You are on page 1of 36

POWER SYSTEM PROTECTION

UNIT-1:- Introduction and components of a protection


system

Describe the essential qualities of protective relaying.


1. Sensitivity: Detects and responds to even small abnormalities or faults.
2. Selectivity: Discriminates between different types of faults to
isolate theaffected area accurately.
3. Speed: Provides fast response to faults to limit damage and maintain
systemstability.
4. Reliability: Ensures reliable operation to safeguard equipment and
personnel.
5. Coordination: Coordinates with other protective devices to ensure
selectiveoperation and minimize system downtime.
6. Accuracy: Provides precise and accurate detection and
response toabnormalities or faults.
7. Adaptability: Can be adjusted or configured to suit the specific
requirementsof the power system.

Discuss the nature and causes of faults in a power system.


1. Short Circuit: Direct connection between two or more conductors,
causingexcessive current flow.
2. Ground Fault: Connection between a live conductor and ground,
leading tocurrent leakage.
3. Overload: Excessive current drawn by a load, exceeding the rated
capacity ofthe equipment.
4. Lightning: Atmospheric discharge of electricity, striking power
lines orequipment.
5. Equipment Failure: Malfunction or breakdown of electrical equipment,
leadingto system instability.
6. Human Error: Improper operation or maintenance practices
resulting insystem faults.
7. Environmental Factors: Natural phenomena such as storms, floods, or
animalinterference affecting power lines.
Explain the overlapping of protective zones with neat sketch.
1. Protective zones overlap to ensure comprehensive coverage and coordination
in power systems.
2. Each protective device, such as relays or circuit breakers, is assigned a specific
protection zone.
3. The boundaries of these protection zones are defined based on system
topology and operational requirements.
4. Overlapping zones enable multiple protective devices to respond to faults and
abnormalities within their respective areas.
5. The overlapping regions act as backup layers of protection, ensuring reliability
and minimizing the risk of system-wide failures.
6. Coordination between protective devices is crucial to prevent unnecessary
tripping and maintain system stability.
Discuss the phenomenon of arc extinction in circuit breakers
and its extingush methods.
• Arc Extinction:
• When a circuit breaker interrupts a high-current circuit, it creates an
electrical arc between the contacts.
• The arc generates intense heat and ionizes the surrounding air,
sustaining the flow of current even after the contacts separate.
• Arc Extinction Methods:
1. Cooling: Introducing a cooling medium, such as compressed air or
insulating gas (e.g., sulfur hexafluoride), helps dissipate heat and extinguish the
arc.
2. Lengthening the Arc: Arcing contacts can be designed to elongate the arc
path, increasing resistance and facilitating extinction.
3. Arc Chutes: Arc chutes consist of metal plates or magnetic blowout coils
that divert and split the arc, aiding in its extinction.
4. Magnetic Blowout: Utilizing magnetic forces to blow the arc into an arc
chute, where it is rapidly cooled and extinguished.
5. Deionization: Injecting a deionizing material or using a deionization
chamber absorbs free electrons, reducing ionization and aiding in arc extinction.

With the help of equivalent circuit of a current transformer


derive its dynamic behaviour when subjected to fault.

Here's the dynamic behavior of the CT during a fault:


1. Primary Side (Fault Condition):
• The fault current I_fault flows through the primary winding of the
CT.
• Due to the inductance (L_p) of the primary winding, there will be a
delay in the rise of the current, governed by the equation V = L_p
di/dt, where V is the voltage across the primary winding and di/dt
is the rate of change of current.
• The resistance (R_p) of the primary winding causes some voltage
drop, contributing to the total voltage across the primary side.
2. Secondary Side (Fault Condition):
• The fault current I_fault induces a corresponding current in the
secondary winding according to the turns ratio of the CT.
• The ideal current source (I_s) in parallel with the secondary winding
impedance (Z_s) represents this induced secondary current.
• The secondary current will be proportional to the primary fault
current, scaled by the turns ratio of the CT.
3. Operation of Protective Relay:
• The secondary current induced by the fault may exceed the
threshold of the protective relay.
• Once the secondary current exceeds the relay's threshold, the relay
operates, sending a trip signal to the circuit breaker to isolate the
faulted portion of the system.

Explain primary and back up protection by the protective


relaying equipment.
1. Primary Protection: The first line of defense that quickly detects and
isolatesfaults within its designated zone.
2. Back-Up Protection: Acts as a secondary layer of defense, providing
additionalcoverage in case the primary protection fails.
3. Primary protection operates with minimal time delay to swiftly clear
faults andprevent damage to equipment.
4. Back-up protection ensures system reliability by stepping in if the
primaryprotection malfunctions or is unable to clear the fault.
5. Both primary and back-up protection devices coordinate to
providecomprehensive coverage and maintain system stability.
6. Primary protection is typically set to operate faster than back-up
protection tominimize disruption and ensure selective tripping.
7. The coordination between primary and back-up protection devices is
crucialfor reliable and efficient operation of power systems.

Instrument transformer in power system protection:-


1. Function: Instrument transformers scale down high voltage and current
levels
to safer and more manageable levels for measurement and protection.
2. Types: Current Transformers (CTs) step down high currents, while
VoltageTransformers (VTs) step down high voltages.
3. Placement: CTs are typically connected in series with the line or load,
whileVTs are connected in parallel.
4. Accuracy: They provide precise representations of primary voltage or
currentto protective relays, ensuring accurate fault detection and
response.
5. Isolation: Instrument transformers electrically isolate high
voltage/powersystems from protective relays and meters, ensuring
safety.
6. Reliability: Designed to withstand harsh conditions, they offer
reliableoperation even under extreme circumstances.
7. Integration: Instrument transformers are essential components of
protective
relay schemes, providing crucial input for effective power system
protection.
What do you mean by Zone of protection. List and explain essential
qualities of a protective relay.
Zone of Protection :

1. Definition: Zone of Protection refers to the area of the power system that
a protective relay is responsible for monitoring and controlling.
2. Purpose: It ensures that the protective relay detects and responds to faults
within its designated area, preventing damage to equipment and
ensuring system stability.

Essential Qualities of a Protective Relay :

1. Sensitivity: The relay must detect faults accurately, even at low levels of
fault
current.
2. Selectivity: It should discriminate between faults occurring within its
zone andthose outside, avoiding unnecessary tripping.
3. Speed: A fast response time is critical to isolate faults promptly and
preventfurther damage.
4. Reliability: The relay must operate reliably under various operating
conditionsand environmental factors.
5. Security: It should be immune to external disturbances and
intentionaltampering.
6. Stability: The relay should not operate erroneously due to system
transientsor disturbances.
7. Ease of Maintenance: Simple to install, calibrate, and maintain to
minimizedowntime and ensure continuous protection.
Briefly describe SF6 circuit breaker and for what voltage ranges it
is recommended.
1. Description: SF6 circuit breakers use sulfur hexafluoride gas as the
insulatingand arc-quenching medium.
2. Working Principle: When a fault occurs, the SF6 gas extinguishes the
arc byabsorbing the released energy and rapidly cooling the contacts.
3. Advantages:
• High dielectric strength.
• Excellent arc-extinguishing
• properties.Compact design.
• Minimal maintenance requirements.
4. Applications:
• Used in medium to high voltage power systems, typically ranging
from33 kV to 765 kV.
• Widely employed in substations, power plants, and industrial
facilitiesfor reliable circuit protection.
5. Recommended Voltage Ranges :
• SF6 circuit breakers are suitable for voltage ranges above 33 kV
up toultra-high voltage levels of 765 kV.
• Commonly used in transmission and distribution networks
wherehigher voltage levels are present.

UNIT 2:- FAULT AND OVERCURRENT PROTECTION

Review of Fault Analysis and Overcurrent Protection :

1. Faults:
• Common faults include short circuits, ground faults, and open
circuits.
• Short circuits occur when two conductors with different
potentialscome into contact.
• Ground faults involve unintended connections between live
conductorsand ground.
• Open circuits occur when there is a break in the circuit path.
2. Overcurrent Protection :
• Overcurrent protection devices, such as fuses and circuit
breakers,safeguard electrical circuits from excessive currents.
• Fuses operate by melting a conductor when subjected to
excessivecurrent, interrupting the circuit.
• Circuit breakers use electromechanical or electronic mechanisms
to tripand open the circuit when an overcurrent condition is
detected.
3. Fault Analysis :
• Fault analysis involves identifying and analyzing different types of
faultsto ensure the safety and reliability of electrical systems.
• Techniques such as fault tree analysis, relay coordination
studies, andtransient analysis are employed to analyze faults
and develop protective measures.
4. Protection Coordination :
• Coordination between protective devices, such as relays, fuses,
and circuit breakers, is crucial to ensure selective tripping and
minimizedowntime during faults.
• Protective relay settings must be carefully coordinated to ensure
that the device nearest to the fault operates and isolates the
faulted sectionwhile avoiding unnecessary tripping of upstream
devices.
5. Safety Measures:
• Adequate grounding and insulation resistance testing are
essential toprevent faults and ensure the integrity of electrical
systems.
• Regular maintenance and testing of protective devices are
necessary toverify their proper operation and reliability during
fault conditions.
6. Future Trends :
• Advanced technologies, such as digital relays, adaptive
protection schemes, and real-time fault monitoring, are
increasingly being adopted to enhance fault analysis and
protection in modern electricalsystems.

What is negative sequence relay. Explain its working and application


with the help of diagram.
1. Definition: A negative sequence relay is a protective relay designed to
detect
unbalanced conditions in a three-phase power system, particularly
when thenegative sequence component is predominant.
2. Working Principle: It monitors the negative sequence voltage or
currentcomponent of the system. If this component exceeds a set
threshold, indicating an unbalanced condition, the relay operates to
trip the circuit breaker and isolate the fault.
3. Application: Negative sequence relays are used in power systems to
protect against faults such as phase-to-phase or phase-to-ground faults,
unbalancedloads, and motor protection.
4. Operation: When unbalanced conditions occur, such as due to a fault
or severe unbalanced load, the negative sequence relay detects the
excessive
negative sequence component and sends a trip signal to the circuit
breaker,isolating the faulted section of the system.
Introduction to Overcurrent Protection and Overcurrent Relay Coordination :

1. Overcurrent Protection :
• Overcurrent protection is a fundamental aspect of electrical
system protection, aimed at safeguarding equipment and
personnel from theharmful effects of excessive current.
• It involves the use of protective devices such as fuses, circuit
breakers,and relays to detect and interrupt current flows
exceeding predetermined thresholds.
• Overcurrent events can result from faults, overloads, or short
circuitswithin the electrical system.
2. Types of Overcurrent Protection Devices :
• Fuses: Operate by melting a conductor when subjected to excessive
current.
• Circuit Breakers: Mechanically or electronically trip to open the
circuitupon detecting overcurrent conditions.
• Relays: Monitoring devices that initiate tripping action in circuit
breakers or other protective devices in response to abnormal
currentlevels.
3. Overcurrent Relay Coordination :
• Overcurrent relay coordination involves the systematic setting of
relay operating characteristics to ensure the selective operation of
protectivedevices.
• The objective is to ensure that during a fault, only the
nearest protective device operates to isolate the faulted
section while minimizing disruption to the rest of the
system.
• Coordination ensures that protective devices upstream of the
faultedsection do not unnecessarily trip, thereby maintaining
continuity of service and minimizing downtime.
4. Importance of Coordination :
• Proper coordination prevents unnecessary interruptions and
ensuresthat faults are isolated swiftly, minimizing damage and
downtime.
• It improves system reliability, safety, and operational
efficiency byoptimizing the response of protective devices to
fault conditions.
• Effective coordination reduces the risk of cascading failures
andenhances overall system performance.
5. Methods of Coordination:
• Time Grading: Setting the time-delay characteristics of
relays toachieve sequential operation during fault
conditions.
• Current Grading: Setting the pickup current levels of relays such
thatdownstream devices have higher pickup settings than
upstream devices.
• Inverse Time Grading: Adjusting the time-delay characteristics of
relays based on the magnitude of fault current, with shorter time
delaysfor higher fault currents.
6. Considerations:
• System characteristics, fault currents, and load conditions must be
consideredwhen designing and implementing overcurrent protection
schemes.
• Regular maintenance and testing of protective devices are essential to
ensuretheir proper functioning.
Why are IDMT relay widely used for over-current protection?

IDMT relays are commonly used for overcurrent protection because:


1.Simple Design: Easy to understand and use.
2. Flexible Settings:
• Can be easily adjusted to match specific current characteristics of
equipment.
3. Fast Response:
• Quickly detects overcurrent faults and trips the circuit to prevent
damage.
4. Selective Operation:
• Ensures that only the affected part of the system is isolated
during a fault, minimizing disruption.
5. Reliable Performance:
• Offers consistent and dependable protection against overcurrent
conditions.
6. Cost-Effective Solution:
• Provides effective protection at a relatively low cost compared to other methods.
7.Compatibility: Works with various systems and equipment.
UNIT 3: EQUPMENT PROTECTION SCHEMES

Explain the construction and operation of non


directionalovercurrent relay.
1. Construction:
• Non-directional overcurrent relays consist of a current transformer
(CT),a relay coil, a magnetic core, and trip contacts.
• The relay coil is energized by the secondary current of the CT.
2. Operation:
• When the current flowing through the CT exceeds the preset
threshold,the relay coil generates a magnetic field.
• This magnetic field attracts the armature, causing the trip
contacts toclose and initiate the trip signal.
• The trip signal is then sent to downstream circuit breakers or
other protective devices to isolate the faulted section of the
electrical system.
3. Sensitivity Setting :
• The sensitivity of the relay, i.e., the current threshold at which it
operates, can be adjusted to suit specific protection requirements.
• It must be set above the normal operating current but below the
maximum permissible current to avoid unnecessary tripping during
transient conditions.
4. Instantaneous Trip Feature :
• Some non-directional overcurrent relays include an instantaneous trip
feature, where the relay operates immediately upon detecting a fault
without any time delay.
• This feature is typically used for fast-acting protection against severe
faults.
5. Applications:
• Non-directional overcurrent relays are commonly used for general
protection of distribution feeders, transformers, motors, and other
electrical equipment.
• They provide reliable and cost-effective protection against overcurrent
conditions in various industrial and utility applications.
6. Maintenance:
• Periodic testing and calibration are essential to ensure the proper
functioning of non-directional overcurrent relays.
• Regular maintenance helps to identify any issues or faults in the relay
and ensures its continued reliability in protecting the electrical system.

Explain the construction and operation of directional overcurrent relay.


1. Construction:
• Typically consists of a current transformer (CT), relay coil,
magnetic core, directional unit (such as polarized relay or digital
processor), andtrip contacts.
• The directional unit is crucial for determining the direction of
faultcurrents.
2. Operation:
• When the current flowing through the CT exceeds a
predeterminedthreshold, it energizes the relay coil.
• The directional unit compares the phase angles of the current
andvoltage signals to determine the direction of fault current
flow.
• If the fault current flows in the desired direction, the relay
operates andinitiates trip contacts to isolate the faulty section of
the system.
3. Directional Sensing :
• Directional relays use various methods to sense the direction of
fault currents, such as comparison of voltage and current phase
angles ordirectional elements in digital relays.
4. Applications
:
• Directional overcurrent relays are commonly used in
interconnected power systems or radial feeders where fault
direction affects protectioncoordination.
• They are crucial for protecting generators, transformers,
transmissionlines, and distribution feeders.
5. Coordination:
• Coordination with other protective devices, such as circuit
breakers andrelays, is essential to ensure selective operation and
minimize unnecessary system outages.
6. Maintenance :
• Regular testing, calibration, and maintenance are necessary to
ensure
the proper functioning of directional overcurrent relays and to
maintainsystem reliability and safety.
Draw and explain about differential relay and its types in detail.
Differential Relay :

1. Purpose:
• Protects electrical equipment by detecting and isolating internal faults.
2. Construction:
• Consists of a measuring element that compares currents entering and
leaving theprotected zone.
• Typically employs a core with current transformers (CTs) on both the input
and
output sides.
3. Operation:
• Compares the net current entering and leaving the protected zone.
• If the currents are not equal (indicating a fault), the relay operates and
initiatestripping.
4. Features:
• High sensitivity to internal faults.
• Selectivity to avoid unnecessary tripping during external faults.
• Rapid operation to minimize damage and downtime.
5. Applications:
• Commonly used for transformer, generator, motor, and busbar
protection insubstations and industrial facilities.
• Essential for maintaining system reliability and preventing catastrophic
failures.

Current Differential Relay :

1. Purpose:
• Protects electrical equipment by comparing currents entering
andleaving a protected zone.
2. Operation:
• Compares the difference between the sum of currents entering
andleaving the protected zone.
• Operates when the difference exceeds a set threshold,
indicating afault.
3. Applications:
• Used for transformer, generator, and busbar protection.

Percentage Differential Relay :

1. Purpose:
• Protects equipment by comparing the percentage difference
betweeninput and output currents.
2. Operation:
• Operates when the percentage difference between currents
exceeds aset threshold.
• More sensitive to faults than absolute current differential relays.
3. Applications:
• Commonly employed for transformer protection.

Voltage Differential Relay :

1. Purpose:
• Protects equipment by comparing voltages at different points
in thesystem.
2. Operation:
• Compares the difference between voltages on the input and
outputsides.
• Operates when the voltage difference exceeds a set threshold.
3. Applications:
• Used for protection of overhead lines, cables, and busbars.
• Provides backup protection for current differential relays.
Explain the working principle of distance or impedance relays and its types.
1. Purpose:
• Protects power systems by measuring impedance between
relayingpoint and fault location.
2. Operation:
• Calculates impedance by measuring voltage and current phasors.
• Compares impedance with a pre-set characteristic curve.
• Triggers operation when impedance exceeds the curve,
indicating afault.
3. Characteristics:
• Typically inverse or definite time characteristics.
• Can be directional or non-directional based on fault location.
4. Applications:
• Used for transmission line protection.
• Provides backup protection in conjunction with other relays.
5. Advantages:
• Effective for long-distance fault detection.
• Relatively immune to system load and fault resistance variations.
6. Limitations:
• Prone to maloperation due to power swing and system disturbances.
• Requires accurate fault impedance estimation for proper operation.
7. Definite Time Relay (DT Relay):
• Principle: Operates after a predetermined time delay, regardless
of thefault magnitude or system conditions.
• Operation: Upon detection of a fault, the relay initiates a timer.
If thefault persists beyond the set time delay, the relay trips the
circuit breaker to isolate the faulty section.
• Application: Used for protection against faults where a consistent
timedelay is required, such as in feeder protection and backup
protection schemes.
• Advantages: Simple to implement, provides uniform time delay
for allfaults, and is less sensitive to system transients.
• Disadvantages: Lacks selectivity and may trip unnecessarily
fortemporary faults, leading to system disruptions.
8. Time-Distance Relay:
• Principle: Operates based on both time delay and distance to the
faultlocation, ensuring selective and coordinated protection.
• Operation: Compares the fault impedance with pre-set
impedance characteristics (reach) and initiates a time delay if the
fault impedancefalls within the designated zone. If the fault
persists beyond the time delay, the relay trips the circuit breaker.
• Application: Used for protecting transmission lines, where selectivity
and speed of operation are crucial.
• Advantages: Offers selective and high-speed protection, adaptable to
varying system conditions, and minimizes unnecessary tripping.
• Disadvantages: Requires accurate setting coordination to avoid
misoperation and is more complex than definite time relays.
Explain mho relay in detail.
1. Principle of Operation :
• The Mho relay operates by comparing the measured impedance
(Z) ofthe fault loop to a pre-defined characteristic curve on the
R-X plane.
• The characteristic curve represents the permissible region of fault
impedance for reliable operation. It typically forms an ellipse or a
circleon the impedance plane.
• If the measured impedance falls within this characteristic
curve, therelay operates to trip the circuit breaker.
2. Operation:
• When a fault occurs in the protected zone, the Mho relay measures
the
voltage and current signals at its location.
• Using these measurements, the relay calculates the
apparentimpedance of the fault loop.
• If the calculated impedance falls within the characteristic curve,
indicating that the fault is within the protected zone, the relay
operatesto trip the circuit breaker.
3. Application:
• Mho relays are commonly used for the protection of transmission
lines,especially for long-distance protection.
• They provide high-speed and highly selective protection, meaning
they can quickly isolate faults while minimizing the impact on the
rest of thesystem.

Advantages :

1. Speed: Operate rapidly to isolate faults quickly.


2. Selective: Can accurately distinguish faults within their zone.
3. Less sensitive to fault resistance changes : Maintain performance even if
fault resistance fluctuates.

Disadvantages:

1. Coordination: Requires precise coordination with adjacent relays.


2. Susceptible to system transients : May trip falsely due to certain system
disturbances.
3. Limited scope: Not universally suitable; best suited for transmission line
protection.
In what way is distance protection superior to over-current protection for the
protection of transmission line?
1. Selective Tripping: Distance protection can pinpoint the fault location and trip only the affected
segment, minimizing disruption to the entire transmission line.
2. Faster Response: It reacts swiftly to faults, swiftly isolating the faulty section, thus reducing the
likelihood of severe damage to the equipment and system.
3. Adaptability: Distance protection adjusts to different fault conditions and line configurations,
offering robust performance across various scenarios.
4. Long Transmission Lines: Particularly effective for lengthy transmission lines where accurate fault
detection and rapid response are crucial.
5. Complex Faults: Capable of handling complex faults, including resistive faults, with greater
precision compared to over-current protection.
6. Fault Location: Provides accurate fault location information, aiding in rapid maintenance and
restoration efforts.
7. Improved Reliability: Offers enhanced reliability in detecting faults and minimizing outage
durations, ensuring the continuous operation of the transmission network.

Explain about transformer protection using differential protection ( Merz- price


protection)
Merz price protection scheme is used to protect the transformer against earth fault and phase to phase
fault. Merz price protection is used in the transformer of rating exceeding above 1 MVA.
Construction :-When this system is employed for the protection of the transformer the following points
must be considered :-
1. CTs with different turn ratios are selected to compensate for the difference in primary and
secondary winding currents.
2. Phase differences between primary and secondary currents are adjusted using specific transformer
connections.
3. Tap-changing transformers may cause differential currents even in normal conditions, but this can
be mitigated by adjusting CT turn ratios.
4. During transformer energization or service restoration, the high inrush current may trigger the
relay, leading to false fault detection.

WORKING:-
Merz price protection is utilised to protect the power transformer from any phase to phase or any earth
fault . For the given below fig. 2 of the power transformer , which is connected in delta – delta.
To compensate the phase angle of the current , the CTs are connected in star – star , because the winding
connection of given power transformer is delta – delta.

In the normal operating condition , the current through the relay coil is zero. Therefore , no operation of
the relay coil takes place. But , whenever any fault may be phase to phase fault or earth fault take place in
that the corresponding relay coil will operate , which trip the circuit breaker and disconnect the faulty
parts.
Advantage :-
▪ Simple in construction
▪ Reliable
▪ Low cost as compared to other schemes
▪ Accurate and precise

Explain about transformer protection using Buchholz relay.


A Buchholz relay is a protective device used in oil-filled transformers and reactors. It detects and provides
early warning of internal faults, such as overheating, arcing, or insulation breakdown, by monitoring gas
levels within the transformer oil.
WORKING:-
• Gas Accumulation Detection: Monitors gas levels in transformer oil.
• Arcing or Overheating: Detects abnormal gas buildup caused by internal faults like arcing or
overheating.
• Float Mechanism: Utilizes a float mechanism immersed in the transformer oil.
• Tilt Switch: Activates when gas bubbles displace the oil, causing the float to tilt.
• Trip Signal: When tilted, it triggers a trip signal to isolate the transformer from the system.
Explain about fault occurs in generator.
1. Stator Faults:
• Windings overheating due to permanent overloads.
• Phase-to-phase and phase-to-earth faults caused by insulation breakdown.
• Inter-turn faults can occur within the windings.
2. Rotor Faults:
• Earth faults may arise within the rotor.
• Winding short-circuits in wound rotor generators can occur, leading to increased excitation
current.
• Overheating of the rotor may result from unbalanced currents in the stator.
3. Loss of Field / Excitation:
• Occurs when the excitation voltage to the generator's field coils is lost, leading to a loss of
magnetic flux production.
4. Generator Out-of-Step:
• Refers to the generator operating out of synchronization with the rest of the power system,
potentially causing instability.
5. Motor Operation:
• If the generator acts as a motor due to external factors, it may suffer damage or abnormal
operation.
6. Bearings Overheating and Lack of Lubrication Pressure:
• Overheating and insufficient lubrication can damage bearings, affecting generator
operation.
7. Vibration:
• Excessive vibration can indicate mechanical faults or misalignment within the generator.

Types of External Faults in a Generator


External Power System Faults and Abnormal Operating Conditions are:
• External short-circuit faults
• Non-synchronized connection of generator
• Out-of-step (pole slipping or loss of synch)
• Overloads
• Overspeed
• Phase unbalance and negative phase sequence
• Under and over frequency
• Under and over voltages

Explain about generator protection using differential protection ( Merz- price


protection)
DIFFERENTIAL PROTECTION:-
• Purpose: Protects stator windings of the generator from earth faults and phase-to-phase faults.
• Criticality: Stator winding faults can cause significant damage to the generator.
• Objective: Differential protection clears faults swiftly to minimize damage.
• Importance: Essential for ensuring the reliable and safe operation of the generator.
• Swift Response: Trip signal is initiated rapidly to isolate the faulted section.
Merz-Prize Circulating Current System

• Principle: Utilizes circulating currents to detect faults in power systems.

• Operation: Compares currents from different locations in the system to identify


imbalances.

• Two Elements Arranged: One for phase fault protection and the other for earth fault
protection.

• Phase Protection: Elements connected in star with resistor.

• Earth Fault Protection: Relay placed between star and neutral.

• Balanced Circuit: Symmetrical setup prevents balanced overflow current from flowing
through earth fault relay.

• Stability: Sensitive earth fault relay operates with high stability due to symmetrical
circuit configuration.
Explain about bus bar protection current differential protection and voltage
differential protection.
BUS BAR FAULTS:-
1. Overvoltage causes support insulator flashover
2. Polluted insulator causes overvoltage flashover
3. Other linked equipment fails.
4. Earthquake
5. Mechanical damage
Busbar Protection –
Current Differential Protection:
• Current Comparison: Compares currents entering and leaving the busbar.
• Fault Detection: Detects any imbalance in these currents, indicating a fault.
• Selective Operation: Trips only the affected section, minimizing downtime.
• Fast Response: Swiftly isolates faults to prevent widespread damage.

Voltage Differential Protection:


• Voltage Comparison: Compares voltages at different points in the busbar.
• Detects Imbalance: Any voltage mismatch indicates a fault or abnormal condition.
• Selective Tripping: Trips only the affected section, ensuring minimal disruption.
• Reliable Operation: Provides dependable protection against various fault types.
Explain the percentage differential protection for a modern alternator.
• Definition: Percentage differential relay operates on phase difference, includes restraining coil.
• Restraint Function: Controls sensitivity, prevents false tripping.
• Configuration: Restraint coil in pilot wire, operating coil midpoint.
• Operation: Under normal conditions, restraining torque greater, keeping relay inactive.
• Fault Detection: Internal fault increases operating torque, activating trip circuit.
• Adjustment: Number of turns in restraining coil adjusts restraining torque.
• Differential Current: Operating coil proportional to (I1-I2), restraining coil to (I1-I2)/2, preventing
false operation during external faults.

Percentage differential protection in alternator


Percentage differential protection in alternator
• Principle: Compares percentage difference between currents entering and leaving alternator
windings.
• Sensitive: Detects internal faults accurately, providing reliable protection.
• Selective Operation: Trips only the faulty section, minimizing downtime.
• Adaptive: Adjusts to variations in load and fault conditions for optimal performance.
• Modern Implementation: Utilizes advanced electronics for enhanced reliability and flexibility.
What is Universal Torque equation? Using this equation, Draw the schematic
diagram and derive the following characteristics
Impedance relay
Reactance relay
MHO relay
SOME MORE IMPORTANT QUESTIONS FROM OTHER MODULES:-

What is the effect of power swing on distance protective scheme?


1. Misoperation: Power swing can cause distance relays to misinterpret the distance to the
fault, leading to incorrect tripping.
2. Delayed Operation: Distance relays might take longer to operate during power swings,
delaying the protection response.
3. Zone Reaching: Power swing can cause the fault to appear closer or farther than it
actually is, affecting the relay's ability to accurately determine the fault location.
4. Security: Power swings can compromise the security of the protection scheme, as relays
may not trip for genuine faults or might trip unnecessarily.
5. Coordination Issues: Power swings can create coordination issues between different
protection devices, leading to improper coordination and potential system instability.
6. Sensitivity Reduction: Power swing may reduce the sensitivity of distance protective
schemes, making them less responsive to faults within their protection zones.
7. False Tripping: Power swing can result in false tripping of distance relays, causing
unnecessary disruption to the power system due to misinterpretation of system
conditions as faults.

State the difference between conventional and digital relay. Explain


numerical transformer differential protection.
Numerical Transformer Differential Protection:
1. Principle: Compares currents entering and leaving the transformer windings.
2. Digital Signal Processing: Microprocessors calculate the difference between currents
digitally.
3. High-Speed Operation: Quickly detects internal faults to prevent transformer damage.
4. Adaptive Settings: Parameters can be adjusted automatically for different operating
conditions.
5. Communication: Communicates with other relays for coordinated protection.
6. Fault Location: Pinpoints fault location accurately for swift action.
7. Remote Monitoring: Allows remote monitoring and control for improved system
management.

Write a short notes on:-


Current chopping:-
1-Definition: Current chopping refers to the interruption or chopping off of an electrical
current in a circuit during the opening operation of a circuit breaker.
1- Cause: It occurs when the voltage across the circuit breaker contacts rises rapidly during
the opening operation, causing the current to chop off before natural zero crossing.
2- Effect: Results in the generation of high-frequency transients and voltage spikes in the
circuit.
3- Consequences: Can damage the equipment connected to the circuit, including insulation
breakdown and device failure.
4- Prevention: Techniques like arc suppression devices or utilizing circuit breaker designs
that minimize current chopping are employed to mitigate its effects.
5- Importance: Understanding and managing current chopping is crucial for ensuring the
reliability and safety of electrical systems.
6- Mitigation Techniques: Strategies such as using pre-insertion resistors, damping
networks, or advanced circuit breaker designs are employed to reduce the impact of
current chopping on the electrical system.

WAMS and its application:-


1. Definition: WAMS is a system of synchronized measurements collected from various
locations across a wide area power grid.
2. Real-Time Monitoring: Provides synchronized measurements of voltage, current, and
frequency across the grid in real-time.
3. Enhanced Situational Awareness: Allows operators to have a comprehensive view of the
entire power system's dynamic behavior.
4. Wide-Area Protection: Enables faster detection and response to disturbances and faults
by utilizing data from multiple points in the grid.
5. System Stability Enhancement: Facilitates better control of system oscillations and
improves overall stability through advanced control algorithms.
6. Wide-Area Control: Allows for coordinated control actions across different regions of
the grid to maintain stability and reliability.
7. Blackout Prevention: Helps in early detection of potential instability or cascading
failures, allowing operators to take preventive actions to avoid blackouts.
Computer-aided protection of power system:-
1. Automation: Automates protection functions using computers.
2. Fault Analysis: Quickly identifies and locates faults in the power system.
3. Data Processing: Processes data from sensors and relays for accurate fault detection.
4. Remote Control: Allows remote monitoring and control of protection devices.
5. Integration: Integrates with SCADA for comprehensive system monitoring.
6. Adaptive Settings: Adjusts protection settings dynamically based on system conditions.
7. Enhanced Reliability: Improves reliability by reducing response time and human error
in protection operations.

Relay testing:-
1. Verification: Ensures that protective relays are functioning correctly and accurately
detecting faults.
2. Performance Evaluation: Assesses the response time and accuracy of relays under
various fault conditions.
3. Calibration: Adjusts relay settings to ensure they operate within specified tolerances.
4. End-to-End Testing: Validates the entire protection scheme, including relays,
communication systems, and trip devices.
5. Functional Testing: Confirms that relays are performing all intended functions, such as
fault detection, discrimination, and tripping.
6. Simulation: Uses test sets to simulate fault conditions and measure relay response,
allowing for controlled testing without impacting the live system.
7. Documentation: Records test results and settings to maintain an accurate record of
relay performance and compliance with regulatory requirements.

You might also like