Professional Documents
Culture Documents
C Faye
L Le Magorou
P Garcia
J-C Duccini
FRANCE
1
were also tested. The objective is to assess experimentally a seismic behaviour factor q for
12 mm thick OSB sheathing.
2 Walls configurations
Tests were performed on walls of 2,4 m height by 2,4m long with the three following types
of sheathing panels:
- (config. CP10) 10 mm thick plywood complying with EN 636-3,
- (config. P16) 16 mm thick particleboard complying with EN 312/P5,
- (config. OSB12) 12 mm thick OSB/3 complying with EN 300.
These three configurations correspond to the minimum configurations used in seismic zones
in France.
Except for the sheathing panels, shear walls for tests have identical characteristics:
- sheathing panels are fixed using threaded nails of 2.5 mm diameter and 50 mm length
complying with EN 14 592,
- the spacing of the nails is 150 mm and 300 mm respectively on panel edges and panel
center,
- the span of studs is 600 mm. Studs and horizontal members are connected by 4
threaded nails.
In these conditions, according to Eurocode 8, configurations (CP10) and (P16) can be
assigned to the high ductility class. A wall description is presented in Figure 1.
2
For each configuration, two cyclic tests were performed with realistic boundary conditions
(wall is anchored by available stiff commercial anchor brackets and a total vertical dead
load of 15 kN is applied) according to the standard ISO 21581:2010 [2] based on [3]. Test
assembly and shear wall dimensions are presented in Figure 1. The rate of displacement
was chosen to achieve ultimate displacement within 1 minute. The ultimate displacements,
measured previously with the static monotonic test, were respectively 124 mm, 116 mm
and 100 mm for plywood, particle board and OSB configurations.
25000 25000
15000 15000
5000 5000
Force (N)
Force (N)
-120 -100 -80 -60 -40 -20 -120 -100 -80 -60 -40 -20
-5000 0 20 40 60 80 100 120
-5000 0 20 40 60 80 100 120
-15000 -15000
-25000 -25000
Displacement (mm) Displacement (mm)
Figure 2 : load-displacement and envelope curves for cyclic tests at the top of the wall with 10
mm thick plywood sheathing (CP10) (left: test n°1 / right: test n° 2).
25000 25000
15000 15000
5000 5000
Force (N)
Force (N)
-120 -100 -80 -60 -40 -20 -120 -100 -80 -60 -40 -20
-5000 0 20 40 60 80 100 120
-5000 0 20 40 60 80 100 120
-15000 -15000
-25000 -25000
Displacement (mm) Displacement (mm)
Figure 3 : load-displacement and envelope curves for cyclic tests at the top of the wall with 16
mm thick particle board sheathing (P16) (left: test n° 1 / right: test n°2).
Courbes enveloppes et EEEP - 403/11/725.1/6 OSB CHARGÉ
15000
15000
Fmax
90%Fmax 10000
10000
5000
5000
Force (N)
Force (N)
0
0
-120 -100 -80 -60 -40 -20 0 20 40 60 80 100 120 -120 -100 -80 -60 -40 -20 0 20 40 60 80 100 120
V90%Fmax
-5000 -5000
-10000 -10000
-15000 -15000
Displacement (mm) Displacement (mm)
Figure 4 : load-displacement and envelope curves for cyclic tests at the top of the wall with 12
mm thick OSB sheathing (OSB12) (left: test n°1 : right : test n°2).
3
The following were observed:
- shear failure mode of the fasteners of the panels,
- hardening of the nails,
- damage to the particle boards around the nails,
- the anchorage brackets were undamaged.
4 Dynamic tests
4.1 Test Methods
The same wall configurations were then
tested on a shaking table with the
following conditions:
- a total dead load of 15 kN or 20 kN
is applied on the top of the wall,
- wall is anchored by stiff fasteners in
accordance with the provisions of
Eurocode 5 and Eurocode 8,
- the direction of shaking test is
parallel to the wall plane.
The horizontal displacement is measured at
the top of the wall.
5
0,25
0.4
0,2
0.3
0,15
0.2 0,1
Accélération (g)
Accélération (g)
0,05
0.1
0
0 10 20 30 40 50 60 70 80
0.0 -0,05
0 5 10 15 20 25 30
-0,1
-0.1
-0,15
-0.2
-0,2
-0.3 -0,25
-0,3
-0.4
0,60000000
0,40000000
0,20000000
Acceleration (g)
0,00000000
0 5 10 15 20 25
-0,20000000
-0,40000000
-0,60000000
-0,80000000
Temps (s)
.
Figure 8: earthquake 3 (PGA=0.56g)
shear failure
9 5.8 15 1 42 mm at 1.19g 0.1 1.1 g 0.32 g 3.4
on 3 nails
shear failure
19 5 20 2 50 mm at 0.88g on 5 nails
5 1.1 g 0.24 g 4.5
shear failure
20 5.4 20 3 49 mm at 1.3g on 5 nails
5 1.4 g 0.24 g 5.8
Table 2 : results of dynamic tests for CP10 walls: column 2 indicates the natural frequency of the
wall determined before the first seismic test (see section 4.1, step a); column 7 indicates the
permanent displacement at the top of the wall after the seismic test made with PGAnear-collapse;
column 8 indicates the actual value of PGAnear-collapse, test which can be different from the input PGA;
column 10 indicates the qtest value for each wall, calculated as mentioned in section 4.1. (g = 9.81
m/s2)
6
The main observations are the following:
- concerning all CP10 walls, the only visible damage (see column 8 of Table 2) due
to earthquake at PGAnear-collapse,test (see § 4.1 step c) is shear failure of the nails
without damage of the panel ;
- all walls having suffered the earthquake at PGAnear-collapse,test, are able to
withstand an earthquake at its regular PGA, without collapsing;
- the maximum displacement of wall n°9 (42 mm) for seismic at PGAnear-
collapse,test level (see step c of section 4.1) is well below the criterion of 54 mm. So,
the value of 3.4 for q, calculated for the earthquake1 is very conservative. Tests
performed on walls n° 19 and n° 20, with earthquakes 2 and 3, led to higher
conservative values for q: respectively 4.5 and 5.8.
shear failure on 2
5 7.4 15 1 39 mm at 1.25g nails
0.1 1.15 g 0.35 g 3.3
10 nailed
withdrawals /
10 6.2 20 1 54 mm at 1.25g panel without
1.5 1.17 g 0.26 g 4.5
damage
Table 3 : results of dynamic tests for P16 walls. For explanations, see Table 2.
7
4.5 Results of the OSB12 configuration and proposal for the
behaviour factor for OSB12
Height walls OSB12 were tested on the shaking table using the three earthquakes. The
results are presented in Table 4.
The main observations are the following:
- concerning all OSB12 walls (except wall n°13 which over-passed the displacement
limit of 51mm), there was no damage induced by seismic tests;
- all walls having suffered the earthquake at PGAnear-collapse,test, are able to
withstand an earthquake at its regular PGA, without collapsing;
- concerning earthquake 1, four identical tests were performed (on walls n° 7, 8, 11
and 12). The variation (around 9%) of the experimental values of the maximum
displacement at the top is explained by the higher stiffness of the walls n°7, 11 and
12 in comparison with wall n°8.
The following values for behaviour factor of OSB12 were calculated:
- a conservative value of 3.2 for earthquake 1 (walls n° 7, 8, 11, 12)
- a conservative value of 3.8 for earthquake 2 (wall n° 18)
- a conservative value of 4.5 for earthquake 3 (wall n° 15).
Furthermore, comparison of experimental displacements curves of OSB12 and CP10
measured for identical (or very close) seismic tests are presented in Figure 9 and Figure 10.
We can observe that dynamic behaviour of OSB12 and CP10 walls are very similar.
In the opposite, comparison between OSB12 and P16, presented in Figure 11, shows that
P16 walls can suffer significantly higher seismic event than OSB12 wall with similar
displacements.
results concerning only seismic test
performed with PGAnear-collapse (see section 4.1, step c)
1 nail
13 5.6 20 1 57 mm at 1,06g withdrawal 7 1g 0.24 g /*
Table 4 : results of dynamic tests for OSB12 walls. For explanations, see Table 2. * Concerning
wall n° 13, q test is not calculated because the near collapse criterion is over-passed.
8
OSB12 Wall N°18 for earthquake 2 at 0,9g
4
CP10 Wall N°21 for earthquake 2 at 0,9g
3
displacements at the top
2
of the walls (cm)
0
0 10 20 30 40 50 60 70
-1
-2
-3
-4
time (s)
-5
Figure 9 : experimental displacements vs time curves for wall n°18 (OSB12) and wall n° 21
(CP10) when submitted to same seismic test (earthquake 2 at 0,9g).
3
displacements at the top
1
of the wall
(cm)
0
0 5 10 15 20 25 30 35
-1
-2
-3
-4
time (s)
-5
Figure 10 : experimental displacements vs time curves for wall n°7 (OSB12) and wall n° 9
(CP10) when submitted to quasi-same seismic test (earthquake 1 at 1g).
5
P16 wall n°16 for earthquake 3 at 2.07g
4
OSB12 wall n°15 for earthquake 3 at 1.4g
displacements at the top
3
of the wall (cm)
0
0 5 10 15 20 25 30 35
-1
-2
-3
-4
time (s)
Figure 11 : experimental displacements curves vs time for wall n°15 (OSB12) and wall n° 16
(P16) when submitted to earthquake 3, first one at 1.4g, second one at 2.07g.
9
5 Conclusions
This experimental study concerned dynamic tests carried out on three different light frame
walls having racking resistances designed according to the capacity design principles and
supporting a dead load up to 850 kg/m.
The dynamic tests showed that failure modes are due to the yield moment of the fasteners
connecting the sheathing panels to the wooden frame.
For earthquake 1, which is among the five most destructive of our database on 40
representative earthquakes of seismic French zones, a conservative value q of 3.2 was
calculated for OSB12 walls.
Moreover, the dynamic behaviour of walls with OSB (12 mm) and plywood (10 mm)
sheathing panels are very similar:
- their near-collapse criterion displacement are very close,
- during dynamic tests performed with identical earthquakes, their experimental
dynamic displacement curves are very similar.
Thus, it is proposed that a conservative behaviour factor q for OSB sheathing panel with a
thickness of 12 mm should be q = 3, as is the value allowed for CP10 complying
requirements for high ductility class in France.
6 Acknowledgments
This research project was supported by CODIFAB (French Federation of Wood Industry)
and DHUP (French Ministry of Lodging).
7 References
[1] EN 1998-1: Design of structures for earthquake resistance- Part 1: General rules,
seismic actions and rules for buildings.
[2] ISO 21581:2010 : Timber structures- Static and cyclic lateral load test metrhods for
shear walls.
[3] Yasumura M., Karacabeyli E.: International test standard development for lateral load
test for shear walls, Proceedings of CIB-W18, paper 40-15-5, 2007, Slovenia.
[4] Ceccotti A., Sandhaas C., A proposal for a standard procedure to establish the seismic
behaviour factor q of timber buildings, WCTE, World Conference on Timber Engineering,
2010, Italy.
[5] Schädle P., Blass HJ., Influence of different standards on the determination of
earthquake properties of timbre shear wall systems, Proceedings of CIB-18, paper 43-15-2,
2010, New-Zealand.
[6] Research report, FCBA, comportement parasismique des murs à ossature bois, 2012.
10