You are on page 1of 4

Specification sheet

Diesel
generator set
QSK60
series engine
1875-2250kVA 50 Hz
Data Center Continuous

Description
This Cummins commercial generator set is a fully Control system – The PowerCommand® electronic control
integrated power generation system, providing optimum is standard equipment and provides total genset system
performance, reliability, and versatility for stationary integration including automatic remote starting/stopping,
Standby, Prime power, and Continuous duty applications. precise frequency and voltage regulation, alarm and status
message display, AmpSentry™ protection, output
metering, auto-shutdown at fault detection and NFPA 110
Made by Cummins Level 1 compliance.
Data Center Continuous (DCC) - Applicable for supplying
power continuously to a constant or varying electrical load Cooling system - Standard integral set- mounted radiator
for unlimited hours in a data center application. system, designed and tested for rated ambient
temperatures, simplifies facility design requirements for
rejected heat.
Uptime Compliant - Meets the requirement of a Tier III
and IV data center site by being rated to run for unlimited NFPA - The genset accepts full rated load in a single step
hours of operation when loaded to 'N' demand for the in accordance with NFPA 110 for level 1 systems.
engine generator set.
Warranty and service - Backed by a comprehensive
warranty and worldwide distributor network.
Cummins heavy-duty engine - Rugged 4- cycle industrial
diesel delivers reliable power, low emissions and fast ISO8528-5 G3 Capable- Refer to factory for stie and
response to load changes. configuration specific transient performance
classification.
Permanent Magnet Generator (PMG) - Offers enhanced
motor starting and fault clearing short circuit capability.

Alternator - Several alternator sizes offer selectable motor


starting capability; low waveform distortion with non-linear
loads, fault clearing short-circuits capability, and class H
insulation.

Genset DCC rating Engine Model Controller Data Sheets


Model 50 Hz kVA (kW) 50 Hz 50 Hz 50 Hz
C2000D5 1875(1500) QSK60-G3 PC3.3 EA_S_CC_101
C2250D5 2000(1600) QSK60-G4 PC3.3 EA_S_CC_102
C2500D5A 2250 (1800) QSK60-G8 PC3.3 EA_S_CC_63

©2023 Cummins Inc. | EA_T_CC_19_EN (11/23)


Generator set specifications
Voltage regulation, no load to full load ± 0.5%
Random voltage variation ± 0.5%
Frequency regulation Isochronous
Random frequency variation ±0.25%
EMC compatibility Emissions to EN 61000-6-2:2005
Immunity to EN 61000-6-4:2007+A1:2011

Engine specifications
Design 4 cycle, 60° Vee, turbocharged and low temperature after-cooled
Bore 159 mm (6.25 in)
Stroke 190 mm (7.48 in)
Displacement 60.2 L (3673 in3)
Cylinder block Cast iron, 60ºV 16 cylinder
Battery capacity 2200CCA at ambient temperature 0ºF to 32ºF (-18 °C to 0°C)
Battery charging alternator 40 amps
Starting voltage 24- volt, negative ground
Fuel system Direct injection
Fuel filter Triple element Spin on fuel filters with water separator
Air cleaner type Dry replaceable element
Lube oil filter type(s) Four spin-on, combination full flow and bypass filters
Standard cooling system High ambient cooling system

Alternator specifications
Design Brushless, 4 pole, drip-proof revolving field
Rotor Direct coupled by flexible disc
Insulation system Class H
Standard temperature rise 125°C
Exciter type PMG (Permanent Magnet Generator)
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion No load < 1.5%. Non distorting balanced linear load < 5%
Telephone harmonic factor (THF) < 3%

Available voltages
50 Hz Line-Neutral/Line-Line
 220/380  230/400  240/415  6060/10500
 6350/11000
*Note: Consult factory for other voltage.

Generator set options


Engine Control panel Alternator Generator set
● Normal duty Air Cleaner ● PC3.3 ● Anti-condensation heater ● Standard spring mounting
○ Battery charger
● Coolant heater w/temp ○ Multiple language support ○ Stator winding temp sensor
adjust, forced pump 380 ○ Manual available in
○ User-configurable relays ● Exciter voltage regulator
V,9kW multiple languages
○ Digital input/output (PMG)
○ Engine toolkit ○ Heater control cabinet
○ Independent Hour Meter ○ Generator bearing temp
sensor.
● Low Coolant Level
Warning/Shutdown
○ High Bearing Temp Warning
○ High Alternator Temp Shutdown
○ Exhaust Gas Temp Monitoring
Cooling system Exhaust System Warranty
● High Ambient cooling ● Industrial Silencer;In-Line Entry ● Comprehensive warranty ● Standard
system system (Consult factory for ○ Option
○ Residential Silencer, Side Entry
availability)
○ Enhanced High Ambient Silencer
cooling system ● Flexible
○ Remote radiator interface ● System Fixing Kit
*Note: Some options may not be available on all models – consult factory for availability.

©2023 Cummins Inc. | EA_T_CC_19_EN (11/23)


PowerCommand 3.3 control system
Engine data
• DC voltage.
• Engine speed
• Lube oil pressure and temperature.
• Coolant temperature
• Comprehensive FAE data (where applicable).
Other data
• Genset model data.
• Start attempts, starts, running hours, kW hours.
• Load profile (operating hours at % load in 5% increments).
Control system • Fault history.
• Data logging and fault simulation (requires InPower).
The PowerCommand control system is an integrated
microprocessor based generator set control system providing Standard control functions
voltage regulation, engine protection, alternator protection,
operator interface and isochronous governing. Digital governing (optional)
AmpSentry – Includes integral AmpSentry protection, which • Integrated digital electronic isochronous governor.
provides a full range of alternator protection functions that are • Temperature dynamic governing.
matched to the alternator provided. Digital voltage regulation
Power management – Control function provides battery • Integrated digital electronic voltage regulator.
monitoring and testing features and smart starting control system.
• 3-phase, 4-wire Line-to-Line sensing.
Advanced control methodology – Three phase sensing, full
wave rectified voltage regulation, with a PWM output for stable • Configurable torque matching.
operation with all load types. AmpSentry AC protection
Communications interface – Control comes standard with • AmpSentry protective relay.
PCCNet and Modbus interface. • Over current and short circuit shutdown.
Service - InPower™ PC-based service tool available for detailed • Over current warning.
diagnostics, setup, data logging and fault simulation.
• Single and three phase fault regulation.
Reliable design – The control system is designed for reliable
• Over and under voltage shutdown.
operation in harsh environment.
Multi-language support • Over and under frequency shutdown.
• Overload warning with alarm contact.
Operator panel features • Reverse power and reverse Var shutdown.
Operator panel features – The operator panel, in addition to the • Field overload.
alternator, displays the Utility/AC Bus data.
Engine protection
Operator/display functions
• Battery voltage monitoring, protection and testing.
• 320 x 240 pixels graphic LED backlight LCD.
• Over speed shutdown.
• Auto, manual, start, stop, fault reset and lamp test/panel lamp
• Low oil pressure warning and shutdown.
switches.
• High coolant temperature warning and shutdown.
• Alpha-numeric display with pushbuttons.
• Low coolant level warning or shutdown.
• LED lamps indicating genset running, remote start,not in auto,
common shutdown, common warning,manual run mode, auto • Low coolant temperature warning.
mode and stop. • Fail to start (over crank) shutdown.
Paralleling control functions • Fail to crank shutdown.
• Digital frequency synchronization and voltage matching. • Cranking lockout
• Isochronous kW and kvar load sharing controls • Sensor failure indication.
• Droop kW and kvar control. • Low fuel level warning or shutdown
• Sync check. • Fuel-in-rupture-basin warning or shutdown.
• Extended paralleling (Peak Shave/Base Load). • Full authority electronic engine protection.
• Digital power transfer control (AMF) provides load transfer Control functions
operation in open or closed transition or soft (ramping) transfer • Time delay start and cool down.
mode
• Real time clock for fault and event time stamping.
Alternator data
• Exerciser clock and time of day start/stop
• Line-to-neutral and Line-to-Line AC volts.
• Data logging.
• 3-phase AC current.
• Cycle cranking.
• Frequency.
• Load shed.
• kW, kVar, power factor kVA (three phase and total).
• Configurable inputs and outputs (4).
• Remote emergency stop.
Options
• Auxiliary output relays (2).

©2023 Cummins Inc. | EA_T_CC_19_EN (11/23)


Ratings definitions

Data Center Continuous (DCC):


Applicable for supplying power continuously to a constant or varying electrical load for unlimited hours in a data center application.

Dimension and Weight

Do not use for installation design.


This outline drawing is for reference only. See respective model data sheet for specific model outline drawing number.
Model Dim “A” mm Dim “B” mm Dim “C” mm Set weight* dry kg Set Weight* wet kg
C2000D5¹ 6206 2494 2800 16367 17041
C2250D5¹ 6206 2494 2800 16567 17241
C2500D5A² 6206 2494 2800 16767 17441
Note: ¹ Weights represent a set with standard features for LV Alternator. ² Weights represent a set with standard features for HV Alternator.
See outline drawings for weights of other configurations.

Codes and standards

This product was manufactured in a plant


whose quality management system is This generator set has been designed to
ISO 9001 registered as being in conformity with ISO 8528 comply with ISO 8528 standards.
ISO 9001.

This generator set is available as CE This generator set is available as UKCA


marked. marked.

This generator set has been designed to be


AS 3000 compatible with AS/NZS 3000 Standard.

For more information contact your local Cummins distributor

©2023 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry and InPower are trademarks of Cummins Inc. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
EA_T_CC_19_EN (11/23)