You are on page 1of 3

De-rating Curve

Smart Transformer Station


STS-3000K-H1
Transformer De-rating Curve

Huawei Technologies Co., Ltd.

Version Created by Date Remarks


V1.0 Wangwei; Wanggewen; Leiying 2021.11.02 Preliminary
V1.1 Wangwei; Wanggewen; Leiying 2022.01.28 Data updated
V1.2 Wangwei; Wanggewen; Leiying 2022.07.05 Data updated

The text and figures reflect the current technical state at the time of printing. Subject to technical changes. Errors and omissions excepted.
Huawei assumes no liability for mistakes or printing errors. Version No.: 01-(202207)
De-rating Curve

De-rating Curve VS. Ambient Temperature


Transformer De-rating Curve VS. Ambient Temperature of STS-3000K-H1

The characteristic of transformer inside STS-3000K-H1 shall perfectly match the output characteristic of
SUN2000-200/215KTL and LUNA2000-200KTL.

T RA NSFO RME R DE - RAT I NG CURVE VS. A MBI E NT T E MPE RAT URE


3800

3600
TRANSFORMER CAPACITY / KVA

3400

3200

3000

2800

2600

2400

2200
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60

AMBIENT TEMPERATURE / ℃
Specific Rated

Model Type -25 °C 30 °C 35 °C 40 °C[1] 45 °C 50 °C 55 °C 60 °C

Rated 3,655 kVA 3,655 kVA 3,519 kVA 3,400 kVA 3,125 kVA 2,960 kVA 2,624 kVA 2,304 kVA
STS-3000K-H1
Specific[2] 3,655 kVA 3,655 kVA 3,604 kVA 3,468 kVA 3,315 kVA 3,024 kVA 2,672 kVA 2,304 kVA

Note:
[1] at ambient temperature max./monthly(hottest month)/annual average (°C) 40 / 30 / 20
[2] Specific transformer capacity shall be achieved under specific operating conditions when LV AC input
voltage ≥ 800 Vac.

[3] at altitude(M) 1000

The text and figures reflect the current technical state at the time of printing. Subject to technical changes. Errors and omissions excepted.
Huawei assumes no liability for mistakes or printing errors. Version No.: 01-(202207)
De-rating Curve

Maximum Working Temperature Vs Altitude


Maximum Working Temperature Vs Altitude for Smart Transformer Station

Maximum Working Temperature VS. Altitude


45
Maximum Working Temperature / ℃ with Rated

40
40
34
35

30 28

25 22
Power

20
16
15

10

0
1000 2000 3000 4000 5000
Altitude above Sea Level / m

Note:
The maximum working temperature is the ambient temperature below which smart transformer
station can output rated power without de-rating.
When the altitude rises, the cooling capacity of the smart transformer station de-rates. So the internal
temperature of smart transformer station in the high altitude area will be higher and severerthan that in
the low altitude area.
When altitude > 1000m, the maximum working temperature of smart transformer station should de-rate
by altitude, and it de-rates in accordance with 6°C /1000m.

The text and figures reflect the current technical state at the time of printing. Subject to technical changes. Errors and omissions excepted.
Huawei assumes no liability for mistakes or printing errors. Version No.: 01-(202207)

You might also like