Professional Documents
Culture Documents
J Schmid
A Just
SP Technical Research Institute of Sweden
SWEDEN
M Klippel
A Frangi
ETH Zürich, Institute of Structural Engineering IBK, Zürich
SWITZERLAND
Keywords
Fire design model, Reduced cross section Method, Compression, Tension, Bending, Timber, standard fire, Fire resistance, Fire
testing
Summary
For the design of timber members exposed to fire the “Reduced Cross-Section Method” provides a popular
design method using an effective cross-section and mechanical properties at normal temperature. The
method, originally developed for single span bending beams, has been further introduced in standards and
handbooks for a large range of timber members including columns under compression and members under
tension. Additionally, the method can be applied to cross-laminated panels or even I-joists. Recently, the
method and its extended applications were discussed showing limitations as well as significant differences
depending on the state of stress.
A total number of 110 fire tests were analysed and are discussed in this paper (79 members in bending, 6
members in compression and 25 members in tension). The results of the analysis of the fire tests show that
the number of tests with reliable information is limited, among others, due to varying testing procedures and
the lack of information reported. However, all results with adequate information content showed a significant
variation of the zero-strength layer determined depending on the mode of stress. This is in agreement with
advanced simulations presented in earlier research presented by the authors.
Introduction
While calculation methods provide a fast and cheap method to evaluate the load-bearing resistance of timber
members, fire tests are time intensive and costly. Simulations of the fire performance of structural members
are used for complex structures but even for the verification of easy-to-use models. In general, simulations
use effective material properties to include effects 20
Zero-strength layer d0 [mm]
1
standards in Europe in the 1960s to tests performed by SP in Sweden in 2013 to conduct a comprehensive
analysis of the zero-strength layer.
The requirements to consider a dataset as sufficient are, among others, reference tests at normal temperature,
the standard fire exposure during loaded tests, the documentation of the failure time, the failure mode, and
the residual cross-section. If the datasets were not complete, different scenarios were chosen and
documented. The determined data were indicated as such and results were used separately. For the
determination of all results, mean values were used and no safety factors were included in the analysis. For
all members tested in a fire test, the zero-strength layer was calculated. For the determination of the zero-
strength layer, results of the large-scale tests and design principals in terms of EN 1995-1-1 [6] were used,
assuming ambient material properties in the fire situation and using effective cross-sections. In the following,
the different fire tests are described shortly. The standards mentioned for each reference refer to the version
at the time the reference was written and the tests were performed. Further, the results obtained from the fire
tests were grouped in certain, uncertain and very uncertain results depending on the data reported in the
different references.
2
with a fire retardant; two were protected from direct fire exposure by a fire protection system. Protected and
impregnated beams were not evaluated in this study. The beams were exposed to fire according to the
standard fire specified in DIN 4102:1940 [8] on all four sides. No significant influence of the adhesive used
was observed regarding the load-bearing resistance. However, beams produced with the UF adhesive
showed increased charring at the sides in areas of the glue lines. The fire exposure was 30 minutes in a gas-
fired furnace. The load was applied prior to the fire test by means of two hydraulic jacks and kept constant
until failure or 30 minutes fire exposure. The applied load corresponded to a bending stress of 12,75 N/mm2.
For some of the larger cross-sections (h ≥ 400 mm), due to stability problems (lateral buckling) during the
fire test, the load was applied only for 15 minutes and the next 15 minutes the timber member was only
exposed to fire. Failure occurred during the fire tests in four cases. In the other cases, the load was increased
after extinguishing about 35 minutes after the fire test had been terminated. Among others, it was observed
that the decrease of flexural stiffness leading to the observed stability problems can be explained by an
increased charring of about 1 mm/min instead of 0,66 mm/min, the determined charring rate. Since
increasing the load until failure after the end of the fire test may be a questionable test procedure, all results
determined from these tests were estimated to be uncertain but used for further investigations for this paper.
For further analysis in this study, the residual cross-section was determined using a notional charring rate
including the corner roundings of βn = 0,7 mm/min as specified in EN 1995-1-2. This was done for either
30 minutes or, if the beam failed earlier, for the specific failure time. The reported specific stiffness
measurements for every beam were used to predict 24
d0 [mm]
the specific bending strength of the specimens
resulting in a mean bending strength of about 20
37 N/mm2. This value was estimated using today’s
strength classes for glued laminated timber of
16
EN 1194 [14], a correction of the bending strength
by means of EN 1995-1-1 [6] considering the actual
depth and a conversion factor between the 12
characteristic value and the mean value given by
JCSS [12]. In general, the poor prediction method 8
results only in an indication of the zero-strength
layers. All beams with depths of 400 mm and above 4
did not show bending failure but shear failure;
corresponding results for the zero-strength layer are 0
further reported as very uncertain since the results 0 15 30 45
are expected to be lower for bending failure. A mean t [min]
value for the zero-strength layer of the beams failed Figure 2. Determined zero-strength layer for tension
in bending in the investigation in [13] was derived to tests [13]. Red squares indicate uncertain results;
about 8,4 mm considering only uncertain results, see white squares indicate very uncertain results.
Table 1.
Table 1. Zero-strength layer results (minimum, maximum and mean) for all 24 evaluated results reported in
[13] as well as for certain results only.
basis of calculation d 0,min [mm] d 0,max [mm] d 0,mean [mm]
all results 0,9 16,5 8,9
uncertain results 0,9 16,5 8,4
3
bending strength of every beams, in this study the density reported was used together with specified ratios
between density and bending strength given in EN 1194 [14]. To estimate a mean strength by means of the
derived characteristic value, a ratio of 1,29 given by JCSS [12] was used. To determine the zero-strength
layer, a mean bending strength of 34 N/mm2 was further used. Due to the assumptions of the residual cross-
section as well as the material properties all results are considered as uncertain results. The zero-strength
layer was determined separately for four-sided fire exposure (10 tests), see Figure 3, and three-sided fire
exposure (4 tests), Figure 4.
10 10
d0 [mm]
d0 [mm]
8 8
6 6
4 4
2 2
0 0
-2 -2
-4 -4
-6 -6
0 15 30 45 60 75 0 15 30 45 60 75 90
t [min] t [min]
Figure 3. Determined zero-strength layer for bending Figure 4. Determined zero-strength layer for
tests and four sided fire exposure [15]. Red squares bending tests and three sided fire exposure [15].
indicate uncertain results. Red squares indicate uncertain results.
Table 2. Zero-strength layer results (minimum, maximum and mean) for all 14 evaluated results reported in
[15] by means of two different material characterisation.
r mean f m,mean
basis of material characterisation [kg/m 3 ] f m,k [N/mm 2 ] [N/mm 2 ] d 0,min [mm] d 0,max [mm] d 0,mean [mm]
reported specific beam densities variable variable variable -5,5 9,9 1,8
mean of reported densities 460 24,5 31,7 -6,2 16,9 2,0
For comparison reasons in Table 3 zero-strength values determined by means of the specific density and the
mean batch density are given; differences are very limited. The in [15] reported charring depths at the top of
the four-sided fire exposed beams are considerably lower than at the bottom side (up to 55% lower) most
likely due to the very limited space of only 160 mm between the specimen and the furnace lock. Thus, the
heating at the top side was limited. The observed mean charring rate βn = 0,67 is slightly lower than specified
in EN 1995-1-2; however the observed charring depths seem to be quite low considering the fact that the
extinguishing work was finished about 30 to 60 minutes after the end of the fire test. Thus, the cross-section
in the fire test is larger than assumed in this study and any calculated zero-strength layer is non-conservative.
4
resistance for the two different types of adhesives was reported. The paper does not contain any information
on the stiffness or strength properties of the material tested, however the density of each beam is reported. To
estimate a bending strength of all beams, in this study the reported specific beam density between 395 and
475 kg/m3 was used together with specified ratios between density and bending strength given in EN 1194
[14]. To estimate a mean bending strength values by means of the derived characteristic value a ratio of 1,29
given by JCSS [12] was used. To determine the zero-strength layer, a bending strength of in mean 30 N/mm2
was used. In this study, the residual cross-sections were estimated by means of the reported charring depth
values. Due to the assumptions of the material properties as well as the residual cross-section all results are
considered as uncertain results, results for beams which showed lateral buckling failure are evaluated as very
uncertain results (results B11b09 and B11b10 in Figure 5). The zero-strength layers were determined for all
10 tests and are given in Figure 5. However, test B11b05 (see Figure 5) is a result of the test with three-sided
fire exposure. The reported charring depths at the top of the four-sided fire exposed beams are considerably
lower than at the bottom side (up to 51% lower) most likely due to the very limited space of only 160 mm
between the specimen and the furnace lock. Thus, the heating at the top side was limited. A significantly
larger charring rate than given in EN 1995-1-2 [1] 26
d0 [mm]
was observed at the bottom of the beams 24 B11b10
(βn,mean = 0,86 mm/min). Although fall-off of char 22
was observed a delamination or an influence of the 20
adhesive was not reported. Considering the lower 18
charring at the top of the beams, the observed overall 16 B11b09
mean charring rate βn = 0,66 mm/min is slightly 14
lower than specified in EN 1995-1-2 [1]. Reported 12
charring depths seem to be quite low considering the 10 B11b05
fact that the extinguishing work was finished about 8
30 to 60 minutes after the end of the fire test. Thus, 6
4
the cross-section in the fire test is larger than
2
assumed in this study and any calculated zero-
0
strength layer is non-conservative. For comparison -2
reasons in Table 3 zero-strength values determined -4
by means of the specific density and by means of the 0 15 30 45 60 75 90
mean batch density are given; differences are very t [min]
limited. The conclusions reported in [16] include the
Figure 5. Determined zero-strength layer for
assumption that the behaviour of the compression
bending tests and three sided fire exposure [15]. Red
zone governs the overall fire performance of some
squares indicate uncertain results.
beams.
Table 3. Zero-strength layer results (minimum, maximum and mean) for all 14 evaluated results reported in
[16] by means of two different material characterisation.
f m,mean
basis of material characterisation r mean [kg/m 3 ] f m,k [N/mm 2 ] [N/mm 2 ] d 0,min [mm] d 0,max [mm] d 0,mean [mm]
reported specific beam densities variable variable variable -3,2 24,6 7,7
mean of reported densities 440 22,8 29,5 -3,7 21,2 7,8
5
ultimate tensile strength of the DF specimens; for 16
d0 [mm]
these tests a ratio of ultimate strength to allowable
14
stress of 2,85 (general value, specified in [17]) was
used for further calculations in the present 12
Table 4. Zero-strength layer results (minimum, maximum and mean) for all 15 evaluated results reported in
[17] as well as for certain results only.
basis of calculation d 0,min [mm] d 0,max [mm] d 0,mean [mm]
all results -3,4 15,2 7,3
certain results 5,6 6,4 6,1
6
reference tests in tension were performed to 10
d0 [mm]
determine the tensile strength between 19,1 and
27,3 N/mm2, which were used to estimate the
ultimate load-bearing resistance. The fire exposed 8
length of the tested members was about 760 mm. The
applied load was in the range of 0,18 to 0,54 of the 6
predicted ultimate load-bearing resistance. Of six
performed fire tests two failed in the connection area 4
at the supports, for one specimen (C04t04, see Figure
C04t04
7) a failure near the connection was observed after
the test. All tests are included in this paper; however, 2
the results for failure due to the connection are
evaluated as uncertain since the timber members 0
would have performed better. Thus, a lower zero-
strength layer than determined here can be expected -2
in these cases. One result of the zero-strength layer 0 15 30 45 60
shows a negative value, which indicates that the t [min]
material properties were better than predicted. The
Figure 7. Determined zero-strength layer for tension
zero-strength layer for members in tension was
tests [18]. Black squares indicate certain results,
determined in general to be lower than 7 mm as
red squares indicate uncertain results.
specified in EN 1995-1-2 [1], see Figure 7 and Table
5.
Table 5. Zero-strength layer results (minimum, maximum and mean) for fire tests in tension reported in [18]
as well as for certain results only.
basis of calculation d 0,min [mm] d 0,max [mm] d 0,mean [mm]
7
bending tests with specimens of a length of 4000 mm exposed to fire on all sides. Dimensions varied from
120 mm to 140 mm in width and 278 mm to 600 mm in depth. The applied load was between 0,23 and 0,30
of the predicted ultimate load-bearing resistance. Due 36
d0 [mm]
to the limited span of 3400 mm the absolute applied 34
loads were rather high and resulted in unintended 32
30
failure modes for beams with depths of 600 mm: 28
shear failure was observed for both tests with 26
24
specimens of higher grade GL32h; the determined 22
zero-strength layers are evaluated as very uncertain 20
18
and may be used to determine zero-strength layers for 16 C04b03
the shear capacity due to the observed failure mode. 14
The specimen C04b03 (see Figure 9) resulted in a 12
10
combined shear and bending failure and was 8
C04b04
evaluated further as uncertain result. Three residual 6
4
cross-sections are reported by the authors. To 2
estimate the moment of inertia of the residual cross- 0
sections available images of the residual cross- 0 15 30 45 60
t [min]
sections were analysed in this study. If no images
were available, the mean of before determined Figure 9. Determined zero-strength layer for
notional charring rates was used. The specimen bending tests [18]. Black squares indicate certain
C04b04 (see Figure 9) had an initial moisture content results, red squares indicate uncertain results, and
of 22,2% at the fire test, thus the result is evaluated as white squares indicate very uncertain results.
uncertain.
Table 7. Zero-strength layer results (minimum, maximum and mean) for fire tests in bending reported in
[18].
basis of calculation d 0,min [mm] d 0,max [mm] d 0,mean [mm]
all results 3,3 34,5 16,5
8
Table 8. Zero-strength layer results (minimum, maximum and mean) for fire tests in
tension reported in [19].
basis of calculation d 0,min [mm] d 0,max [mm] d 0,mean [mm]
reported charring n =0,65 8,5 10,3 9,3
n acc. to EN 1995-1-2 7,3 9,4 8,1
d0 [mm]
to reduce the risk of failure in the range of knots
outside of the knot-free area of about 300 mm. Before 14
the fire tests, reference tests at ambient temperature
12
were performed with finger-jointed boards to obtain
mean strength values of the material [23]. The density 10
of each board as well as in general the residual cross-
sections were determined after the test. The fire tests 8
lasted between 55 and 73,5 minutes. In nearly all cases 6 T01t02
the fire tests with solid boards were performed with
constant load-level of about 25% of the mean tensile 4
strength at ambient temperature; however, for test
2
specimen T01t02 (see Figure 11) the test load was
increased after 40 minutes until failure. As already 0
observed for tests performed by White [17], a small 0 15 30 45 60 75
zero-strength layer of only about 2 mm was calculated t [min]
for this test, in which the load was increased until Figure 11. Determined zero-strength layer for
failure after a certain time of fire exposure; this result tension tests [21], [22]. Black squares indicate
is considered to be uncertain. Results of the certain results, and white squares indicate
determination of the zero-strength layers are given in uncertain results.
Table 9.
Table 9. Zero-strength layer results (minimum, maximum and mean) for all 4 evaluated results reported in
[21], [22] as well as for certain results only.
basis of calculation d 0,min [mm] d 0,max [mm] d 0,mean [mm]
9
procedure, five beams failed during the fire test. The results of fire tests are plotted in Figure 12 as a function
of the predicted bending moment resistance at normal temperature.
1,0 24
Efi/E20 [-]
d0 [mm]
Fire test result 22
20
0,8 Corrected value (load)
18
16
0,6 14
12
0,4 10
R² = 0,49 8
6
0,2 d0 (fire tests)
4
d0 (corrected results)
2
0,0 0
0 15 30 45 60 75 0 15 30 45 60 75
t [min] t [min]
Figure 12. Test results of [24]. Load ratio Efi/E20 Figure 13. Determined zero-strength layer for
versus time of failure. bending tests [24].
In Figure 12, an exponential correlation was fitted to the fire test results to consider the scatter of the material
properties of the glulam beams. In a next step, corrected values were determined to represent fire test results
with perfect fit to the before mentioned correlation function; the failure time was kept constant but the load-
level Efi/E20 (ratio of effect of loads in the fire situation and at normal temperature) was modified. Results of
the corrected values were then used for further evaluation but treated separately. The residual cross-section at
specific failure could not be investigated due to the test set-up. For this study, the notional charring rate n
was determined using images of the residual beams considering a fire exposure of 60 minutes when the fire
test was terminated after the failure of the last beam. A mean value was found to be βn = 0,71 mm/min,
which is in good agreement with n specified in EN 1995-1-2 [1]. The determined zero-strength layer results
for five fire tests as well as the corrected results are shown in Figure 13, the mean values for a determination
by means of the fire test results and the corrected fire test results respectively are given in Table 10.
Table 10. Zero-strength layer results (minimum, maximum and mean) for all 5 evaluated results reported in
[24]. Zero-strength layers derived from the fire tests as well as corrected values are specified.
basis of calculation d 0,min [mm] d 0,max [mm] d 0,mean [mm]
fire tests 11,1 23,1 18,2
corrected results 14,6 17,9 16,6
10
Conclusions
In this paper, results are presented as zero-strength layers determined by fire tests whereby most of the tests
are large-scale fire tests. On the basis of extensive experimental investigations, the large variation of the zero-
strength layer determined could be shown. The paper extends the analysis of the zero-strength layer
significantly by a comprehensive evaluation of 110 fire tests under standard-fire exposure. However, due to
the lack of the characterisation of the material later tested in fire, in many references an uncertainty regarding
the determined zero-strength layer has to be mentioned. Figure 14 gives the mean values for the zero-strength
layer depending on the state of stress for all references analysed. The number of fire tests considered for the
calculation of the shown value are indicated.
18
Zero-strength layer d0 [mm]
n=6 n=8
16
14 members
in
12 compression
10 n=3 n=4 n=11
n=10
8
n=8
6
n=1
4
n=4 n=14 n=2
2
members in tension members in bending
0
Figure 14. Determined zero-strength layer corresponding to fire test results reported in literature.
Fire exposed members in tension
Although truss construction elements are very commonly used, e.g. in attics, only few fire tests with
members in tension are available. The evaluated tests of White [17] and Fragiacomo et al. [19] show a mean
value which agrees very well with the today’s general rule for the zero-strength layer in EN 1995-1-2 [1];
however, uncertain results indicate a higher value for longer fire exposures. Results of [18] and [21] show
higher scatter but are in general in agreement with the other authors. Further, results are in good agreement
with advanced calculations as given in [4].
Fire exposed members in compression
Limited literature with focus on the compression strength in the fire situation is available. However, the
presented tests represent high reliability since tests were performed according to present European testing
standards as well as offering comprehensive reference tests to describe the material properties of the tested
members. Results show a mean value considerably larger than given in EN 1995-1-2 [1]. This was earlier
indicated by Klippel et al. [4] based on advanced calculation with timber material properties given in [1].
Fire exposed members in bending
For bending tests, a very large variation of the results for the zero-strength layer can be observed. References
using obsolete test procedures show either low results or values which agree fairly well with rules given in
EN 1995-1-2 [1]. Although many fire tests were performed in the past, results are uncertain due to the lack of
material characterisation. Further, the test methods are often deviating from today’s standard testing
requirements regarding the heat flux and the loading of the specimens.
Results
Based on the analysis of fire test, the today’s design model in EN 1995-1-2 [1] seems to fit well for tension
members while for compression members the design model is non-conservative. For members in bending,
further investigation and comparison with advanced calculation is needed; a large scatter for the zero-strength
layer was determined, most likely due to the assumptions of the material properties.
11
Acknowledgements
This study was carried out at and funded by SP Wood Technology (formerly SP Trätek), a division of SP
Technical Research Institute of Sweden as well as ETH Zürich. The authors would like to thank R. White and
P. Steer for their help in evaluating some fire tests.
References
[1] EN 1995-1-2:2004, Eurocode 5: Design of timber structures – Part 1-2: General – Structural fire design. European Standard.
[2] ISO 834-1 Fire-resistance tests – Elements of building construction – Part 1: General requirements. International Organization
for Standardization, Genève, Switzerland, 1999.
[3] EN 1363-1, Fire resistance tests - Part 1: General requirements, 1999.
[4] Klippel, M., Schmid, J., Frangi, A.: The Reduced Cross-Section Method for timber members subjected to compression, tension
and bending in fire; CIB W18. Meeting 45; Växjö, Sweden; Lehrstuhl für Ingenieurholzbau, University of Karlsruhe,
Karlsruhe, Germany; 2012.
[5] Schmid, J., König, J.: The Reduced Cross-Section Method for the design of timber structures exposed to fire – Background,
limitations and new developments; Structural Engineering International; 22 (4); 2012.
[6] EN 1995-1-1:2010, Eurocode 5: Design of timber structures – Part 1-2: General design. European Standard.
[7] Dorn, H., Egner, K.: Fire Tests on Glued Laminated Structural Timber (Glulam Beams); original in Holz-Zentralblatt Stuttgart,
(28): 435-438/1961, NRC TT-1131. Ottawa, Canada, 1964.
[8] DIN 4102, Widerstandsfähigkeit von Baustoffen und Bauteilen gegen Feuer und Wärme. DIN Deutsches Institut für Normung
e. V., Berlin, Germany, 1940.
[9] Hall, G.S.: Fire Resistance Tests of Laminated Timber Beams. Timber Research and Development Association, High
Wycombe, U.K. 1968.
[10] BS 476-1, Fire tests on Building materials and structures – part 1: Test conditions. British standard. BSI, British standards
institution. London, UK, 1953.
[11] EN 338 Structural timber – Strength classes. European Standard. European Committee for Standardization. Brussels. 2003.
[12] JCSS, Joint Committee on Structural Safety, "Probabilistic Model Code"; www.jcss.byg.dtu.dk.
[13] Dorn, H., Egner. K.: Brandversuche an brettschichtverleimten Holzträgern unter Biegebeanspruchung - Flame Tests on
Laminated Trusses under Bending Load. Mitteilung aus der Amtl. Forschung und Materialprüfanstalt für das Bauwesen der
T.H. Stuttgart; (in German). 1967.
[14] EN 1194, Timber structures - Glued laminated timber - Strength classes and determination of characteristic values, 1999.
[15] Dreyer, R.: Brettschichtverleimte Binder unter Biege- und Feuerbeanspruchung, Institut für Baustoffkunde und Stahlbetonbau
der technischen Universität Braunschweig, 1970.
[16] Dreyer, R.: Träger, Binder und Decken aus Holz unter Biege- und Feuerbeanspruchung, Institut für Baustoffkunde und
Stahlbetonbau der technischen Universität Braunschweig, 1970.
[17] White, R.H., Tensile Strength of Fire-Exposed Wood Members, 1996.
[18] Peter, M., Göckerl, T.: Bemessung von Voll- und Brettschichtholzbauteilen aus maschinell sortiertem Schnittholz für den
Brandfall – Teil 2: Brandversuche zur Bestätigung der theoretischen Ergebnisse. (in German) Institut des Zimmerer- und
Holzbaugewerbes e.V., Berlin, 2006.
[19] Fragiacomo, M., Menis, A., Moss, P.J., Clemente, I., Buchanan, A.H., Nicolo, B. Predicting the fire resistance of timber
members loaded in tension, Fire and Materials, Fire Mater, John Wiley & Sons, Ltd, 37:114-129, 2013.
[20] Lane, W., Buchanan, A., Moss, P., Fire Performance of Laminated Veneer Lumber (LVL). EWPA, Engineered Wood Products
Association, Madison, United States, 2004.
[21] Klippel M., Frangi A., Hugi E.: Experimental analysis on the fire behaviour of finger-jointed timber members Journal of
Structural Engineering (ASCE), URL: http://ascelibrary.org/doi/abs/10.1061/%28ASCE%29ST.1943-541X.0000851, 2013.
[22] Klippel M., Frangi A.: Fire tests on finger-jointed timber boards - Test report, Institut of Structural Engineering, ETH Zurich,
IBK-Report, under preparation, Zurich, Switzerland, 2013.
[23] Frangi, A., Bertocchi, M., Clauß, S., Niemy, P., Mechanical behaviour of finger joints at elevated temperatures. Wood Science
Technology, DOI: 10.1007/s00226-011-0444-9. 2011.
[24] Lange, D. et al.: Assessment of the impact of different fire scenarios on structural timber performance and reliability – Part 1:
Fire tests; SP Report 2013, under preparation. Borås, Sweden, 2013.
[25] EN 408, Timber structures - Structural timber and glued laminated timber - Determination of some physical and mechanical
properties, 2010.
12