific recommendations of this Code are followed.
should be provided with locks. If the meters are inset in corridor partitions they
should be separated from any accommodation at the back by non-combustible 703. E.'dernnl hydrants. Fire hydrants should be provided within the confines
construction having the same fire resistance as that of the corridor partitions. of the site if necessary, in consultation with the water and fire authorities.
For the planning and construction of transformer chamber and service intake
rooms, see Clauses 403 and 404. 704. Internal hydrants. a. Every building should be equipped with at least one
rising main to comply with the following recommendations:
503. Heating and ventilation. In entrance halls it is desirable to provide some
permanent form of heating which itself is entirely free from any fire risk, in order (i) In buildings of not more than 200 ft in height to the topmost floor
to discourage the use of portable heaters by tenants. on which there is a dwelling, rising mains may be ' dry '; in buildings of
Simple air extract systems are dealt with in Clause 309. Where a more com- greater height they should be ' wet '.
plicated ducted ventilation or air conditioning system is to be installed it should (ii) Outlets from rising mains should be provided on every floor above
be so designed that smoke or fire will not be carried to places where it would the .first in blocks of flats and on every entrance floor above the first floor
jeopardize escape. of the block in blocks of maisonnettes. They should be as near as possible to a
main staircase or a fire lift.
SECTION SIX: FIRE ALARl\:IS
(iii) Outlets should be so situated that no part of the building is more
601. General. A fire alarm system to warn the occupants is not considered than 200 ft from an outlet. The distance should be measured along the route
necessary, but reasonable means for calling the fire brigade should be provided. to be traversed including, in the case of maisonnettes, the distance up or down
It is recommended that the Postmaster--General should be approached at an a staircase to any point on a floor on which an outlet is not situated. If the
early stage with a view to providing at least one public telephone within the recommended distance cannot be achieved with one rising main, more than
block or a call box very near to it. one should be installed.
(iv) Dry rising mains should have a diameter of 4 in and should be fitted
with twin inlets for fire brigade connections. The inlets should be placed in a
SECTION SEVEN: FIRE BRIGADE FACiliTIES
convenient position on the external wall of the building not more than 3 ft
701. Genernl. In high blocks of flats it is essential that provision should be made above the level of the ground and they should be situated not more than
to assist the fire service in applying water to a fire as early as possible. This 29
zg
LFB00060984/8

LFB00060984_0008
CP 3 :Chap, IV : 1962 CP 3 :Chap. IV: 1962

40 ft away from the verticril position of the rising main. Inlets should be another staircase on the same floor to which there is access. In addition, if a
· contained in a glass~ fronted box, the door of which should be: fire lift is riot in a main staircase enclosure or within 15 ft of a door in a main
A. glazed with wired glass and indicated by the words ' FIRE staircase enclosure it should be within 15 ft of a smoke-stop door across a
BRIGADE DRY MAIN INLET' painted on the inner face of the glass, corridor that leads to a main staircase.
n. fastened only by means of a spring lock which can also be operated In order to ease the difficulty of accommodating the space necessary for over~
from the inside without the aid of a key after the glass has been broken, run at the top of the shaft for a high speed lift it is considered that a fire lift need
and not serve the top floor of a building provided the lift is not more than 15 ft from
a main staircase on the floor below, the hydrant outlet on the top floor is within
c. made large enough for hose to be connected to the inlets even if
the staircase enclosure or in a ventilated lobby adjoining the staircase, and the
the door cannot be opened and the only means of access is by breaking
number of fiats on the top floor does not exceed eight.
the glass. The size ofthe box should not be less than 22 in x 15 in x 12 in i'
' A fire lift should have a platform area of not less than 15~ sq ft and be
deep and it should have a fall of 1 in towards the front at the base. In
capable of carrying a load of 1200 lb. Its speed should be such that it can reach
selecting the positions for inlets, due regard should be paid to the position
the top floor from ground level within one minute. TI1e electric supply to any
of street hydrants.
fire lift should be provided by a sub-main circuit exclusive to the lift, except
(v) Wet rising mains in buildings more than 200 ft in height should be that where the fire lift is one of a battery of not more than six lifts (whether fire
fed from two independent sources of water supply. Duplicate booster lifts or not) the other lifts may be fed from the same supply. The cables supplying
pumps, operated by alternative sources of power and arranged to operate current to the lift motor should pass through routes of negligible fire risk.
automatically on a fall of pressure or a flow of water, should be provided to
ensure that a minimum pressure of 60 lb per sq in is maintained at the highest
outlet. The pressure at any outlet should not exceed 75 lb per sq in. SECfiON EIGHT: ADVICE TO TENANTS
b. In buildings which are designed to exceed 100 ft in height, the rising 801. General. Throughout this Code reference is made to various recommenda-
main should be installed as soon as the building exceeds that height and should tions with regard to fire safety which must depend to a large extent for their
be extended progressively as work on the building proqeeds, in order to provide effectiveness upon the co"operation of the tellll.nts. They must be able to under-
fire-fighting facilities during the various stages of construction. stand the reasons for certain principles of design and construction and be willing
705. Hydraulic hose reels. It is generally considered that hydraulic hose reels to ensure that such devices are well maintained and properly operated. In
cannot be justified in the interests of safety of life alone. The provision of such Section One of this Code, reference is made to the fact that the building must be
reels will, however, facilitate the work of the fire brigade and may result in designed and constructed in such a way that there is no undue risk of any of the
reducing ftre and water damage. - occupants being trapped by fire or smoke in any part of the building. This
must, to a greater or lesser extent, depend upon fire resisting doors being dosed
706. Fire lifts. A normal passenger lift or lifts should be arranged so as to be and not wedged open, which is so often the case; and likewise it must depend
available for the exclusive use of firemen in an emergency by providing at ground upon the condition of self-dosing door mechanisms.
level a switch in a glass fronted box marked ' FIRE SWITCH' which operates The crux of the whole problem however is that of fire prevention and there
a control whereby firemen can obtain the use of the lift without interference from is a special need in the case of high blocks of flats and maisonnettes to impress
the landing call points . .A.Jternatively, the fire switch may be in a box protected upon tenants certain elementary rules and principles. It is recommended, there-
by a metal cover and which can be unlocked by a key which would pass the dry fore, that advice should be promulgated for the benefit of tenants and distributed
riser box and any other locks which would require to be opened by the fire in rent books, rate demands and so on and also posted in the form of prornlnent
brigade. notices at appropriate points throughout the building. A suggested form is given
A sufficient number of lifts should be arranged as fire lifts to ensure that in in an appendix to this Code. The form of advice refers only to specific items as
fiats, every floor (except, under the circumstances described below, the top :,
they relate to multi-storey fiats and maisonnettes and does not attempt to deal
floor} and in maisonnettes every entnnce floor, has direct access to at least one with general fire precautions. If local authorities and other housing agencies
such lift. A fire lift should not be more than about 15 ft from a main staircase feel that more extensive advice on fire precautions should be made available,
if that is the only staircase to which there is access, or about 50 ft if there is this information can be obtained from the fire authority.
30 31
LFB00060984/9

LFB00060984_0009
CP 3 : Chap. IV : 1962 CP 3 :Chap. IV : 1962

APPENDIX FIGURES lLLUSTRATING PRINCIPLES


STATED IN CLAUSES 203 AND 204
FORM OF ADVICE TO TENANTS
KEY
This building has been designed and constructed to ensure the safety of all its
occupants in the event of fire. Your safety also, however, depends to some extent
FD = Fire resisting door
upon the manner in which you and other occupants observe certain basic rules.
SD = Smoke-stop door
C =Corridor
Sources of fire. L =Lobby
0 = Permanent opening
Most fires are caused by carelessness and one or more of the following may
W = Recommended opening window
be causes:
S = Staircase
Absence of adequate fire guards;
Airing of clothes;
Failure to disconnect radio and television sets from the main supply at tt~)J = Smoke from a fire originating in a fiat.
night and when away from home;
Careless use of matches and smoking materials;
Use and location of paraffin heaters.

Paraffin heaters.
These should, under no circumstances, be used in the entrance lobby or in
any position in the dwelling in which, should they be knocked over or catch fire
through draught, overfilling or defect, your escape from the dwelling would be
seriously endangered.

Self-dosing doors.
Self-closing doors can be found in most parts of this building, including the
entrance doors to flats and maisonnettes and doors to staircases, corridors, etc. Fig. 1
These are provided to arrest the spread of fire and smoke. THEY MUST NOT BE (~afe)

KEPT OPEN,
Make sure that the self-closing mechanism is effective at all times. If not,
report to the porter or caretaker or to the housing authority.
Before going to bed, close as many doors in your home as practicable as this
will help to prevent fire spread.
Abuse of fire--fighting equipment.
Fire fighting equipment, in the form of fire mains and outlets, is installed in
this building. Make it your business to see that such equipment is not interfered
with. If you find it apparently damaged, please report this immediately.
IN THE EVENT OF A FIRE, HOWEVER SMALL, CALL THE FIRE BRIGADE lMMIIDIATELY
(Insert calling procedure) Fig. 2
{unsafe)

32 :n
LFB00060984/10

LFB00060984_0010
CP3 :Chap. IV : 1962
CP3 : Chap. IV: 1962

Flat I Flat 2 Flat 3 Flat 4

0
w
w

a. Fire originating in fiut No. 1


Flat 8 Flat 7 Flot 6 Flat 5
..
'
Fig. 5

0 0

b. Fire originating in fiat No. 7


Fig. 3

--:-: :·.
Flat 8 Flat 7 Flat 6 Flat 5
Flat 2 /:t . Flat 3 Fl~t 5
Fig. 6
(Ullsufe)

Flat 2 Flat Flat 4

Flat 8 L Flat 7
FD

0
Flg. 4

Flat S Fiat 7 Flo t 6 Flat 5


F':tg. 7
(for upper floor plan see Fig. 5)
34
LFB00060984/11

35

·.~
LFB00060984_0011
CP 3 : Chap. IV : 1962

Fig. 8
(for upper !loor plan sec Fig, 1)

Fiat 2

Ftat 3

Fig. 9
LFB00060984/12

Printed In England by Gaylard & Son, London, S.E.H

LFB00060984_0012

You might also like