You are on page 1of 12

DATASHEET ALTERNATOR

Kohler Alternator description KH01221T


Alternator type KH01221TO4N

- GENERAL CHARACTERISTICS -
Voltage Type (V) 400/230 Altitude (m) 0-1000
Number of Phase Three phase AVR Regulation Yes
Number of pole 4 Indication of protection IP23

Winding type Standard


Winding pitch 2/3
Capacity for maintaining short circuit at 2.7 ln for 5 s Yes

Insulation Protection Type : NORMAL


Imprégnation adaptée pour : - Clean air / Humidity <=95%

Efficiency & Power

Frequency (Hz) 50 Hz Nominal voltage (V) 400

Insulation System Class H


Class temp Rise Class H Class F Class B
Rated temp Rise (K) / 125 K / 40°C 130 K / 25°C 150K / 40°C 163 K / 27°C 105 K / 40°C 80 K / 40°C
Ambiant temp (°C) continuous standby (*) standby standby continuous continuous
Nominal Rating(kVA) 230.0 230.0 244.0 253.0 209.0 184.0
Nominal Rating(kW) 184.0 184.0 195.2 202.4 167.2 147.2
Efficiency 100% 91.7 91.7 91.4 91.3 92.0 92.4
(*) UL

- ELECTRICAL CHARACTERISTICS -
Voltage regulation at established rating (+/- %) 0.50
T° class (H/125K), continuous 40°C H / 125°K
T° class (H/163K), standby 27°C H / 163°K
Wave form : NEMA=TIF <50
Unbalanced load acceptance ratio (%) 8
Number of wires 06
Total Harmonic Distortion in no-load DHT (%) <2.5
Wave form : CEI=FHT <2
Total Harmonic Distortion, on linear load DHT (%) <5
Technology Brushless
L-L Harmonic Maximum - Single (%) 1,8
Deviation Factor (%) 3.0

IND-C
STATUS/ETAT : ACTIF
The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
DATASHEET ALTERNATOR
Kohler Alternator description KH01221T
Alternator type KH01221TO4N

Reactances
Saturated Unsaturated

Direct axis synchro reactance (Xd) (%) 272.0 340.0


Direct axis transcient reactance (X'd) (%) 17.1 21.4
Direct axis subtranscient reactance (X''d) (%) 13.7 17.1
Quadra axis synchro reactance (Xq) (%) 138.4 173.0
Quadra axis subtranscient reactance (X"q) (%) 17.40 21.75
Zero sequence reactance (Xo) (%) 0.70 0.70
Negative sequence reactance (X2) (%) 15.58 19.48
Reactance desaturation coef 1.250

(*) Reactances provided for Class H 125°C/40°C PRIME

Short circuit ratio

Short circuit ratio (Kcc) 0.371


Exciter time constant (Te)
Subtranscient time constant (T"d) (ms) 10.000
Short circuit transcient time constant (T'd) (ms) 100.000
Open circuit time constant (T'do) (ms) 1983.00
Subtranscient time constant (T"q) (ms) 10.0
Leakage stator reactance (Xa)(%) 0.85
Stator Resistance (Ra)(%) 0.056
Armature time constant (Ta) (ms) 15.000

No load excitation current (io) (A) 1.01


Full load excitation current (ic) (A) 3.84
Full load excitation voltage (uc) (V) 37.4
Heat rejected to ambient air (kW) 16.58
No load losses (W) 3298.52
Stator resistance (for 20°C ambient ) (Ω) 0.03914
Rotor resistance (for 20°C ambient ) (Ω) 0.54154
Exciter resistance - stator/inductor (for 20° ambient ) (Ω) 10.010
Exciter resistance - rotor/armature (for 20° ambient ) (Ω) 0.100

R0 resistor (homopolar) 1.2000


R2 resistor (reverse) 9.700
X/R ratio 4.4

Recovery time (Delta U = 20% transcient) (ms) 500


Engine start (Delta U = 20% perm. or 30% trans.) (kVA) 524.05
Transcient dip (4/4 load) - PF : 0,8 AR (%) 14.00

IND-C
STATUS/ETAT : ACTIF
The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
DATASHEET ALTERNATOR
Kohler Alternator description KH01221T
Alternator type KH01221TO4N

- Additional electrical characteristics -


Winding X1, X2 auxiliary resistance (for 20° ambient ) (Ω) 0.000
Winding Z1, Z2 auxiliary resistance (for 20° ambient ) (Ω) 0.510
Auxiliary winding X1, X2 excitation voltage at no load (V) 0.0
Auxiliary winding Z1, Z2 excitation voltage at no load (V) 8.1

- MECHANICAL CHARACTERISTICS -
Number of bearing 1
Overspeed (rpm) 2250
Coupling Direct
Air flow (m3/s) 0.480
Net Weight of the alternator with single bearing config (kg) 599.0

IND-C
STATUS/ETAT : ACTIF
The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
DATASHEET ALTERNATOR
Kohler Alternator description KH01221T
Alternator type KH01221TO4N

- TECHNICAL CURVES -
Motor starting curve locked rotor (0,6PF)

Motor starting curve locked rotor (0,3PF)

IND-C
STATUS/ETAT : ACTIF
The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
DATASHEET ALTERNATOR
Kohler Alternator description KH01221T
Alternator type KH01221TO4N

Efficiencies curve (by excitation system)

Loading curve (by excitation system)

IND-C
STATUS/ETAT : ACTIF
The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
DATASHEET ALTERNATOR
Kohler Alternator description KH01221T
Alternator type KH01221TO4N

Short circuit curve at no load and rated speed

Influence due to connection


Curves shown are for star (Y) connection
For other connections, use the following multiplication factors:
- Series delta : current value x 1.732
- Parallel star : current value x 2
Influence due to short-circuit
Curves are based on a three-phase short-circuit. For the other types of short-circuit, use the following multiplication
factors:
(*) For configuration TO4N/TO4D/TO4R, Capacity for maintaining short circuit at 2.7 ln for 5 s = YES

IND-C
STATUS/ETAT : ACTIF
The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
DATASHEET ALTERNATOR
Kohler Alternator description KH01221T
Alternator type KH01221TO4N

Rejection curve (by excitation system)

Capability curve (PQ diagram)

IND-C
STATUS/ETAT : ACTIF
The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
DATASHEET ALTERNATOR
Kohler Alternator description KH01221T
Alternator type KH01221TO4N

Thermal stator current limit curve

IND-C
STATUS/ETAT : ACTIF
The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
DATASHEET ALTERNATOR
Kohler Alternator description KH01221T
Alternator type KH01221TO4N

- DIMENSIONS -
Overall dimension drawing (Single bearing)

IND-C
STATUS/ETAT : ACTIF
The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
DATASHEET ALTERNATOR
Kohler Alternator description KH01221T
Alternator type KH01221TO4N

Overall dimension drawing (Two bearings)

IND-C
STATUS/ETAT : ACTIF
The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
DATASHEET ALTERNATOR
Kohler Alternator description KH01221T
Alternator type KH01221TO4N

- TORSIONAL ANALYSIS DATA -


Rotation part drawing for torsional vibration calculation (Single bearing)

IND-C
STATUS/ETAT : ACTIF
The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
DATASHEET ALTERNATOR
Kohler Alternator description KH01221T
Alternator type KH01221TO4N

Rotation part drawing for torsional vibration calculation (Two bearings)

IND-C
STATUS/ETAT : ACTIF
The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.

You might also like