You are on page 1of 1

MODULAR NITROGEN GENERATORS

INS-
INS-1500(EU), INS-
INS-2000(EU), INS-
INS-2500(EU)
Steps in the nitrogen generation process:
1. Air is compressed from the atmosphere and pressurized through a high-pressure Air Compressor (AC).
2. This compressed air is then fed from the Air Storage Tank (AT) to the Nitrogen Cabinet (NC).
3. In the Nitrogen Cabinet (NC), the air passes through the nitrogen membrane.
4. The nitrogen membrane—using an advanced hollow fiber membrane separation process—allows the nitrogen to
separate from the oxygen and any other residual gas.
5. From the membrane, up to 99% nitrogen at a -50 degree C dew point is then piped into the Nitrogen Storage Tank (NT).
6. From the Nitrogen Storage Tank (NT), the nitrogen is piped to an Air Maintenance Device (AMD), which is connected to
the Preaction system (PACV).
7. If the Preaction system (PACV) supervisory pressure drops, the generator resumes operation and automatically supplies
high-purity, dry nitrogen.

POTTER NITROGEN GENERATOR SYSTEM


AIR
COMPRESSOR

BLEEDER
NGP-SPV or INS-PV
VALVE
AC NAMD (choose one)

AIR BVL PURGE


MAINTENANCE VALVE
DEVICE
NC
AIR
STORAGE NT
TANK PACV
NITROGEN
AT STORAGE PREACTION/
1 NITROGEN TANK DRY PIPE
CABINET/ CONTROL
CONTROLLER VALVE
1

You might also like