Professional Documents
Culture Documents
MAC0111062C0
CONTENTS
Page Page
1 Features 2 11 3-way Valve 48
2 Functions 3 12 Servicing Information 61
3 Product Specifications 6 13 Troubleshooting Guide 65
4 Dimensions 12 14 Technical Data 67
5 Refrigeration Cycle Diagram 14 15 Exploded View 71
6 Block Diagram 15 16 Replacement Parts List 72
7 Wiring Diagram 16 17 Exploded View 73
8 Operation Details 17 18 Replacement Parts List 74
9 Operating Instructions 33 19 Electronic Circuit Diagram 75
10 Installation Instructions 38
1 Features
• High Efficiency • Solar Refreshing Deodorizing Filter
− Remove unpleasant odour from the air
• Compact Design
• Quality Improvement
• Comfort Environment − Gas leakage protection
− 8 hours of sleep mode operation − Prevent compressor reverse cycle
− Air filter with function to reduce dust and smoke − Inner protector
− Wider range of horizontal discharge air − Noise prevention during soft dry operation.
− New Automatic air swing and manual adjusted by − Anti-dew Formation Control (Cooling & Soft Dry)
remote control for horizontal airflow. − Overload Protection Control (Heating)
− Outdoor Fan Control
• Auto Restart − Compressor High Pressure Control
− Random auto restart after power failure for safety restart − Blue Coated Condenser
operation
− High resistance to corrosion.
2
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
2 Functions
Remote Control
Self illuminating
button
OFF / ON I TEMP.
Operation OFF / ON Room Temperature Setting
Heating, Cooling, Soft Dry Operation.
MODE • Temperature Setting (16°C to 30°C)
Operation Mode Selection
• AUTO Automatic Operation Mode Automatic Operation
• HEAT Heating Operation Mode • Operation with 2°C higher than
• COOL Cooling Operation Mode standard temperature.
• DRY Soft Dry Operation Mode • Operation with standard temperature.
• Operation with 2°C lower than
standard temperature.
FAN SPEED
Indoor Fan Speed Selection
ON-TIMER
• FAN Low Fan Speed OFF-TIMER
Timer Operation Selection
• FAN Medium Fan Speed
• FAN High Fan Speed • 24-hour, OFF / ON Real Timer Setting.
• AUTO Automatic Fan Speed
FAN
TIME
AIR SWING
Time / Timer Setting
Vertical Airflow Direction Control
• Hours and minutes setting.
• Vertical Automatic Airflow
SET
Direction Control and Manual CANCEL
Airflow Direction Control (5 Timer Operation Set / Cancel
stages of adjustment).
• ON Timer and OFF Timer setting and
• Horizontal Automatic Airflow
cancellation.
Direction Control and Manual
Airflow Direction Control (5
stages of adjustment). CLOCK
Clock Setting
POWERFUL • Current time setting.
Powerful Mode Operation OFF/ON
SLEEP
ECONOMY Sleep Mode Operation OFF / ON
Economy Mode Operation OFF/ON
3
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Indoor Unit
AUTO
OFF / ON
Automatic Operation Button Sleep Mode Auto Control
• Press for < 5s to operate Automatic • Indoor Fan operates refer to Indoor Fan
operation mode. Speed control.
(Used when the remote control cannot be used.) • Operation stops after 8 hours.
• Press continuously for 5s or < 10s to
operate Test Run/Pump down. “Beep” Indoor Fan Speed Control
sound will be heard at the 5th second.
(Used when test running or servicing.) • High, Medium and Low.
• Press continuously for 10s and above to • Automatic Fan Speed Mode
omit or resume the remote control signal – Heating : Fan speed varies from Me
receiving sound. “Beep, beep” sound will → SSLo in accordance with
be heard at the 10th second. indoor heat exchanger.
– Cooling : Fan rotates at Hi, Me and
Operation Indication Lamps (LED) SLo speed. Deodorizing
control is available.
• POWER (Green) .......... Lights up in operation, – Soft Dry : Fan rotates at SLo speed.
blinks in Automatic Deodorizing control is
Operation Mode judging available.
and Hot Start operation.
• SLEEP (Orange) ......... Lights up in Sleep Mode Airflow Direction Control
Operation.
• TIMER (Orange) ......... Lights up in Timer Setting. • Automatic air swing and manual adjusted
• POWERFUL (Orange) ... Lights up in Powerful by remote control for vertical and horizontal
Mode Operation. airflow.
• ECONOMY (Green) ...... Lights up in Economy
Mode Operation. Time Delay Safety Control
• Restarting is inhibited for appro. 3 minutes.
Operation Mode
• Heating, Cooling, Soft Dry and Automatic 7 Minutes Time Save Control
Mode. • Cooling Operation only.
4
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Outdoor Unit
5
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
3 Product Specifications
Unit CS-A18BK CU-A18BK
Power Source Phase, Voltage, Cycle (1) Single, 230 - 220, 50 Hz
(4)
(2) Single, 240 - 230, 50 Hz
(3) Single, 220, 50 Hz
Cooling Capacity kW (BTU/h) (1)
(2) 5.30 - 5.30 (18,100 - 18,100)
(4)
(3) 5.30 (18,100)
Heating Capacity kW (BTU/h) (1) 5.70 - 5.65 (19,400 - 19,300)
(4)
(2) 5.75 - 5.70 (19,600 - 19,400)
(3) 5.65 (19,300)
INTAKE
Air Volume Indoor Air (Lo) m3/min (cfm) (1) Cooling; 13.1 (460) - 13.1 (460)
(2) Heating; 14.1 (500) - 14.1 (500) —
(4)
(3) Cooling; 13.1 (460) —
Heating; 14.1 (500)
Indoor Air (Me) m3/min (cfm) (1) Cooling; 14.6 (520) - 14.6 (520)
(2) Heating; 14.7 (520) - 14.7 (520) —
(4)
(3) Cooling; 14.6 (520) —
Heating; 14.7 (520)
Indoor Air (Hi) m3/min (cfm) (1) Cooling; 15.4 (540) - 15.4 (540)
(2) Heating; 15.9 (560) - 15.9 (560) —
(4)
(3) Cooling; 15.4 (540) —
Heating; 15.9 (560)
Indoor Air (SHi) m3/min (cfm) (1) Cooling; 15.9 (560) - 15.9 (560)
(2) Heating; 15.9 (560) - 15.9 (560) —
(4)
(3) Cooling; 15.9 (560) —
Heating; 15.9 (560)
Noise Level dB (A) (1) Cooling; High 43 - 43, Low 38 - 38 Cooling; High 55 - 54
(4) Heating; High 42 - 42, Low 38 - 38 Heating; High 56 - 55
(2) Cooling; High 43 - 43, Low 38 - 38 Cooling; High 56 - 55
Heating; High 42 - 42, Low 38 - 38 Heating; High 57 - 56
(3) Cooling; High 43, Low 38 Cooling; High 54
Heating; High 42, Low 38 Heating; High 55
Power level dB (1) Cooling; 54 - 54 Cooling; 68 - 67
Heating; 53 - 53 Heating; 69 - 68
(2) Cooling; 55 - 55 Cooling; 70 - 69
Heating; 54 - 54 Heating; 72 - 71
(3) — —
(4)
6
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
7
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Note:
• Specifications are subject to change without notice for further improvement.
• (1) — CS-A18BKP/CU-A18BKP5 (Europe).
• (2) — CS-A18BKP-2/CU-A18BKP5-2 (Oceania).
• (3) — CS-A18BKP-3/CU-A18BKP5-3 (Argentina).
• (4) — CS-A18BKP-6/CU-A18BKP5-6 (Turkey).
8
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
INTAKE
Air Volume Indoor Air (Lo) m3/min (cfm) (1) Cooling; 14.4 (510) - 14.4 (510) —
(2) Heating; 15.6 (550) - 15.6 (550)
(4)
(3) Cooling; 14.4 (510) —
Heating; 15.6 (550)
Indoor Air (Me) m3/min (cfm) (1) Cooling; 16.4 (580) - 16.4 (580) —
(2) Heating; 16.4 (580) - 16.4 (580)
(4)
(3) Cooling; 16.4 (580)
Heating; 16.4 (580) —
Indoor Air (Hi) m3/min (cfm) (1) Cooling; 17.5 (620) - 17.5 (620) —
(2) Heating; 18.1 (640) - 18.1 (640)
(4)
(3) Cooling; 17.5 (620) —
Heating; 18.1 (640)
Indoor Air (SHi) m3/min (cfm) (1) Cooling; 18.1 (640) - 18.1 (640) —
(2) Heating; 18.1 (640) - 18.1 (640)
(4)
(3) Cooling; 18.1 (640) —
Heating; 18.1 (640)
Noise Level dB (A) (1) Cooling; High 47 - 47, Low 41 - 41 Cooling; High 60 - 59
(4) Heating; High 46 - 46, Low 41 - 41 Heating; High 61 - 60
(2) Cooling; High 47 - 47, Low 41 - 41 Cooling; High 61 - 60
Heating; High 46 - 46, Low 41 - 41 Heating; High 62 - 61
(3) Cooling; High 47, Low 41 Cooling; High 59
Heating; High 46, Low 41 Heating; High 60
Power level dB (1) Cooling; 58 - 58 Coolling; 73 - 72
Heating; 57 - 57 Heating; 74 - 73
(2) Cooling; 59 - 59 Coolling; 75 - 74
Heating; 59 - 59 Heating; 78 - 77
(3) — —
(4)
9
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
10
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Note:
• Specifications are subject to change without notice for further improvement.
• (1) — CS-A24BKP/CU-A24BKP5 (Europe).
• (2) — CS-A24BKP-2/CU-A24BKP5-2 (Oceania).
• (3) — CS-A24BKP-3/CU-A24BKP5-3 (Argentina).
• (4) — CS-A24BKP-6/CU-A24BKP5-6 (Turkey).
11
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
4 Dimensions
12
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
13
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
14
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
6 Block Diagram
15
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
7 Wiring Diagram
16
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
8 Operation Details
8.1. Cooling Mode Operation
Cooling in operation according to Remote Control setting.
• When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
• When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
• The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
Anti-Freezing Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
17
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
When Automatic Fan Speed is selected at Remote Control during cooling operation.
• Fan speed rotates in the range of Hi to Me.
• Deodorizing Control.
18
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
• The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
• During Soft Dry operation, the Indoor Fan will operate at SLo speed.
• Once room temperature reaches below Soft Dry OFF temperature. Indoor Fan, Compressor and Outdoor Fan stop for 6
minutes.
• Once the compressor stops, it will not start for 3 minutes during Cooling operation.
Anti-Freezing Control
• Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor
stops.)
• Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting
is valid during compressor stops.)
When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.
• Fan speed off and on at SLo speed.
• Deodorizing Control.
19
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
20
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
• When the compressor is stopped by Power Switch, Remote Control or there is a power failure, it restarts after 3 minutes when
the Power Switch, Remote Control is turned ON or the power supply is resumed.
• When the setting temperature is reached during heating operation, the compressor stops and it will not start for 4 minutes.
During starting of Heating mode and after deice, Outdoor Fan ON for 90 sec. (Hi).
When Heating operation starts, Indoor Fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
21
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
When Automatic Fan Speed is selected at Remote Control during heating operation.
• Fan speed rotates in the range of Me → SLo according to the heat exchanger temperature.
22
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Deicing Control
• Normal Deicing
Deice operation detection commences in Heating operation starts or 60 minutes after previous deice operation. If the
outdoor piping temperature drops to -4°C or 50 sec. continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
• Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and
after compressor starts for 1 minutes, deicing starts.
• After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.
23
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
24
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
1. When the Automatic Mode Operation is selected, the indoor fan operates at SLo fan speed for 25 seconds to sense intake air
temperature and determine the 1st operation mode. If indoor intake air temperature is less than 16°C, Heating mode will
immediate operate.
2. Operation mode will be determine again after 1 hour of operation, if the room temperature reaches to set temperature and
compressor off time is over 7 minutes 30 seconds continuously.
The present operation mode will be continued, if the room temperature does not reach to set temperature (Compressor keeps running)
eventhough after 1 hour from automatic operation mode started.
O O
Soft Dry 23°C Soft Dry Not Applicable (Judgement: (Judgement:
Heating 23°C & Above) Below 23°C)
O O
Heating Cooling (Judgement: Not Applicable (Judgement:
23°C Heating Above 23°C) 23°C & below)
• The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX1 at
indoor electronic controller.
25
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Heating Operation
• If there is a power failure, operation will be automatically restarted after 3 to 5 1/2 minutes when the power is resumed.
It will start with previous operation mode and airflow direction.
• Restart time is decided randomly using 4 parameter:-
Intake air temperature, setting temperature, fan speed and Air Swing Blade position.
• Auto Restart Control is not available when Timer or Sleep Mode is set.
• This control can be omitted by open the circuit of JX2. (Refer Circuit Diagram)
26
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
27
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
28
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
However, if the “Automatic Operation Button” has been pressed the Automatic operation will be activated.
If you do not require this operation, you may change it by using the remote control.
29
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Purpose of this operation is to save or reduced electrical power consumption of the room air conditioner.
However consumer is advised to use Economy Mode operation after the room temperature reaches the desired temperature.
2. Heating Mode
• When the Economy Mode is set, the temperature will be automatically decreased 0.5°C against the present setting
temperature.
30
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
2. Heating Mode
• When the Powerful Mode is set, the set temperature will be automatically increased 3°C against the present setting
temperature.
31
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
A. Purpose
To reduce starting current lower than 45A.
B. Basic Operation
1. When indoor relay is turn ON, starting capacitor will be turn ON through RY-C for ~ 1 second. After that reactor will be turn
OFF through RY-L and in the same time RY-C will turn OFF causes starting capacitor to be OFF.
2. When the unit operation ON by remote controller or thermostat OFF → ON the starter kit will be functioned.
3. When the unit operation OFF → ON by the inner protector, the starter kit will be not function, mean the unit will be ON as
a normal operation.
32
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
9 Operating Instructions
SAFETY PRECAUTIONS
■ Installation Precautions ■ Operation Precautions
Before operating, please read the following
“Safety Precautions” carefully.
! Warning ! Warning
● To prevent personal injury, injury to others and This sign warns of death or serious injury.
property damage, the following instructions must be ● Do not install, remove and reinstall the unit by
followed. yourself. ● Do not share outlet.
Improper installation will cause leakage, electric ● Do not insert plug to operate the unit. Do not
● Incorrect operation due to failure to follow instructions pull out plug to stop the unit.
shock or fire. Please engage an authorized dealer
will cause harm or damage, the seriousness of which or specialist for the installation work. ● Do not operate with wet hands.
is classified as follow:
● Do not damage or modify the power cord.
● Do not insert finger or other objects into the
! Warning indoor or outdoor units.
● Plug in properly.
● This room air conditioner must be ● Use specified power cord.
! Caution earthed.
Improper grounding could cause
This sign warns of damage to property. electric shock.
● Ensure that the drainage piping is OFF
These symbols (with a black background) denote ● Switch off the power supply before cleaning.
actions that are COMPULSORY. ● Ventilate the room regularly.
● Pay attention as to whether the installation
rack is damaged after long period of usage.
OFF
3
HE
1
A
AT
ON CO
OL
OF AU
F TTO DRY
AU FA
AN
TTO N
PO AU
WE TE FA
AN
N
TTO
RFUL MP
3 Ste
p
MO
AIR
DE
SW
ING
EC
ON
OM
OF
F/O
N
1 Y
ON SL
EE
OFF 2 P
FAN
SP
EE
CHE 3 D
CK TIM SE
RES ER T
ET CA
CLO NC
CK EL
2
BAT +
TER
Y
7 6 5 4
● Remote Control Indication Sticker
1 Front Panel (Europe & Argentina only)
1 Front Panel
2 Air Intake Vent
2 Air Filters
3 Power Supply Cord
3 Air Purifying Filter
4 Air Outlet Vent
5 Drain Hose
33
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
AU
CO
O
AU L D
TO RY
FA
N
PO AU TO
WER T TO
1
FUL FA
2 Operation Display
N
MO
DE
AU AIR EC
TO SW ON
IN OM
3 OFF/ON
7 Vertical Airflow Direction Button
POWERFUL
!
4
8 ON-Timer Button
5 # 1 Slide down the remote control cover completely
MODE ECONOMY SLEEP
6 9 OFF-Timer Button
$
AIR SWING
7
FAN SPEED
$
2 Insert the batteries
0 Reset Point
1 2 3 – Be sure the direction is correct
8 ON SET
% (Press with fine-tipped object to clear the memory) – 12.00 at display - flashing
9 ^ • Set the current time (CLOCK) immediately to
OFF CANCEL ! OFF/ON Button prevent battery exhaustion.
TIMER & (self-illuminating button)
0 CHECK RESET CLOCK
* ● About the batteries
@ Sleep Mode Operation Button • Can be used for approximately one year.
(
# Fan Speed Selection Button ● Observe the following when replacing the
batteries
$ Horizontal Airflow Direction Button • Replace with new batteries of the same type.
• Do not use rechargeable batteries (Ni-Cd).
● Remote Control Signal. % Timer Set Button • Remove the batteries if the unit is not going to be
• Make sure it is not obstructed. used for a long period.
• Maximum distance : 10 m. ^ Timer Cancellation Button
• Signal received sound.
One short beep or one long beep.
& Time-Setting Button
● Notes for Remote Control.
• Do not throw or drop. * Clock Button
• Do not get it wet.
• Certain type of fluorescent lamps may affect ( Remote Control Cover
signal reception. Consult your dealer.
AU
TO
HE
Cooling Model Heat Pump Model
AT
CO
1
ON
2 2 OF
F
O
AU L D
TO RY
AU
TO
FA
N COOL – 26°C ~ 28°C COOL – 26°C ~ 28°C
PO A
TE FA UTO
WER N
DRY – 1°C ~ 2°C DRY – 1°C ~ 2°C
6 3 MO
DE
FUL MP
2
G Y
SL
EE
P
6
HEAT – 20°C ~ 24°C
FAN
1 Connect the power supply cord to an independent • Operation with 2°C higher than the standard
power supply temperature.
■ To start the operation
• Press 1. • Operation with the standard temperature.
2 Open the front panel
• POWER indicator (green) on the indoor unit will light
up. • Operation with 2°C lower than the standard
3 Remove the air filters • To stop, press once more. temperature.
34
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
■ Setting the Fan Speed ● Use this air conditioner under the following ● Operation Details
• Press 4 to select:- conditions:
FAN – Low Fan Speed COOL – Cooling Operation
FAN – Medium Fan Speed • To set the room temperature at your preference
FAN – High Fan Speed Cooling Model cooling comfort.
AUTO
FAN – Automatic Fan Speed (Unit in °C)
The speed of the indoor fan is adjusted AUTO – Automatic Operation
automatically according to the operation. DBT: Dry Bulb Temp Indoor Outdoor • Sense indoor temperature to select the optimum
The indoor fan stops occasionally during WBT: Wet Bulb Temp mode.
DBT WBT DBT WBT
cooling operation. • Temperature is not displayed on the remote control
Maximum Temperature 32 23 43 26 during AUTO operation.
■ Setting the Vertical Airflow Direction.
• Press 5 to select:- Minimum Temperature 16 11 16 11 DRY – Soft Dry Operation
• A very gentle Cooling Operation, prior to
AUTO dehumidification. It does not lower the room
temperature.
• During Soft Dry operation, the indoor fan operates at
Heat Pump Model Low fan speed.
AUTO • For COOL/DRY operation.
Swing up/down automatically. (Unit in °C)
HEAT – Heating Operation
AUTO • For HEAT operation DBT: Dry Bulb Temp Indoor Outdoor (for Heat Pump Model only)
(For Heat Pump Model only) WBT: Wet Bulb Temp • Heat is obtained from outdoor air to warm up the
DBT WBT DBT WBT
When the discharge air temperature is room. When the outdoor ambient air temperature
low such as at the start of the heating Maximum Temperature-Cooling 32 23 43 26 falls, the heating capacity of the unit might be
operation, the air blows at horizontal (Maximum Temperature-Heating) (30) (-) (24) (18) reduced.
level. As the temperature rises, the hot • Defrosting Operation
air blows in a downwards direction. Minimum Temperature-Cooling 16 11 16 11 Depend on the outdoor temperature, the operation
(Minimum Temperature-Heating) (16) (-) (-5) (-6)
occasionally stops to melt the frost on the outdoor
■ Setting the Horizontal Airflow Direction.
unit.
• Press 6 to select:-
FAN – Air Circulation Operation
● Notes (for Cooling Model only)
Indoor
Horizontal Unit • If the unit is not going to be used for an extended • When the room temperature reaches the set
Airflow period of time, turn off the main power supply. If it is temperature, operation commences at Low airflow
Direction left at the ON position, approximately 2.5 W of volume. It stops when the room temperature drops to
Remote AUTO
electricity will be used even if the indoor unit has been
Control 2°C below the set temperature.
turned off with the remote control.
• If operation is stopped, then restart immediately, the (It is useful when using a heater).
unit will resume operation only after 3 minutes.
AUTO • For COOL/DRY operation.
Swing left/right automatically.
8 POWERFUL OFF/ON
CONVENIENCE OPERATION
■ Sleep Mode Operation ■ Economy Mode Operation
MODE ECONOMY SLEEP
To obtain a comfortable room temperature while To save electrical power consumption.
7 6 sleeping:- Please use this mode when the room has reached
AIR SWING
• Press 6. your desired temperature.
FAN SPEED
• Sleep mode indicator on the indoor unit will light up. • Press 7.
1 2 3 • To cancel this operation, press once more. * Economy mode indicator (green) on the indoor unit
1 ON SET
3 will light up.
5 4 ● Sleep Mode Operation Details • Press once more to cancel this operation.
OFF CANCEL
• When the room temperature reaches the set
TIMER 2 temperature, the airflow volume will change to low ■ Powerful Mode Operation
automatically. To obtain the set temperature quickly.
SETTING THE TIMER • Sleep Mode Operation time is 8 hours. • Press 8.
• When used together with the timer, the timer has a * Powerful mode indicator (orange) on the indoor
Ensure that the current time is correct before setting the priority. unit will light up.
timer. The timer cannot be set if the time display is * Powerful mode will operate for 15 minutes only.
flashing. Cooling Model • To cancel this operation, press once more.
■ ON-TIMER Operation ● Economy / Powerful Mode Operation Details
To start the air conditioner operation automatically.
• Economy and Powerful operation cannot be
• Press 1 to set the operation. Temperature Approx. 0.5°C
• Press 2 to increase or decrease the time. Approx.
increase. selected simultaneously.
ST
• Then press 3. e e 0.5°C • The changes of the temperature and airflow volume
increase.
• To cancel this operation, press 4. tm
• Cooling or Soft Dry are automatic.
t p
e
i r
Sleep Operation for sleep shift • The remote control display remains unchanged.
■ OFF-TIMER Operation Operation operation will start to
n a button is
Sleep shift • If sleep button or operation mode button is pressed,
operation avoid overcooling.
To stop the air conditioner operation automatically. g t pressed. economy or powerful operation will be cancelled.
• Press 5 to set the operation. u starts.
• During FAN – Air circulation operation, the powerful
• Press 2 to increase or decrease the time. r
e 0~1 hour ← 1 hour → Time and economy operation are not available.
• Then press 3.
• To cancel this operation, press 4. after approx. 8 hours of sleep shift (cooling model only)
operation, it will stop automatically.
35
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
36
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
TROUBLESHOOTING
■ Normal Operation ■ Call the Dealer Immediately
If the following conditions occur, turn off and unplug the
Is it okay? This is the answer
main power supply, and then call the dealer immediately.
• Air conditioner has been restarted, but does not • This is to protect the air conditioner. Wait until the air
operate for 3 minutes. conditioner begins to operate. • Abnormal noise is heard during operation.
• A sound like water flowing can be heard. • This is the sound of refrigerant flowing inside the air • Water or foreign material gets into the remote
conditioner. control by mistake.
• It seems that fog is coming out from the air • Condensation occurs when the airflow from the air
conditioner. conditioner cools the room. • Water leak from the indoor unit.
• The room has a peculiar odour. • This may be a damp smell emitted by the wall, • Switches or buttons do not operate properly.
carpet, furniture or clothing in the room.
• This is to remove smell emitted by the surroundings. • The circuit breaker switches off frequently.
• During Automatic Fan Speed setting,
indoor fan stops occasionally.
• Power supply cord and plug become unusually
• The outdoor unit emits water or steam. • In COOL/DRY operation, moisture in the air warm.
condenses into water on the cool surface of outdoor
unit piping that causes dripping.
• (For Heat Pump Model only) • This is to melt the frost which has accumulated on
Operation stops for about 12 minutes during the outdoor unit (defrosting operating). This will take
heating (The power indicator blinks). no longer than about 12 minutes. Water drips from
the outdoor unit. Wait until this operation ends. (the
power indicator will light up).
(Frost will accumulates on the outdoor unit when the
outdoor temperature is low and humidity is high.)
• (For Heat Pump Model only) • This is to prevent undesired cooling effect during
During heating operation, indoor fan may heating operation.
run at on and off conditions.
■ Abnormal Operation
Is it okay? Please check
• The air conditioner does not operate. • Has the circuit breaker been tripped?
• Has the power plug been removed from the wall
outlet?
• Is the timer being used correctly?
• Air conditioner produces loud noise during • Is the installation work slanted?
operation. • Is the front grille closed properly?
• The air conditioner does not cool or warm • Has the temperature been set incorrectly?
effectively. • Are the filters dirty?
• Are the intake or outlet vents of the outdoor unit
obstructed?
• Are all windows and doors closed?
37
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
10 Installation Instructions
Required tools for Installation Works
1. Philips screw driver 5. Spanner 9. Gas leak detector 13. Multimeter
2. Level gauge 6. Pipe cutter 10. Measuring tape 14. Torque wrench
18 N.m (1.8 kgf.m)
55 N.m (5.5 kgf.m)
65 N.m (6.5 kgf.m)
3. Electric drill, hole core drill 7. Reamer 11. Thermometer 15. Vacuum pump
(ø70 mm)
4. Hexagonal wrench (4 mm) 8. Knife 12. Megameter 16. Gauge manifold
This indication shows the possibility of causing injury or damage to properties only.
Symbol with background white denotes item that is PROHIBITED from doing.
• Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
1. Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire.
2. Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire.
3. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or
electrical shock.
4. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
done, the set will drop and cause injury.
5. For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
6. Use the specified cable (2.5 mm2) and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no
external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
cause heat-up at connection point of terminal, fire or electrical shock.
8. When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
9. Do not damage or use unspecified power supply cord. Otherwise, it will cause fire or electrical shock.
10. Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet with
other electrical appliances. Otherwise, it will cause fire or electrical shock.
38
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
1. The equipment must be earthed. It may cause electrical shock if grounding is not perfect.
2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at
surrounding of the unit, it may cause fire.
3. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
furniture.
39
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Attached accessories
Piping size Rated Max. Max. Additional
Model Gas Liquid Length Elevation Piping Refrigerant
(m) (m) Length (g/m)
(m)
C18BK, 1/2” 1/4” 5 20 25 20
V18BK
C24BK,
V24BK, 5/8” 1/4” 5 20 25 30
XC24BK
A18BK, 1/2” 1/4” 5 20 25 20
W18BK
A24BK, 5/8” 1/4” 5 20 25 30
W24BK
Example: For A24BK
If the unit will be installed at a 10m distance, the quantity of
additional refrigerant should be 75g...(10 - 7.5)m × 30g/m = 75g
INDOOR UNIT
• There should not be any heat source or steam near the
unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into
consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
• Recommended installation height for indoor unit shall be
at least 2.3 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short
circuit of the discharged air.
• If piping length is over 7.5m, additional refrigerant
should be added as shown in the table.
40
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
The mounting wall is strong and solid enough to prevent it from Caution
the vibration. When the wall is hollow, please be sure to use the
sleeve for tube ass’y to prevent dangers caused by
mice biting the connecting cable.
41
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
(This can be used for left rear piping & left bottom piping also.)
42
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
• Secure the cable onto the control board with the holder
(clamper).
43
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
44
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
10.3.4. (a) EVACUATION OF THE EQUIPMENT (FOR EUROPE & OCEANIA DESTINATION)
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.
1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve.
• Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4. Close the valve of both the Low and High sides of the charging set and turn off the vacuum pump. Make sure that the needle
in the gauge does not move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at a torque of 18 N.m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.
CAUTION
• If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
• If the leak stops when the piping connections are tightened further, continue working from step 3.
• If the leak does not stop when the connections are retightened, repair the location of leak.
• Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause
frostbite.
45
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
2) Air purging
The air remaining in the Refrigeration cycle which contains
moisture may cause malfunction on the Compressor.
1. To purge the air, push the pin on the Gas side 3-way
valve for three seconds with a Hexagonal wrench and
set it free for one minute.
• Repeat this for three times.
2. To balance the refrigerant, close the low pressure side
valve on the Manifold gauge and release refrigerant
from the piping through service port until the gauge
indicates 0.5 - 0.3 MPa.
3. Set both 3-way valves to open position with the
Hexagonal wrench for the unit operation.
3. Secure the cable onto the control board with the holder (clamper).
4. Attach the control board cover back to the original position with the screw.
46
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
1. Please carry out insulation at pipe connection portion as • Operate the unit at cooling operation mode for fifteen
mentioned in Indoor/Outdoor Unit Installation Diagram. minutes or more.
Please wrap the insulated piping end to prevent water from • Measure the temperature of the intake and discharge air.
going inside the piping.
• Ensure the difference between the intake temperature and
2. If drain hose or connecting piping is in the room (where dew the discharge is more than 8°C.
may form), please increase the insulation by using POLY-E
FOAM with thickness 6 mm or above.
CHECK ITEMS
• Open front panel and remove air filters. Is the connecting cable being fixed to terminal board firmly?
(Drainage checking can be carried out without removing the
front grille.) Is the connecting cable being clamped firmly?
• Pour a glass of water into the drain tray-styrofoam. Is the drainage OK?
• Ensure that water flows out from drain hose of the indoor (Refer to “Check the drainage” section)
unit.
Is the earth wire connection properly done?
47
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
11 3-way Valve
3-way Valve (Liquid Side) 3-way Valve (Gas Side)
48
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Required tools: Hexagonal wrench, adjustable wrench, The air in the indoor unit and in the piping must be purged. If air
torque wrenches, wrench to hold the remains in the refrigeration pipings, it will affect the
joints, gas leak detector, and charging compressor, reduce the cooling capacity, and could lead to a
set. malfunction.
Procedure:
1. Connect a charging hose with a push pin to the Low 5. Disconnect the charging hose from the vacuum pump
and High sides of a charging set and the service ports and from the service ports of the 3-way valves.
of a 3-way valves. 6. Tighten the service port caps of both the 3-way valves
• Be sure to connect the end of the charging hose with the at a torque of 18 N.m with a torque wrench.
push pin to the service port. 7. Remove the valve caps of both the 3-way valves.
2. Connect the centre hose of the charging set to a Position both of the valves to “open” using a hexagonal
vacuum pump. wrench (4 mm).
3. Turn on the power switch of the vacuum pump and 8. Mount the valve caps onto both of the 3-way valves.
make sure that the needle in the gauge moves from 0 • Be sure to check for gas leakage.
cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate
the air for approximately 10 minutes.
Caution
4. Close the valve of both the Low adn High sides of the If gauge needle does not move from 0 cmHg (0 MPa)
charging set and turn off the vacuum pump. Make sure to -76 cmHg (-0.1 MPa) in step (3) above, take the
following measures:
that the needle in the gauge does not move after
approximately 5 minutes. If the leaks stop when the piping connections are
tightened further, continue working from step (3).
BE SURE TO TAKE THIS PROCEDURE IN ORDER TO
If the leaks do not stop when the connections are
AVOID REFRIGERANT GAS LEAKAGE. retightened, repair the location of the leak.
49
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Procedure:
1. Confirm that both the 3-way valves are set to the open 6. Operate the air conditioner at the cooling cycle and
position. stop it when the gauge indicates 0 kg/cm 2G (0 MPa).
• Remove the valve stem caps and confirm that the valve • If the unit cannot be operated at the cool condition
stems are in the open position. (weather is rather cool), press the Pump Down Switch
• Be sure to use a hexagonal wrench to operate the valve on the Indoor unit.
stems. • So that the unit can be operated.
2. Operate the unit for 10 to 15 minutes. 7. Immediately set the gas side 3-way valve to the close
position.
3. Stop operation and wait for 3 minutes, then connect the • Do this quickly so that the gauge ends up indicating 1 to
charge set to the service port of the 3-way valve. 3 kg/cm2G (0.1 MPa to 0.3 MPa)
• Connect the charge hose with the push pin to the Gas
side service port. 8. Use refrigerant reclaiming equipment to collect
refrigerant from indoor unit and pipes.
4. Air purging of the charge hose.
• Open the low-pressure valve on the charge set slightly 9. Disconnect the charge set, and mount both the 3-way
to purge air from the charge hose. valve’s stem nuts and the service port caps.
• Use a torque wrench to tighten the service port cap to a
torque of 18 N.m.
5. Set the Liquid side 3-way valve to the close position.
• Be sure to check for gas leakage.
50
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
WHEN REINSTALLING AN AIR CONDITIONER, BE SURE TO If air remains in the indoor unit and refrigeration pipes, it will
EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES affect the compressor, reduce to cooling capacity, and could
in the following procedure. lead to a malfunction.
Procedure:
1. Connect a charging hose with a push pin to the Low • BE SURE TO USE REFRIGERANT RECLAIMING
and High sides of a charging set and the service port of EQUIPMENT WHILE DISCHARGING THE
the 3-way valve. REFRIGERANT.
• Be sure to connect the end of the charging hose with the • Purge the air from charge set’s centre hose.
push pin to the service port. • Be sure to check for gas leakage.
2. Connect the centre hose of the charging set to a
vacuum pump.
3. Turn on the power switch of the vacuum pump and Caution
make sure that the needle in the gauge moves from 0 If gauge needle does not move from 0 cmHg (0 MPa) to
cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate -76 cmHg (-0.1 MPa) in step (3) above, take the
following measures:
the air for approximately 10 minutes.
If the leaks stop when the piping connections are
4. Close the valve of both Low side and High side of the tightened further, continue working from step 3.
charging set and turn off the vacuum pump. Make sure
If the leaks do not stop when the connections are
that the needle in the gauge does not move after retightened, repair the location of the leak.
approximately 5 minutes.
BE SURE TO TAKE THIS PROCEDURE IN ORDER TO
AVOID REFRIGERANT GAS LEAKAGE.
7. Tighten the service port caps of both the 3-way valves
5. Disconnect the charging hose from the vacuum pump.
at a torque of 18 N.m with a torque wrench.
6. Charge the pipes and indoor unit with gas refrigerant
8. Remove the valve caps of both the 3-way valves.
from liquid (High) side 3-way valve service port and
Position both of the valves to “open” using a hexagonal
then discharge the refrigerant until gas side (Low) side
wrench (4 mm).
gauge needle indicates 3 kg/cm2 (0.3 MPa).
9. Mount valve caps onto the 3-way valves.
51
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Procedure:
1. Confirm that both the 3-way valves are set to the
opened position.
4. Open the valve (Low side) on the charge set and loosen
the hose connected with the Refrigerant Reclaiming
Equipment to purge the air from the hose.
52
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
11.1.5. Evacuation
Procedure:
1. Connect the vacuum pump to the charge set’s centre
hose.
53
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
(After Evacuation)
Procedure:
1. Connect the charge hose to the charging cylinder. 4. Immediately disconnect the charge hoses from both 3-
• Connect the charge hose which you disconnected from way valve service ports.
the vacuum pump to the valve at the bottom of the
cylinder. 5. Mount the valve stem nuts and the service port caps
onto the 3-way valves.
2. Purge the air from the charge hose. • Use torque wrench to tighten the service port caps to a
• Open the valve at the bottom of the cylinder and use a torque of 18 N.m.
screwdriver to press the check valve on the charge set • Be sure to check for gas leakage.
to purge the air (be careful of the liquid refrigerant).
3. Open the High side on the charge set and charge the
refrigerant to the unit.
• Be sure to open only the High side valve on the charge
set to charge the system from the liquid-side (high-
pressure) pipe. (If the system cannot be charged with
the specified amount of refrigerant, operate the
compressor until the specified amount can be charged,
and then close the valve at the bottom of the charge
cylinder.)
54
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Procedure:
1. Recheck the piping connections. 8. Use torque wrench to tighten the service port cap to a
2. Open the valve caps and service port caps for both torque of 18 N.m.
3-way valves. 9. Set the both 3-way valves to the open position.
3. Connect the charging cylinder to the manifold gauge as 10. Mount the valve caps to the 3-way valves.
shown above. 11. Check for gas leakage.
4. Open the valve of the low pressure side of manifold • At this time, especially check for gas leakage from the
gauge counterclockwise for 10 seconds, and then close both 3-way valve’s caps, and from the service port caps.
it.
5. Check for gas leakage.
• Check the flare connections for gas leakage. Caution
6. Purge the air from the system. If gas leakage is discovered in step (3) above, take
the following measures:
• Open the Low pressure side valve of the manifold
a. Re-tighten the connecting portion with torque
gauge. wrenches.
• Press the service port pin with the hexagonal wrench to If the leakage ceases, continue the works from
purge the air for three seconds and then wait for one step (4).
minute. b. Locate and repair the leak. (Gas leak detector)
Repeat this three times or more. Repeat the works from step (1).
7. Balance the refrigerant in the pipings and the indoor
unit.
• Close the Low pressure side valve of the manifold
gauge.
• Press the service port pin with the hexagonal wrench to
release the refrigerant until the gauge indicates 0.1 to
0.3 MPa.
55
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Procedure:
1. Confirm that both the 3-way valves are set to the open 6. Operate the air conditioner at the cooling cycle and
position. stop it when the gauge indicates 0.1 MPa.
• Remove the valve caps and confirm that the valve caps • If the unit cannot be operated at the cooling (weather is
are in the raised position. rather cool), press the Pump Down switch on the Indoor
• Be sure to use a hexagonal wrench to operate the valve unit.
stems. • So that the unit can be operated.
2. Operate the unit for 10 to 15 minutes. 7. Immediately set the gas side (Low side) 3-way valve to
the close position.
3. Stop operation and wait for 3 minutes, then connect the • Do this quickly so that the gauge ends up indicating 0.1
manifold gauge to the service port of the 3-way valve as 0.3 MPa.
shown above.
• Connect the manifold gauge to the gas side service 8. Disconnect the manifold gauge, and mount both the
port. 3-way valve’s caps and the service port caps.
• Use torque wrench to tighten the service port nut to a
4. Air purging of the charge hose. torque of 18 N.m.
• Open the Low pressure side valve of manifold gauge • Be sure to check for gas leakage.
slightly to purge air from the charge hose.
5. Set the liquid side (High side) 3-way valve to the close
position.
56
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
(Re-installation)
Procedure:
1. Remove the cap nut from 3-way valves. 5. Check for gas leakage.
• Remove the cap nut from 3-way valves after carefully • Check the flare connections for gas leakage.
checked whether the piping connection was properly
and certainly done.
6. Discharge the refrigerant.
• Close the valve on the gas cylinder and discharge the
2. Confirm that valve in both 3-way valves are set to the refrigerant until the gauge indicates 0.1 to 0.3 MPa.
CLOSE.
4. Air purging.
• Open the valve on the gas cylinder.
• Open the valve on the manifold gauge, discharge for
three seconds and wait for one minute. Repeat this
three times.
57
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Procedure:
1. Confirm that both the 3-way valves are set to the open
position.
58
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
11.2.5. Evacuation
Procedure:
1. Connect the vacuum pump to the manifold gauge’s
centre hose.
59
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
(After Evacuation)
Procedure:
1. Connect the charge hose to the gas charging cylinder. 4. Immediately disconnect the charge hose from the
• Connect the charge hose which you disconnected from 3-way valve’s service port.
the vacuum pump to the valve at the bottom of the • Stopping partway will allow the refrigerant to be
cylinder. discharged.
• If the system has been charged with liquid refrigerant
2. Purge the air from the charge hose. while operating the air conditioner, turn off the air
conditioner before disconnecting the hose.
• Open the valve at the bottom of the cylinder and press
the check valve on the charge set to purge the air. (Be
careful of the liquid refrigerant). The procedure is the 5. Mount the valve caps and the service port caps.
same if using a gas cylinder. • Use a torque wrench to tighten the service port nut.
• Be sure to check for gas leakage.
3. Open the valve (Low side) on the charge set and charge
the system with liquid refrigerant.
• If the system cannot be charged with the specified
amount of refrigerant, it can be charged with a little at a
time (approximately 150g each time) while operating the
air conditioner in the cooling cycle; however, one time is
not sufficient, wait approximately 1 minute and then
repeat the procedure. (pumping down-pin)
60
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
12 Servicing Information
12.1. Indoor Electronic Controllers Removal Procedures
• Open the Intake Grille and remove the screw at the front
of the Front Grille. (Fig. 1).
• Remove the 3 caps and 3 screws at the bottom of the
Front Grille. (Fig. 1)
• Remove the Front Grille by releasing the 3 hooks at the
top of the Front Grille. (Fig. 1)
Fig. 1
Fig. 2
Fig. 4
61
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
12.2. Cross Flow Fan Indoor and Fan Motor Removal Procedures
Fig. 5
2. Pull out the Drain Hose from outlet to remove the Discharge
Grille. (Fig. 6)
Fig. 6
Fig. 7
Fig. 8
62
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
Fig. 9
8. Push up the Evaporator and pull out the Cross Flow Fan
from shaft. By then, Fan Motor can be taken out. (Fig. 10).
Fig. 10
63
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
When the batteries are inserted for the first time, or the
batteries are replaced, all the indications will blink and the
remote control might not work.
If this happen, remove the cover of the remote control and
you will find a resetting terminal, and by shorting it with a
minus screwdriver, it will return to normal.
64
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
13 Troubleshooting Guide
13.1. Refrigeration cycle system
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table on the right.
65
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
13.1.1. Relationship between the condition of the air conditioner and pressure and
electric current
Cooling Mode Heating Mode
Condition of the air
conditoner Low Pressure High Pressure Electric current Low Pressure High Pressure Electric current
during operation during operation
Insufficient refrigerant
(gas leakage)
Heat radiation
deficiency of the
outdoor unit
Inefficient compression
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
• Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor • The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
• The difference between high pressure and low pressure becomes almost zero.
• Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
• The compressor is a humming sound.
• Electric current during operation becomes approximately 80% lower than the normal value.
Insufficient switches of the 4-way valve
• The temperature different between from the discharge tube to the 4-way valve and from
suction tube to the 4-way valve becomes almost zero.
66
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
14 Technical Data
67
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
68
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
69
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
70
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
15 Exploded View
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
71
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
(Note)
• All parts are supplied from MACC, Malaysia (Vendor Code: 086).
• “O” marked parts are recommended to be kept in stock.
• (1) — CS-A18BKP, CS-A24BKP (Europe).
• (2) — CS-A18BKP-2, CS-A24BKP-2 (Oceania).
• (3) — CS-A18BKP-3, CS-A24BKP-3 (Argentina).
• (4) — CS-A18BKP-6, CS-A24BKP-6 (Turkey).
72
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
17 Exploded View
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
73
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
(Note)
• All parts are supplied from MACC, Malaysia (Vendor Code: 086).
• “O” marked parts are recommended to be kept in stock.
• (1) — CU-A18BKP5, CU-A24BKP5 (Europe).
• (2) — CU-A18BKP5-2, CU-A24BKP5-2 (Oceania).
• (3) — CU-A18BKP5-3, CU-A24BKP5-3 (Argentina).
• (4) — CU-A18BKP5-6, CU-A24BKP5-6 (Turkey).
74
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
• CS-A18BK / CU-A18BK
• CS-A24BK / CU-A24BK
TEST R54 1k
PC01 TLP620 R52 1.82k
R50 47k C16 0.01µ 1 4
R48
BLU + C09 10k
DEICE 10µ c Q001
1 1 R55
(BLU) 50V
2 3 1k b
2 2
R51 47k
3 3
BZ
4 4 R53
BZ01
1k e
HOT
YLW
(RED)
BLK TO OUTDOOR
WHT
RY-HOT
WHT
RED
GRY
BLK
VLT
COIL
(4-WAYS VALVE)
AC01
COMPRESSOR
COMP (VLT) AC (WHT) HOT 1 (RED) DEICE (GRY) HOT 2 (BLK) (WHT)
ELECTRONIC 2A
(T 3. 15A L 250V)
CONTROLLER FUSE 01
RED
RY-DEICE
BLU
RY-PWR
FUSE
RY-HOT
C13
CAPACITOR
TF 1
(AIR TEMP.)
SENSOR
RY-OFF
ZNR2
C13 R58
CN-TH (WHT)
1 0.01µ 10k
ZNR3
ZNR4
TF 2
2
Fig. 3 4
RY-H/L
3
3 R59 1k
4 2
(PIPE TEMP.)
FM2 FM1
SENSOR
1
(ORG) (BRW) C22 R68
Fig. 4 0.01µ 10k
RED ORG
POWER SUPPLY
BRW or YLW
BLK AC02
(BLK)
R06
WHT AC03 24k
(WHT)
RECEIVER
(KR-3)
PH302C CN-RCV
8 IN+ VCC1 1 1
330 2
7 IN- OUT 2 3
0.01µ
6 CO VCC2 3 6.3V
0.01µ 47µ
137k
+
–
5 GND FO 4
INDICATOR
8
1 26
(KR-10) RY-PWR
2 25 R08 R028
CN-DISP
Auto 3 24 43 /2W 43 /2W
10
(PH) 4 23
9
1 2 CN-DISP 5 22
8
1 7 6 21
D101
2 6 7 20
D102 RY-HOT
3 5
D103 9
4 4
5 3
D104
6 2
D105
7 1
IC05
A52A20030R
5 4 3 2 1
CN-STM1
5 4 3 2 1 (ZH5)
VERTICAL
75
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
1 2 3 4 5 6 7
CN-MAIN
R11 1k
C01 R34
0.01µ 10k
C17 + C14
47µ 0.1µ
25V
C02
0.01µ
C20 + C11
100µ 0.01µ
16V
R19 D06
R20 D07 R02 20k
R21 D08
R22 D09
R23 D10 R10 10k R47 C23
510 0.1µ
R24 D11
R25 D12 R29 1k
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
C06 R42
P47/A07
P46/A06
P45/A05
P44/A04
P43/A03
P42/A02
P41/A01
P40/A00
P67
P66
P65
P64
P75
P74
P73
P72
1000p 20k
P71 (MB)
1 48
P50/A8
2 RY-PWR DRIVE SIGNAL STEPPING P70 47
P51/A9 MOTOR AUTO OPERATION
R13 430
DRIVE TEST RUN P03/NTP3 46
3 R07 20k
P52/A10 SIGNAL REMOTE CONTROL
R14 620 SOUND
P02/NTP2
4 BUZZER 45
P53/A11
R15 620 TIMER SHORTEN R08 C18 R01
RY-HOT DRIVE P01/NTP1 5.1k 0.022µ 100
5 DISPLAY 44
P54/A12 SIGNAL
R16 620 POWER CLOCK INPUT
6 P00/NTP0 43
P55/A13 R32 X01
R17 430
REMOTE-CONTROL 150k
7 Vcc 42
P56/A14 COMMAND INPUT
IC01 X1 41
8 P57/A15
A52D0022GB15
OSC
X2
9 Vss 40
4.096 MHz
10 VDD IC 39 (47pF X 2)
IC04
C03 +
A52PST600DR
0.01µ 11 P30 XT1 38
1.6V
P17/AN7
P16/AN6
P15/AN5
P14/AN4
P13/AN3
P12/AN2
P11/AN1
P21/S0
P35 16V
Avss
VCC
P36
P23
P24
P25
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Fig. 2
R31
1k
R56
1k
8 JX1
1 26
2 25
R43 1k
5 D1 SK 4
3 24
R09 10k JX2
4 23 RX1
6 D6 CS 3
5 22 R57
6 21 20k 7 GND Vcc 2 JX4
7 20 C05
8 RS R/B 1 0.1µ
9 R41
IC02 24k JX3
A52BR9020F
R37
10k
R40
C04 R30 R33 C08 10k
R38
0.1µ 20k 15k 0.1µ
39k
C15
0.01µ
5 4 3 2 1 4 3 2 1
CN-STM2 (PH) CN-TH
REMOTE CONTROL NO.
5 4 3 2 1 (ZH5)
JX3 JX4 RX1
PIPE TEMP. SENSOR AIR TEMP. SENSOR 0 SHORT SHORT
(20k 3950) (15k 3950) 1 SHORT OPEN
HORIZONTAL 2 OPEN OPEN 10K
Fig. 1 3 SHORT OPEN 10K
76
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
R020
T02
F001 R026 5 9 D101
1 + R019
2 3
R003 L002
3 IC101
FAN MOTOR 4 ZD004 R021
I O
5V
5
R023 R053 C016 R033 C015
6 R018 C016
7 e
Q005
b c D045
Q003
PC001 b +
R114 1 4 c D006 C105
R002 ZD005
R008 D013 C011
R024 R034 R054 e
c
PC004
2 3 1 4 b
R116 IC001
PC002 R048 R047
4 1 e D014
R001 R032 C014 C017 R055 Q006 ZD006 ZD007
2 3
R004
feedback
3 2
R118 PC003
1 4
R115 R005
c D002
b
2 3
Q102 e R006
R117 D003
R007
(PH)
CN103
1
2
3
4
5
6
7 R028
e PC005
R029 4 1
(PH) b
CN101
c
1
2 3 2
3 R113
4 R009
5
e Q001
ZD001 C066 R011
+ 10k
PC006
4.7k b 4 1
R010 c
3 2
R112
77
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
TIMER TABLE
Test Mode
Name Time (When test point Remarks
Short-circuited)
Sleep Mode Waiting 1 hr. 6 sec.
Sleep Mode Operation 8 hrs. 48 sec.
Real Timer 1 hr. 1 min.
10 min. 10 sec.
1 min. 1 sec.
Time Delay Safety Control 2 min. 58 sec. 0 sec.
Forced Operation 60 sec. 0 sec.
Time Save Control 7 min. 42 sec.
Anti-Freezing 4 min. 0 sec.
Auto Mode Judgement 25 sec. 0 sec.
Soft Dry OFF 6 min. 36 sec.
ON 10 min. 60 sec. Soft Dry: 10 min. operation
Cooling 40 sec. 4 sec.
70 sec. 7 sec.
Deodorizing Control 20 sec. 2 sec.
180 sec. 18 sec.
Soft Dry 40 sec. 4 sec.
360 sec. 36 sec.
Comp. Reverse Rotation Detection 5 min. 30 sec. Comp. ON 5 min. and above
2 min. 0 sec.
Comp./ Fan Motor Delay Timer 1.6 sec. 0 sec.
Powerful Mode Operation 15 min. 15 sec.
Random Auto Restart Control 0 ~ 62 sec. 0 ~ 6.2 sec.
4 Way Valve 5 min. 30 sec.
After Deice Ended 30 sec. 3 sec. Comp. OFF after deice
Hotstart Delay Times 4 min. 0 sec.
Hotstart Finish Times 2 min. 0 sec.
78
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
79
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
TOP VIEW
80
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5
BOTTOM VIEW
81
CS-A18BKP CU-A18BKP5 / CS-A24BKP CU-A24BKP5